2. FIRST START-UP
SUPPOR
T
C
ENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P04
HEATING RUN-UP
THROUGH THIS PARAMETER YOU CAN SET THE TIME, DURING
START-UP PHASE, NECESSARY FOR THE BOILER TO REACH
THE MAXIMUM SET POWER (ON THE HEATING SIDE).
00 - 04
00 = (DISABLED)
01 = 50 SECONDS
02 = 100 SECONDS
03 = 200 SECONDS
(SET BY DEFAULT)
04 = 400 SECONDS
P05
ANTI-WATER HAMMER SELECTION
ONCE THIS FUNCTION IS ENABLED, THE DHW CONTACT WILL
BE DELAYED FOR A TIME EQUAL TO THE SET VALUE.
00 - 20
00 = DISABLED
01 - 20 = THE VALUE IS
EXPRESSED IN SECONDS
P06
DOMESTIC CIRCUIT PRESERVATION FUNCTION
(ONLY FOR ISTANTANEOUS BOILERS)
THROUGH THIS PARAMETER YOU CAN PRESERVE THE
CIRCULATOR THE DIVERTER VALVE IN DOMESTIC POSITION
FOR A PERIOD OF TIME EQUAL TO THE POST-CIRCULATION
(SEE PARAMETER P09), SO AS TO MAINTAIN THE SECONDARY
EXCHANGER HOT.
00 - 01
00 = DISABLED
(SET BY DEFAULT)
01 = ENABLED
P07
HEATING TIMING
THROUGH THIS PARAMETER YOU CAN SET THE MINIMUM
TIME FOR WHICH THE BURNER WILL BE TURNED OFF ONCE
THE HEATING TEMPERATURE REACHED THE USER SET
TEMPERATURE.
00 - 90
VALUE EXPRESSED
IN MULTIPLES OF 5
SECONDS
(PRE-SET AT 36 X 5 = 180
SECONDS)
P08
POST-CIRCULATION HEATING TIMING
THROUGH THIS PARAMETER YOU CAN SET THE PUMP
DURATION OF OPERATION DURING HEATING CYCLE, AFTER
THE MAIN BURNER TURNS OFF DUE TO THE ENVIRONMENT
THERMOSTAT.
00 - 90
VALUE EXPRESSED
IN MULTIPLES OF 5
SECONDS
(PRE-SET AT 36 X 5 = 180
SECONDS)
P09
POST-CIRCULATION DOMESTIC / BOILER TIMING
THROUGH THIS PARAMETER YOU CAN SET THE PUMP
OPERATION DURATION ON THE DOMESTIC CIRCUIT, AFTER
THE TAP IS CLOSED.
00 - 90
VALUE EXPRESSED
IN MULTIPLES OF 5
SECONDS
(PRE-SET AT 24 X 5 = 120
SECONDS)