background image

                                                                                                10                                                                              48008002-06 

 

 
COMMISSIONING

 

 
Once units are fully installed they must be commissioned to ensure they have been correctly fitted in accordance with 
manufacturer’s instructions. 

Isolate mains supply before  

 

1.  Check that the unit is fitted correctly and all supporting drop rods are secure and lock nuts have been tightened.  
2.  Ensure that all the unit sections are thoroughly clean and free from any installation debris. 
3.  Check the coil faces are clean and free from dust; check all the water connections to the coil for leaks. 
4.  Ensure all air is vented from both coils and the system independently 
5.  Check the filters to make sure they are clean and free from dust and correctly fitted. 
6.  Ensure all access panels and blanking plates are securely fixed in position. 
7.  Check that all actuators are securely fitted to the correct valves. 
8.  Check electrical work to ensure it complies with BS7671 and that the necessary safety and isolating devises have been 

fitted.[refer to wiring diagram supplied with the unit ] 

9.  Use manual air vents to vent any air trapped in the coil. 

                                            

 

 
 
                     Manual Air Vents 
 
 
                                                                        
                                

 
 
 
 
                                                        
 
 
 
 

 

 

 

 

 

 

Fig. 9 

 

 

 

 

 

R/H pipe work connections shown 

 
 

 
 
 
 
 

10.  Check the condensation drain tray for debris and remove any if found. 
11.  Pour some water into the drain tray to verify the free flow of water. 
12.  Units with condensation pumps fitted check the operation of the condensation pump by pouring a small amount of water 

into the drain tray and ensure the pump clears any water, and operates any alarms etc. 

13.  Start the fan and blow-through the system thoroughly. 
14.  Before operating Electric Air Heaters[if fitted] the air flow through the unit should be established. 
15.  Check the air volume and external pressure is as specified. Adjust air volume as necessary using speed selector and fine 

adjustment switches. 

16.  Check the motor full load current. Nameplate denotes full load current at speed 6 [NR40]. Nameplate value to be unit max 

current value. 

17.  Check the on/off temperature across the coil and adjust water flow accordingly. 
18.  Check the function of the controls and [water flow temperatures.] 
19.  After initial start up and continuous running of the unit it is recommended that the following checks are carried out, 

 

 

a] Motor full load current.    

 

 

b] Condition of filter. 

 

 

 

c] Condensate and drains for free flow and leaks. 

 

 

 

d] Operation of controls.    

20.  AC motor units, there is a fan speed switch to give three main speeds and a fine adjustment switch for adjusting fan motor 

speed. 

21.  On EC / DC motor units the speed control must not exceed 10.0Vdc and be capable of supporting a 2mAmp Load 

 

 

AIRSIDE MEASURING AND BALANCING 

 
The most accurate air side measurement for air volume and balancing are obtained by taking readings with an anemometer 
traverse across the inlet to the fan coil unit. 

Flow connection heating 

Return connection heating 

Flow connection cooling 

Return connection cooling 

Summary of Contents for Amber Series

Page 1: ...Units Designed for Ceiling or Void Mounting INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS TEV Ltd Armytage Road Brighouse West Yorkshire United Kingdom HD6 1QF UK Tel 01484 405630 Fax 01484 405620...

Page 2: ...e used 4 It is manually isolated from the electrical mains supply 5 Electrical equipment is earthed to comply with IEE regulations and local by laws 6 All electrical work must be carried out by a Qual...

Page 3: ...ntation 5 Filters 5 INSTALLATION Dimensional details 6 Pre Unit Installation 7 Fitting unit 7 Fitting float switch 7 9 Connection of ductwork 9 COMMISIONING Airside Measuring and Balancing 10 Electric...

Page 4: ...s AC Speed control of the fan motors is achieved by means of a multitapped auto transformer which is wired to a three speed and fine adjustment switches Supplied with continuous filament media filters...

Page 5: ...aged Maintenance It is essential that the following instructions as laid down in this section are carried out and maintained during the period of storage before commissioning Internal Surfaces If duct...

Page 6: ...B Spigot Options Weight approx Kg AMB 1 630 595 1 2 3 4 37 AMB 2 880 845 1 2 3 4 45 AMB 3 1230 1195 1 2 3 4 5 55 AMB 4 1230 1195 1 2 3 4 5 60 AMB 5 1430 1395 1 2 3 4 5 70 AMB 6 1430 1395 1 2 3 4 5 75...

Page 7: ...unit up using a spirit level checking to ensure the unit sits level in both directions the drip tray is designed with a built in fall to ensure condensation runs to the drain connection 7 Use nuts and...

Page 8: ...nt pipe is higher than the water level in the drip tray 13 The drain pipe from the condensate pump must be run to a common drain It is important that any condensate pump installed must be in accordanc...

Page 9: ...Typical installation showing ductwork connected to unit The ducts should be pushed fully over the spigot up to the outer casing of the unit and secured to the spigot with screws once fitted they shou...

Page 10: ...ation of the condensation pump by pouring a small amount of water into the drain tray and ensure the pump clears any water and operates any alarms etc 13 Start the fan and blow through the system thor...

Page 11: ...ice and maintenance of Quartz fan coil units and must be read before any maintenance is attempted WARNING It is essential that before any work is carried out the unit is isolated externally from the e...

Page 12: ...ws and slide element upwards letting the screw head pass through the key hole slots 5 Remove wires from element take note of terminal connections used 6 Remove elements from the unit must be replaced...

Page 13: ...irty filters will reduce the air volume handled by the unit thus adversely affecting its performance The length of time between cleaning of filters is dependant upon the environment A six to twelve mo...

Page 14: ...emperatures Alternatively Electric Heating elements are available and can be supplied wired for single phase or three phase supply as appropriate or as specified Multiple units fitted on the same syst...

Reviews: