Mode of Connected device
List box {Master; Slave}, default = "Master"
Mode of connected device: MASTER
Broadcast address
It is possible to set address, which will be handled as a broadcast address while Broadcast =
"On". Default broadcast address of the Modbus RTU protocol is 0.
Mode of connected device: SLAVE
Response timeout
Number { 0 – 8190}, default = 300
The Response timeout parameter controls how long the unit waits for an acknowledgement
frame. The timeout is started when the original frame received from the Radio channel is
transmitted to the connected device (over the serial channel). Transmission of any other frame
to the connected device is temporarily blocked, whilst Response timeout is active. Response
timeout = 0 disables this feature.
7.1.2.3.10. PR2000
PR2000 is an abbreviation for the PROTEUS 2000 SCADA protocol. This protocol is used in Master-
Slave applications.
57
© RACOM s.r.o. – M!DGE3 Cellular Router