background image

5

Mounting & Installation

The unit will not turn off lights when 

power is initially applied until the time 

delay period (10 secs to 15 minutes) 

has elapsed.  

 

Detection Test

1. Walk to an area of the room where 

normal activity will occur. Remain 

motionless for 5 seconds. This 5 

second period allows the Red LED 

Test Circuit to recharge. Move 

one arm until the LED blinks. This 

indicates that your movement has 

been detected.

2. Move to other areas. Repeat the 

test. Red LED will blink when 

sensor detects movement.

Set-up & Adjustment

Adjusting Photo Control

The photo control allows the LOS2500 

to keep lights on during sunny days or 

to operate only during low light levels.

For operation on sunny days use a 

1/4” screwdriver to turn “photo” arrow 

to sun symbol.

For operation only on days with low 

light levels turn “photo” arrow to moon 

symbol.

PHOTO

TIME

SENS

PHOTO

TIME

SENS

Mounting Holes

LED

Mounting & Wiring 

CAUTION: For your own safety and 

to prevent damage to the unit, turn 

off ALL power by removing the 

power fuse or turning off the circuit 

breaker. 

 

Please read the entire Installation 

Manuals before proceeding.

 

All wiring should comply with local 

electrical codes and requires a 

qualified electrician.

 

Make sure the total lighting load 

connected to the LOS2500 does 

not exceed the following ratings:

120V  

 

277V

3.35hp 

  6.7hp

2000W   Fluorescent 

1500W

2000W Incandescent 

1500W

 

To switch more wattage, install a relay 

to handle the load. 

Switches most types of fluorescent 

and/or incandescent lighting. Instant 

Start fluorescent ballasts may not be 

rated for use with any kind of  

occupancy sensor. However, the 

LOS2500 cannot be used with  

dimmers.

1. 

Place sensor in circuit in front of all 

lights. 

2. 

Connect as shown in wiring  

diagram. 

3. 

Twist on wire nuts. Secure with 

electrical tape. 

4. 

Make “Time” and “Sensitivity” 

adjustments while power is off (see 

section #3) 

5. 

Insert plastic cap in mounting screw 

hole. Apply LightAlert label over 

other screw hole. 

6. 

Mount on box, turn on power. 

Power In

Light

White

Black

Black

Red

White

-

+

Sensor

4

Wiring Diagram

Summary of Contents for los 2500

Page 1: ...LOS 2500 SUPER CEILING SENSOR Installation Manual ...

Page 2: ...ensor to eliminate detection through doorway DOORWAY DOORWAY Sensor sees through doorway Sensor s view is limited 2 How large an area does the LOS2500 cover At a 9 mounting height the maximum coverage is 2000 square feet The detection pattern covers 360 degrees from the sensor location in the following pattern The L0S2500 sensor sees infrared heat changes caused by the motion of people within its ...

Page 3: ...r own safety and to prevent damage to the unit turn off ALL power by removing the power fuse or turning off the circuit breaker Please read the entire Installation Manuals before proceeding All wiring should comply with local electrical codes and requires a qualified electrician Make sure the total lighting load connected to the LOS2500 does not exceed the following ratings 120V 277V 3 35hp 6 7hp ...

Page 4: ... machinery with heat venting fans computers copiers etc Move the offending infrared source or mask the lens facing the source to avoid detecion Reducing sensitivity will also help Troubleshooting Set up Adjustment Time Adjustment The LOS2500 allows adjustment of the delay time from 10 seconds to 15 minutes If no movement is detected for the time period selected the lights turn off The Time Adjustm...

Page 5: ... and description of problem If your unit is out of warranty or the damage is unrelated to the original manufacture return your unit directly to us with a check for 20 made payable to RAB Lighting Inc for repair or replacement of the unit Under no circumstances shall we be liable for any incidental or consequential damage arising out of or in connection with the use or performance of this product o...