background image

7

4.  Make sure the sensor is not   

“seeing” people in other rooms or 

hallways through open doorways. 

Mask the lens in the direction of 

the door. 

5.  Make sure line voltage has not 

browned out below 110 volts. If 

voltage is not adequate sensor will 

not operate properly. 

Lights Turn On Without 

Reason

1. 

Check items #2, 3 & 4 under Lights 

Do Not Turn Off. 

Maintenance & Repair 

A LOS2500 requires no maintenance 

other than keeping the lens area 

clean and free of obstructions. Do not 

attempt to open or repair the unit-

there are dangerous voltages inside 

the case, and no user serviceable 

parts. For repair service, follow your 

warranty instructions.

Lights do Not Turn On

1. 

Check for obstructions between 

sensor and area of acitivity. 

2. 

Check that the bulbs and fixtures 

work. Check wiring against 

diagram. 

3. 

Check that the power is on. 

4. 

Increase sensitivity control to 

maximum. 

Lights Do Not Turn Off

1. 

Check items #1, 2 &3 above. 

2. 

Make sure there is no motion in the 

room for at least 15 minutes. stay 

completely out of the protection 

pattern to avoid activating the unit. 

3. 

Check the room for possible 

sources of infrared energy 

sources within view. Look for 

air conditioners, heaters, fans, 

concentrated or reflected lights, 

moving equipment or machinery 

with heat venting fans (computers, 

copiers, etc). Move the offending 

infrared source, or mask the lens 

facing the source to avoid detecion. 

Reducing sensitivity will also help.

Troubleshooting

Set-up & Adjustment

Time Adjustment

The LOS2500 allows adjustment

of the delay time from 10 seconds to 

15 minutes.  

If no movement is detected for the 

time period selected, the lights turn off. 

The Time Adjustment is factory set for 

5 minutes.

The Time should be reduced only in 

heavy traffic areas such as hallways, 

kitchens, copier rooms, etc. to achieve 

maximum energy savings.

Keep the time setting at maximum in 

large rooms (over 400 sf). 

Sensitivity Adjustment

Adjusting the Sensitivity control

is not normally necessary. It can 

reduce detector sensitivity 5%. Less 

sensitivity may be desired for smaller 

rooms (less than 400 sf).

If the unit is being activated by HVAC 

or other infrared sources (other than 

people), reducing the sensitivity may 

help.

6

Masking the Lens

If the sensor’s location gives it a view 

of other rooms or hallways, lights 

will be turned on when movement 

is detected in these adjacent areas. 

The sensor’s detection zone may be 

restricted by covering a portion of 

the lens with the masking elements 

provided.

Temperature Stabilization

If the sensor was in transit and 

subjected to extreme heat or freezing 

before installation it may take up to 

an hour for the sensor to reach room 

temperature and operate normally. 

Summary of Contents for los 2500

Page 1: ...LOS 2500 SUPER CEILING SENSOR Installation Manual ...

Page 2: ...ensor to eliminate detection through doorway DOORWAY DOORWAY Sensor sees through doorway Sensor s view is limited 2 How large an area does the LOS2500 cover At a 9 mounting height the maximum coverage is 2000 square feet The detection pattern covers 360 degrees from the sensor location in the following pattern The L0S2500 sensor sees infrared heat changes caused by the motion of people within its ...

Page 3: ...r own safety and to prevent damage to the unit turn off ALL power by removing the power fuse or turning off the circuit breaker Please read the entire Installation Manuals before proceeding All wiring should comply with local electrical codes and requires a qualified electrician Make sure the total lighting load connected to the LOS2500 does not exceed the following ratings 120V 277V 3 35hp 6 7hp ...

Page 4: ... machinery with heat venting fans computers copiers etc Move the offending infrared source or mask the lens facing the source to avoid detecion Reducing sensitivity will also help Troubleshooting Set up Adjustment Time Adjustment The LOS2500 allows adjustment of the delay time from 10 seconds to 15 minutes If no movement is detected for the time period selected the lights turn off The Time Adjustm...

Page 5: ... and description of problem If your unit is out of warranty or the damage is unrelated to the original manufacture return your unit directly to us with a check for 20 made payable to RAB Lighting Inc for repair or replacement of the unit Under no circumstances shall we be liable for any incidental or consequential damage arising out of or in connection with the use or performance of this product o...

Reviews: