background image

INSTALLATION INSTRUCTIONS

 

 

 

11 

MIN.DISTANCES IN mm

H

A

X

L

Y

X

Y

L

H

1000

410

60

60

B

A

B

200

300

3.4

 

Installing the boiler 

  

 

The appliance must be installed 
exclusively on a flat vertical solid wall 
capable of supporting its weight

  

  The boiler should be fitted within the 

building unless otherwise protected by a 
suitable enclosure i.e. garage or outhouse. 
(the boiler may be fitted inside a cupboard

.

 

  If the boiler is sited in an unheated 

enclosure then it is recommended to leave 
the power on to give frost protection (frost 
protection is active even with on/off switch 
in off position). 

  If the boiler is installed in a room containing 

a bath or shower reference must be made 
to the relevant requirements. 

Note: Flue Terminal Locations must 
also comply with Section 6.9 of 
AS/NZS 5601.1:2010

 

 

In order to allow access to the interior of the 
boiler for maintenance purposes, it is important 
that the necessary clearances indicated in 
figure 1 are respected. To make the installation 
easier, the boiler is supplied with a template to 
enable the pipe connections to be positioned 
prior to fixing the appliance to the wall. 

To install the boiler, proceed as follows (see fig. 
2): 

a.

 

Use a spirit level (of not less than 25 mm 

long) to mark a horizontal line on the wall 
where the boiler is to be fitted.

 

b.

 

Position the top of the  template along the 

line drawn with the level, respecting the 
distances indicated. Then mark the centres 
of the positions of the two wall-plugs or 
anchors. Finally, mark the positions of the 
water and gas pipes. 

c.

 

Remove the template and install the cold 

water pipes, the gas supply pipe and the 
central heating pipes using the fittings 
supplied with the boiler. 

Fix the boiler to the wall using the wall plugs or 
bracket and connect the pipes. 

Fig. 1 

Fig. 2 

Summary of Contents for RS 30 E

Page 1: ...maintenance instructions CE 0694 RS 30 E RAD ING MAN INST 1205 1 DIGITECH AUSTRALIA Technical specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY ENGLISH Instruction Manual for model RS 30 E...

Page 2: ...llation requirements pag 9 3 3 Unpacking pag 10 3 4 Installation boiler pag 11 3 5 Water connections pag 12 3 6 Gas connection pag 13 3 7 Electrical connections pag 14 3 8 Flue connections pag 16 4 Co...

Page 3: ...rised personnel 6 1 General warnings pag 30 6 2 Boiler inspection pag 30 6 3 Accessing the boiler pag 31 6 4 Draining the central heating system pag 32 6 5 Wiring diagrams pag 33 6 6 Troubleshooting p...

Page 4: ...ples plastic bags polystyrene etc must not be left within reach of children in that these items represent a potential hazard and must be disposed of in a responsible manner Before carrying out any cle...

Page 5: ...ndards This fundamental safety requirement must be checked and verified In case of doubt have the electrical system checked by a qualified electrician The manufacturer will not be held liable for any...

Page 6: ...its simplicity the wall mounted appliance is equipped with all the appropriate accessories required to make it a fully independent boiler capable of satisfying domestic hot water production and centra...

Page 7: ...ssure heating bar 3 Min working pressure heating bar 0 3 Dimensions Boiler casing size Width mm 450 Height mm 800 Depth mm 320 Weight net kg 43 Hydraulic connections Central Heating Flow connection Ce...

Page 8: ...GENERAL INFORMATION 5 55 5 G 64 5 HR 80 CWI 102 HF 9 320 720 85 82 280 85 286 82 35 800 130 148 450 2 2 Dimensions HR HEATING RETURN 3 4 HF HEATING FLOW 3 4 G GAS 3 4 CWI COLD WATER INLET 1 2...

Page 9: ...MBER 6 IGNITION ELECTRODE 7 MAIN BURNER 8 CIRCULATING PUMP WITH AIR VENT 9 ELECTRONIC GAS VALVE 10 3 bar PRESSURE RELIEF VALVE 11 SYSTEM DRAIN VALVE 12 ISPECTION FLUE 13 HEATING SENSOR 14 HEATING SAFE...

Page 10: ...VENT 9 AUTOMATIC AIR VENT VALVE 10 3 bar PRESSURE RELIEF VALVE 11 PRESSURE GAUGE 12 FLUE HOOD 13 WATER PRESSURE SWITCH 14 HEATING SENSOR 15 AUTOMATIC BY PASS 16 AIR PRESSURE SWITCH 17 ELECTRIC FAN LEG...

Page 11: ...r Temperature display When the boiler is switched off at the switch on the control panel the word OFF appears on the display The central heating frost protection system nevertheless remain enabled If...

Page 12: ...tallation and should be left with the appliance but do not over ride in anyway statutory obligations 3 2 Installation requirements Please refer to local and national standards in force in the Country...

Page 13: ...of the product Packing materials plastic bags polystyrene nails etc must not be left within reach of children in that these items represent a potential hazard A Place the packed appliance on the floor...

Page 14: ...1 2010 In order to allow access to the interior of the boiler for maintenance purposes it is important that the necessary clearances indicated in figure 1 are respected To make the installation easier...

Page 15: ...and noise coming from the system do not use pipes of reduced diameter short radius elbows or severe reductions in the cross sections of the water passages To facilitate the installation the boiler is...

Page 16: ...inimum of a 22 mm diameter pipe with an uninterrupted supply from meter to boiler and comply with current standards and regulations Check the internal and external seals of the gas supply system A gas...

Page 17: ...nnection to the mains electricity supply must be via a single pole switch with at least 3 millimetres gap between open contacts mounted upstream of the appliance Make sure that the positions of the li...

Page 18: ...connect the wires to the terminal board B as follows Connect the earth wire normally coloured green yellow to the terminal marked with the earth symbol Connect the neutral wire normally coloured blue...

Page 19: ...ies to prevent the penetration of foreign bodies or atmospheric agents ONLY for use with Horizontal concentric flue kit 60 100 mm as per manufacturer s kit No 82101LP ONLY for use with manufacturer s...

Page 20: ...nds to that of the mains supply networks gas electricity water Check that the power supply voltage to the boiler complies with the data plate 230 V 50 Hz and that the live neutral and earth wires are...

Page 21: ...al to 1 2 bar see fig 3 and that the code H2O does NOT appear on the control panel display On completion make sure that the filling tap R is perfectly closed 4 3 Flushing the system Failure to flush a...

Page 22: ...alues The device comes into operation in the following cases The heating water temperature goes below 5 C the burner starts automatically until the water temperature reaches the 30 C The room temperat...

Page 23: ...r ignited if the system still emits noises the operations must be repeated until all the air has been removed Check the pressure in the system If the pressure has fallen re open the filling tap until...

Page 24: ...ry set at 36 x 5 180 8 D H W pump overrun timer Not applicable 00 90 default 18 The overrun timer can be modified Expressed in steps of 5 sec factory set at 18 x 5 90 9 Minimum gas pressure setting 00...

Page 25: ...n 2 Activate the On Off switch while keeping buttons and pressed Wait for P00 to appear on the display 3 Release buttons and 4 Keep button S pressed and use button to select the parameter to modify 5...

Page 26: ...TER 2 GAS SUPPLY 6 Use buttons and to modify the value of the parameter 00 natural gas 01 lpg 7 Press and release button S to confirm The parameter number P02 will appear on the display 8 Switch off t...

Page 27: ...k on again to render the new parameter operative PARAMETER 5 WATER HAMMER PREVENTION Not applicable PARAMETER 6 CENTRAL HEATING TIMER 6 Use buttons and to modify the value of the parameter within the...

Page 28: ...ack on again to render the new parameter operative PARAMETER 8 D H W PUMP OVERRUN TIMER Not applicable 5 3 Regulating the gas pressure PARAMETER 9 MINIMUM GAS PRESSURE SETTING NATURAL GAS 0 22 KPA UNI...

Page 29: ...8 Switch off the appliance and switch it back on again to render the new parameter operative 9 Press button Press button S for 7 seconds until the number 07 flashes on the display chimney sweep funct...

Page 30: ...If a remote control is installed an extra interface board must be installed to control the zone valves Then set the parameter at 01 7 Press and release button S to confirm The parameter number P15 wil...

Page 31: ...MAINTENANCE INSTRUCTIONS 28 5 4 Gas Data Refer to page 4 ADJUSTING POWER OUTPUT GAS PRESSURES KW 19 21 23 25 27 29 NG kpa 0 3 0 37 0 45 0 52 0 6 0 68 ULPG kpa 1 08 1 3 1 55 1 78 2 02 2 25...

Page 32: ...reassembled 6 select the new gas type by changing parameter no 2 see Parameters table 5 1 7 to convert the appliance from L P G to Natural Gas proceed with the min and max gas pressure adjustment 8 in...

Page 33: ...the condition of the combustion chamber and flame When required check that the combustion is correctly regulated and if necessary proceed in line with section Commissioning the boiler Remove and clea...

Page 34: ...ds fig 1 and then up fig 1 Left and right side panel Remove the fixing screws at the front and lower edge of the side panel to remove Grasp the bottom of the panel move it sideways and then upwards to...

Page 35: ...n point and locate the other end of the hose in a suitable drainage system Open the system drain valve see fig 1 Open the air vents on the radiators starting with the highest and moving down the syste...

Page 36: ...e blue brown white black black brown blue orange PRINTED CIRCUIT BOARD DIGITECH SM20019 COD 76677LA blue Key IG Main Switch PA Air Pressure switch TS Safety thermostat SR Heating sensor EV Fan ER Ioni...

Page 37: ...connected place plate A back to position and then the front case panel Connecting the outside temperature sensor Option Connect the wires to the terminal board inside the instrument panel as follows...

Page 38: ...connect the remote controller wires When the wires have been connected place plate A back to position and then the front case panel Connecting the remote controller and the telephone control option C...

Page 39: ...option remote controller board cod 65 00030 Option remote lock out indicator Remote control and zone valves wiring For the installation of a zone valve p c b it is necessary to access the main p c b f...

Page 40: ...HERM Telephone control Terminal block Outside temperature sensor option Option remote lock out indicator Zone valve management option remote controller board cod 65 00030 cod 40 00017 Remote control z...

Page 41: ...overning the correction is reported in figure 1 The selection of the compensation curve is determined by the maximum delivery temperature Tm and the minimum outdoor temperature Te N B The y axis value...

Page 42: ...g REPLACE PART h CONNECT THE IONISATION ELECTRODE WIRE E02 SAFETY THERMOSTAT TRIPPED 95 C i THERMOSTAT MALFUNCTION OR OUT OF CALIBRATION j THERMOSTAT CABLE DISCONNECTED i REPLACE PART j CHECK THE WIR...

Page 43: ...tton deactivates the function The Flue test function operates the boiler at the maximum heating pressure for 15 minutes without any modulation The function is useful for combustion testing 08 Frost Pr...

Page 44: ...THE COMPANY RESERVES THE RIGHT TO APPLY VARIATIONS WITHOUT PRIOR NOTIFICATION NEITHER WILL THE COMPANY BE HELD RESPONSIBLE FOR ANY INACCURACIES IN THIS HANDBOOK DERIVING FROM PRINTING OR TRANSLATION...

Reviews: