Ref.
Description
M1
Refrigerant compressor
M5
Fan motor 1
M6
Fan motor 2
PT20
Pressure sensor, condenser pressure
Q3
Circuit breaker, transfo
Q4
Circuit breaker, control voltage
Q5
Circuit breaker, fan motor
Q8
Circuit breaker, electronic regulator
S0
Main switch (customer's installation)
S1'
Remote start-stop switch
S2
High pressure switch
S3
Flow switch
T1
Transformer, control voltage
TT89
Temperature sensor, refrigerant temperature
TT90
Temperature sensor, LAT in airflow
TT91
Temperature sensor, ambient
Y1
Solenoid valve
1X0
Terminal strip, supply
1X3
Terminal strip, earthing
1X5
Terminal strip, < or = 24 VAC
1X6
Terminal strip, < or = 24 VDC
1X7
Terminal strip, alarm contacts
1X10
Electronic regulator ethernet connection
Dryer protection
The unit is provided with a phase sequence relay (K25).
The high-pressure shut-down switch (S1) stops the compressor motor when the pressure in the
refrigerant circuit reaches the upper set-point of the switch.
After tripping:
• The switch must be reset manually by pressing its reset knob and by pressing reset key (//)
on the regulator (electronic regulator).
The compressor motor has a built-in thermic protection. If the thermic protection trips, the
compressor motor will be stopped. The compressor will restart when the motor windings have
cooled down, which may take up to 3 hours.
Instruction book
36
2920 1992 00
Summary of Contents for QED-1250
Page 2: ......
Page 6: ...8 2 AIR DRYER DATA 108 9 Pressure equipment directives 112 Instruction book 4 2920 1992 00 ...
Page 15: ...Position of components Air cooled dryer Water cooled dryer Instruction book 2920 1992 00 13 ...
Page 17: ...Connections Rear view of Air cooled dryer Instruction book 2920 1992 00 15 ...
Page 31: ...Electrical diagram air cooled QED 1800 ES870 Instruction book 2920 1992 00 29 ...
Page 32: ...Electrical diagram air cooled QED 2100 ES1010 Instruction book 30 2920 1992 00 ...
Page 36: ...Electric cubicle air cooled QED 2100 ES1010 380 V and 460 V Instruction book 34 2920 1992 00 ...
Page 86: ...Dimension drawing air cooled QED 1600 ES760 Instruction book 84 2920 1992 00 ...
Page 87: ...Dimension drawing air cooled QED 1800 ES870 Instruction book 2920 1992 00 85 ...
Page 88: ...Dimension drawing air cooled QED 2100 ES1010 Instruction book 86 2920 1992 00 ...
Page 89: ...Dimension drawing water cooled QED 1250 ES610 Instruction book 2920 1992 00 87 ...
Page 90: ...Dimension drawing water cooled QED 1600 ES760 Instruction book 88 2920 1992 00 ...
Page 91: ...Dimension drawing water cooled QED 1800 ES870 Instruction book 2920 1992 00 89 ...
Page 95: ...Installation proposal water cooled dryer Instruction book 2920 1992 00 93 ...
Page 115: ......