background image

Locate the LOS2500 where it has 

an unobstructed view of the room, 

particularly the areas normally 

occupied by people.

If people can not see the sensor lens 

from their normal positions in the 

room, the sensor will not detect their 

presence.

High cabinets, walls, columns, doors 

and other obstructions may limit the 

sensors view of the entire room.

If obstructions can be moved the 

sensor will have a better view. If the 

obstructed areas are not normally 

occupied, the sensor will still see 

sufficient activity to operate properly.

Several sensors can be used to cover 

large or oddly shaped rooms.

Selecting A Location:

Avoiding HVAC Turbulence

When Heating, Ventilating or Air 

Conditioning (HVAC) registers turn 

on they create turbulence which can 

cause the sensor to activate. !t is 

important that the sensor and HVAC 

register be separated by at least 4’.

3

DETECTION PATTERN

HVAC REGISTER

minimum 4 ft.

CEILING

FLOOR

If the sensor’s location gives it a view 

of other rooms or hallways, lights will 

be turned on when movement is  

detected in these adjacent areas. 

The sensor’s detection zone may be 

restricted by masking a portion of 

the lens; or move sensor to eliminate 

detection through doorway.

DOORWAY

DOORWAY

Sensor sees 

through doorway

Sensor’s view

is limited

2

How large an area does the

LOS2500 cover?

At a 9’ mounting height, the

maximum coverage is 2000 square

feet. The detection pattern covers

360 degrees from the sensor

location in the following pattern:

The L0S2500 sensor “sees”

infrared heat changes caused by

the motion of people within its

detection zone and turns on lights

automatically.

How long do the lights

stay on?

Lights stay on as long as motion is 

detected. They turn off a short time 

after motion in the detection range 

stops. You can adjust this time from 

10 seconds to 15 minutes. Since the 

lights are only on when needed, and 

the sensor uses a negligible amount of 

power, the savings in energy costs are 

substantial.

How much motion is 

necessary to keep lights on? 

A 6” wave of a hand or head tilt

once every 15 minutes is

sufficient to keep the lights on.

How do you adjust the sensor?

Time delay, sensitivity and photocell 

adjustments are located on the back of

the unit. A red LED indicator on the

front panel shows when motion is

detected and aids installation

testing.

How Do RAB Occupancy Sensors Work?

side view

top view

9’

50’

The LOS 2500 has 3 separate 360º 

detectors. Triple overlapping coverage 

provides super sensitivity and 

reliability.

2152 sq. ft. Coverage area

Summary of Contents for los 2500

Page 1: ...LOS 2500 SUPER CEILING SENSOR Installation Manual ...

Page 2: ...ensor to eliminate detection through doorway DOORWAY DOORWAY Sensor sees through doorway Sensor s view is limited 2 How large an area does the LOS2500 cover At a 9 mounting height the maximum coverage is 2000 square feet The detection pattern covers 360 degrees from the sensor location in the following pattern The L0S2500 sensor sees infrared heat changes caused by the motion of people within its ...

Page 3: ...r own safety and to prevent damage to the unit turn off ALL power by removing the power fuse or turning off the circuit breaker Please read the entire Installation Manuals before proceeding All wiring should comply with local electrical codes and requires a qualified electrician Make sure the total lighting load connected to the LOS2500 does not exceed the following ratings 120V 277V 3 35hp 6 7hp ...

Page 4: ... machinery with heat venting fans computers copiers etc Move the offending infrared source or mask the lens facing the source to avoid detecion Reducing sensitivity will also help Troubleshooting Set up Adjustment Time Adjustment The LOS2500 allows adjustment of the delay time from 10 seconds to 15 minutes If no movement is detected for the time period selected the lights turn off The Time Adjustm...

Page 5: ... and description of problem If your unit is out of warranty or the damage is unrelated to the original manufacture return your unit directly to us with a check for 20 made payable to RAB Lighting Inc for repair or replacement of the unit Under no circumstances shall we be liable for any incidental or consequential damage arising out of or in connection with the use or performance of this product o...

Reviews: