background image

QR-25 Series 

Quincy Compressor

52201-107, December 2012 

21 

3501 Wismann Lane, Quincy IL - 62305-3116

Step 13)  Jog  the  starter  switch  to  check  the  rotational  direction  of  the 

compressor.It should agree with the rotation arrow em bossed on 

the compressor sheave.

Step 14)  Check for proper rotation of the cylinder cooling fan (fins inside 

sheave). The fan should blow cooling air across the cylinder.

Initial Starting & Operating

This instruction manual, as well as any instructions supplied by manufacturers 

of supporting equipment, should be read and un derstood prior to starting the 

compressor. If there are any questions regarding any part of the instructions, 

please call your local Quincy distributor, or the Quincy Compressor factory.

When using battery cables to start engine driven units do not use 

more than a total of 40 ft. of #4 gauge cable (GND & HOT).

With the pre­starting checklist completed and satisfied, start the compres­

sor. Watch and listen for excessive vibration and strange noises. If either ex­

ist, stop the compressor. Refer to SECTION 6, 

Troubleshooting

 for help in 

determining the cause of such prob lems.

If  you  are  starting  a  pressure  lubricated  model,  check  the  oil  pressure. 

Compressors  producing  up  to  250  PSIG  of  discharge  air  pressure  should 

maintain  18  to  20  PSIG  of  oil  pressure.  High  pressure  rated  compressors 

producing more than 250 PSIG of discharge air pressure should maintain 22 

to 25 PSIG of oil pressure.

Normally the oil pressure does not need to be adjusted. But if it does, loosen 

the locknut on the adjustment screw located on the left side of the oil pump 

housing (see Fig. 4-1, Oil Pressure Adjustment). Increase the oil pressure by 

turning the adjustment screw clockwise; decrease the oil pressure by turn ing 

the adjusting screw counterclockwise. After adjustment tighten the locknut. 

Check the air receiver pressure gauge or system pressure gauges for 

proper readings. If inadequate or excessive air pressure condi tions exist, 

refer to Section 6 Troubleshooting.

Heat created during the initial startup of a new compressor will cause 

slight expansion of the head(s). This slight expansion crushes the head 

gasket ever so slightly and affects the torque value of the cylinder fasteners 

(capscrews). To ensure optimal performance, Quincy recommends that you 

initially operate the compressor for at least one hour. Shut the compressor 

off and follow precautions outlined in SECTION 5, 

Stopping for Main-

tenance

.  Retorque  the  cylinder  to  head  capscrews  to  the  specifications 

outlined in the parts book corresponding to the Record of Change for your 

compressor after the compressor has cooled.

Observe compressor operation closely for the first hour of opera tion and 

then frequently for the next seven hours. After the first eight hours, monitor 

the compressor at least once every eight hours. If any abnormal conditions 

are witnessed, stop the compressor and correct the problem. After two days of 

operation check belt tension, lubricant level, and inspect the system for leaks.

Pix 1068

Fig. 4-1 

Oil Pressure Adjustment

CAUTION !

Summary of Contents for QR-25 210

Page 1: ...n its entirety and understood prior to installation by all personnel who install operate and or maintain this product Product warranty information is available at www quincycompressor com about warran...

Page 2: ...y Requirements 10 Mounting 10 System Components 11 Wiring Schematics 12 Induction System 14 Compressed Air Discharge System 15 SECTION 4 START UP OPERATION Pre Starting Checklist 20 Initial Starting O...

Page 3: ...truc tionssupplied by manufacturers of supporting equipment should be read and understood prior to starting the compressor If there are any questions regarding any part of the instructions please call...

Page 4: ...t installing a pressure relief valve of proper size and design between the shutoff valve and the compressor Do not use plastic pipe rubber hose or lead tin soldered joints in any part of the compresse...

Page 5: ...y warned that failure to ob serve the safety precau tions and procedures outlined in this manual may result in serious personal injury damage to property and may void your warranty Quincy Compressor m...

Page 6: ...d in the cylinder The air is then compressed in the cylinder during the upstroke of the piston Total compression from atmo spheric pressure to the final discharge pressure is accomplished in one strok...

Page 7: ...eam air piping Compressed air dryers reduce the moisture vapor concentration and prevent water formation in compressed air lines Dryers are a recommended companion to filters aftercoolers and automati...

Page 8: ...e compressor must start more than six 6 times per hour If the demand for compressed air is continuous and exceeds one half or more of the compressor s capacity Control Version S should be used Once th...

Page 9: ...s run control In either situation the hydraulic unloader protects the compressor from excessive damage caused by a drop in oil pressure Specifications Bore s RPM Maximum Model Stroke LP HP Range PSIG...

Page 10: ...motor Do not substi tute with a triple voltage 208 230 460 3 phase motor Step 5 Read the pressure relief valve nameplate to be sure it does not exceed the working pressure shown on the compressor or a...

Page 11: ...ately ventilated and not closer than 24 inches to a wall or another compressor Note A gas engine will produce carbon monoxide always provide adequate ventilation Inspec tion and mainte nance checks ar...

Page 12: ...d disconnect switch should be provided When a 3 phase motor is used to drive a compres sor any unreasonable voltage imbalance between the legs must be eliminated and any low voltage corrected to preve...

Page 13: ...re The customer is responsible for pro viding a suitable foundation isolator mounting where necessary Mounting Mobile Units Units mounted to truck beds should be fas tened in such a way so as not to c...

Page 14: ...UTION Verify all wires are secure and fasteners are torqued before connecting power to the unit All wires are red unless otherwise specified Dashed lines represent wires supplied by others At Installa...

Page 15: ...AUTION Verify all wires are secure and fasteners are torqued before connecting power to the unit All wires are red unless otherwise specified Dashed lines represent wires supplied by others At Install...

Page 16: ...k or compressed air delivery system during main tenance procedures Manual Shutoff Valves Manual shutoff valves block the flow of air pressure in either direction This type of valve can be used to isol...

Page 17: ...ping should be at least the same size or larger in di ame ter as the inlet connection to the compressor For every 10 feet of inlet piping or every 90 bend increase the inlet piping diameter by one pip...

Page 18: ...accident Never join pipes or fittings with lead tin soldering Welded or threaded steel pipes and cast iron fittings designed for the pres sures and temperatures are recommended Pressure Vessels Air re...

Page 19: ...nternal com ponents as a result of condensation A compres sor must operate long enough during each run cycle to reach full operating temperature in order to reduce the risk of condensation Lubricant t...

Page 20: ...the tank to 30 PSIG by pulling the pressure relief valve ring refer to Fig 3 4 Checking Pressure Relief Valves Relieving System Pres sure Step 3 Slowlyopenthedrainvalveandallowthemoistureandairmixture...

Page 21: ...Drain Decal Read and understand the instruction manual WARNING Drain the tank WARNING Condensation could cause rust resulting in reduced wall thickness and risk of explosion Drain the tank daily Visua...

Page 22: ...quantity and types of lubri cant to be used Step 3 Check motor pulley and compressor sheaves for alignment and tightness on shaft Refer to SECTION 5 Pulley Sheave Align ment Belt Tension Step 4 Manual...

Page 23: ...essure Normally the oil pressure does not need to be adjusted But if it does loosen the locknut on the adjustment screw located on the left side of the oil pump housing seeFig 4 1 OilPressureAdjustmen...

Page 24: ...place if necessary Step 3 Drain liquid from the air receiver refer to Section 3 Manually Draining An Air Tank and moisture trap if so equipped Step 4 Jog the starter button and check compressor rotati...

Page 25: ...in valves within the area to be serviced Step 5 Wait for the unit to cool before starting to service Temperatures of 125 F can burn skin Some surface tem pera tures exceed 350 F when the compressor is...

Page 26: ...rs or Monthly Check belt tension Every 500 Hours or Every 3 Months Change oil filter more frequently in harsher environments Torque pulley clamp screws or jamnut Every 1000 Hours or Every 6 Months Whe...

Page 27: ...10W ISO 32 32 80 F SAE 20W ISO 68 60 104 F SAE 30 ISO 100 The lubricant selected must have a pour point at least 15 F lower than the minimum expected ambient temperature Pulley Sheave Alignment Belt...

Page 28: ...ure de flection force Step 3 Lay a straightedge across the top outer surface of a drive belt from pulley to sheave Step 4 At the center of the span perpendicu lar to the belt apply pressure to the out...

Page 29: ...esigned pressure for the system or overload the motor beyond its Maximum Amp Draw Full Load Amps x Service Factor Maximum Amp Draw Never assume a compressor is safe to work on just because it is not o...

Page 30: ...See Fig 5 4 Compressor Directional Arrows and Fig 5 5 Driveshaft Alignment Step 3 Re install the six 6 housing bolts and torque them in a star or cross pattern to specifications outlined in the parts...

Page 31: ...ded maximum pressure will void the warranty and may cause personal injury Setting Unload Pressure Step 1 Flip the toggle to the RUN position as shown or turn the knurled knob if so equipped coun tercl...

Page 32: ...incorrectly sized for the alti tude it is operating at Piston rings not seated allow 100 hours at full pressure Water in the crankcase Compressordoesnotrunlongenoughtogethotandvaporizetheliquids lubri...

Page 33: ...ompressor loads Air receiver too small and unloads excessively Compressor valves or unloaders defective Excessive system leakage Compressor operating at incorrect speed Unloader pilot differential set...

Page 34: ...mpressor valves Pressure setting too high Clogged intercooler internally or exter nally Inadequate ventilation or recirculation of hot air Pulley sheave rotation wrong Incorrect speed Running clearanc...

Page 35: ...mum Loose electrical connection amper age allowed multiply Wire size too small the FLA on the motor Incorrect lubricant nameplate by the service Discharge pressure too high factor Intercooler plugging...

Page 36: ...6 0 915 0 902 0 890 8000 0 962 0 945 0 925 0 900 0 886 0 873 9000 0 957 0 938 0 915 0 887 0 868 0 857 10000 0 951 0 931 0 902 0 872 0 853 0 840 11000 0 945 0 923 0 891 0 858 0 837 12000 0 938 0 914 0...

Page 37: ...125 36 5 37 0 33 0 35 0 43 5 43 5 41 0 150 38 0 38 5 34 0 36 5 46 0 45 5 43 0 175 39 5 40 0 35 0 38 0 48 5 47 5 45 0 200 41 0 41 5 36 0 39 0 51 5 49 0 47 0 225 42 0 43 0 37 0 40 5 53 5 51 0 48 5 250...

Page 38: ...QR 25 Series Quincy Compressor 52201 107 December 2012 36 3501 Wismann Lane Quincy IL 62305 3116 Typical QR 25 Unit with Vertical Receiver Typical QR 25 Unit with Horizontal Receiver Decal Locations...

Page 39: ...QR 25 Series Quincy Compressor 52201 107 December 2012 37 3501 Wismann Lane Quincy IL 62305 3116 Typical Engine Driven QR 25 Unit with Horizontal Receiver...

Page 40: ...irty 30 days after receipt of notification of readiness for shipment Claims for shortages will be deemed to have been waived if not made in writing with ten 10 days after the receipt of the material i...

Page 41: ...al provided with Quincy Compressor products as well as any instructions supplied by manufacturers of supporting equipment should be read and understood prior to performing maintenance NOTE Make your e...

Page 42: ......

Page 43: ...Reciprocating Systems 217 222 7700 Air Master 217 277 0270 E mail info quincycompressor com Website quincycompressor com...

Reviews: