PG
14
Size (3-bit)
The Size field must be set to 4 (100b).
Precision (3-bits)
The precision field describes what the precision of the temperature filter value. The
filter must be zero (0x00).
Scale (2-bits)
The scale field indicates the temperature scale used, 0 indicate the use of the Celsius
temperature scale and 1 indicates use of the Fahrenheit scale.
Bound Size (3-bits)
The size field indicates the number of bytes used for the temperature filter value. This
field must be one (0x01).
Temperature Filter Lower Bound (8-bit)
The thermostat will report ambient temperature changes for temperature values less
than the lower bound. This field must be between 0F and 124F. By default, this value
is 124F (report all temperature changes).
Temperature Filter Upper Bound (8-bit)
The thermostat will report ambient temperature changes for temperature values
greater than the upper bound. This field must be between 0F and 124F. By default,
this value is 0F (report all temperature changes).