11.  Once the unit is fitted in position remove the float valve assembly from the drain tray unscrew the self tapping screw in the 

drain tray and use it to secure the float switch bracket in position on the end of the drain tray. To ease fitting the float 
switch can be slid out of the plastic fixing bracket fit as shown in Fig. 5 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 5 

 
 

12.  It is important that the float switch sits level when the fan coil unit is fully installed and that the open end of the vent pipe is 

higher than the water level in the drip tray. 

 
 

13.  The drain pipe from the condensate pump must be run to a common drain. 

  

It is important that any condensate pump installed must be in accordance with the 

manufacturer’s requirements. 

 
 

                                             

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

   

Fig. 6 

 
 

14.  It is recommended to use flexible duct connections when connecting to sheet metal ductwork. 
15.  All connecting ductwork must be independently supported before connecting to the fan coil spigots. 
16.  Ensure all actuator heads are correctly fitted to the valves. 

 
 
 
 
 

 

Typical valve assembly with actuators fitted. 

 

 

These can be four way or two way valves 

 

 

 depending on specification of unit. 

 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 7                                                                            

                 

Cable Tie 

Float Switch Bracket 

Float Switch 

Vent Pipe 

Vent Pipe 

Summary of Contents for Amber Series

Page 1: ...Units Designed for Ceiling or Void Mounting INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS TEV Ltd Armytage Road Brighouse West Yorkshire United Kingdom HD6 1QF UK Tel 01484 405630 Fax 01484 405620...

Page 2: ...e used 4 It is manually isolated from the electrical mains supply 5 Electrical equipment is earthed to comply with IEE regulations and local by laws 6 All electrical work must be carried out by a Qual...

Page 3: ...ntation 5 Filters 5 INSTALLATION Dimensional details 6 Pre Unit Installation 7 Fitting unit 7 Fitting float switch 7 9 Connection of ductwork 9 COMMISIONING Airside Measuring and Balancing 10 Electric...

Page 4: ...s AC Speed control of the fan motors is achieved by means of a multitapped auto transformer which is wired to a three speed and fine adjustment switches Supplied with continuous filament media filters...

Page 5: ...aged Maintenance It is essential that the following instructions as laid down in this section are carried out and maintained during the period of storage before commissioning Internal Surfaces If duct...

Page 6: ...B Spigot Options Weight approx Kg AMB 1 630 595 1 2 3 4 37 AMB 2 880 845 1 2 3 4 45 AMB 3 1230 1195 1 2 3 4 5 55 AMB 4 1230 1195 1 2 3 4 5 60 AMB 5 1430 1395 1 2 3 4 5 70 AMB 6 1430 1395 1 2 3 4 5 75...

Page 7: ...unit up using a spirit level checking to ensure the unit sits level in both directions the drip tray is designed with a built in fall to ensure condensation runs to the drain connection 7 Use nuts and...

Page 8: ...nt pipe is higher than the water level in the drip tray 13 The drain pipe from the condensate pump must be run to a common drain It is important that any condensate pump installed must be in accordanc...

Page 9: ...Typical installation showing ductwork connected to unit The ducts should be pushed fully over the spigot up to the outer casing of the unit and secured to the spigot with screws once fitted they shou...

Page 10: ...ation of the condensation pump by pouring a small amount of water into the drain tray and ensure the pump clears any water and operates any alarms etc 13 Start the fan and blow through the system thor...

Page 11: ...ice and maintenance of Quartz fan coil units and must be read before any maintenance is attempted WARNING It is essential that before any work is carried out the unit is isolated externally from the e...

Page 12: ...ws and slide element upwards letting the screw head pass through the key hole slots 5 Remove wires from element take note of terminal connections used 6 Remove elements from the unit must be replaced...

Page 13: ...irty filters will reduce the air volume handled by the unit thus adversely affecting its performance The length of time between cleaning of filters is dependant upon the environment A six to twelve mo...

Page 14: ...emperatures Alternatively Electric Heating elements are available and can be supplied wired for single phase or three phase supply as appropriate or as specified Multiple units fitted on the same syst...

Reviews: