Section VIII - Technical data
51
Cable sizing according UL/cUL
Calculation method according UL 508A, table 28.1 column 5: allowable ampacities of
insulated copper conductors (75 °C (167 °F)).
Maximum allowed current in function of the wire size:
AWG or kcmil
Maximum current
10
< 30 A
8
< 50 A
6
< 65 A
4
< 85 A
3
< 100 A
2
< 115 A
1
< 130 A
1/0
< 150 A
2/0
< 175 A
3/0
< 200 A
Calculation method for UL:
Single supply cables (3 1 PE - configuration (1)):
Add 25 % to the total current from the tables (see UL 508A 28.3.2: "Capacity shall
have 125 % of the full load current")
Install the prescribed maximum fuse on each cable
Parallel supply cable (2 x 3 2 PE - configuration (2)):
Add 25 % to the total current from the tables and divide by 2
Multiply the capacity of the cables with 0.8 (see UL 508A table 28.1 continued)
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 phase + 2 PE as in (3):
Add 25 % to the total current from the tables and divide by √3
Multiply the capacity of the cables with 0.8 (see UL 508A table 28.1 continued)
Fuse size: the recommended maximum fuse size divided by √3 on each cable.
Size PE cable:
For supply cables up to AWG8: same size as the supply cables
For supply cables larger than AWG8: use maximum allowed capacity
< 100 A: Use AWG8
< 200 A: Use AWG6
< 300 A: Use AWG4
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).
Example of supply cable calculation: Itot = 128 A, maximum ambient temperature is 45
°C, recommended fuse = 150 A
Single supply cables (3 1 PE - configuration (1)):
I = 128 A + 25 % = 128 x 1.25 = 160 A
For AWG2/0, the maximum current is 175 A, which is sufficient => use AWG2/0
Install the prescribed maximum fuse (150 A) on each cable
Parallel supply cable (2 x 3 2 PE - configuration (2)):
Summary of Contents for QCV 045
Page 2: ...This page intentionally left blank...
Page 21: ...Section III Installation 21 Dimension drawing QCV 045 QCV 90 vacuum pump...
Page 22: ...Section III Installation 22 Dimension drawing QCV 220 vacuum pump...
Page 23: ...Section III Installation 23 Dimension drawing QCLP 90 Overpressure pumps...
Page 24: ...Section III Installation 24 Dimension drawing QCLP 220 Overpressure pump...
Page 55: ...Notes 55...