8 48008002-06
11. Once the unit is fitted in position remove the float valve assembly from the drain tray unscrew the self tapping screw in the
drain tray and use it to secure the float switch bracket in position on the end of the drain tray. To ease fitting the float
switch can be slid out of the plastic fixing bracket fit as shown in Fig. 5
Fig. 5
12. It is important that the float switch sits level when the fan coil unit is fully installed and that the open end of the vent pipe is
higher than the water level in the drip tray.
13. The drain pipe from the condensate pump must be run to a common drain.
It is important that any condensate pump installed must be in accordance with the
manufacturer’s requirements.
Fig. 6
14. It is recommended to use flexible duct connections when connecting to sheet metal ductwork.
15. All connecting ductwork must be independently supported before connecting to the fan coil spigots.
16. Ensure all actuator heads are correctly fitted to the valves.
Typical valve assembly with actuators fitted.
These can be four way or two way valves
depending on specification of unit.
Fig. 7
Cable Tie
Float Switch Bracket
Float Switch
Vent Pipe
Vent Pipe