ELM & ELM2 EMERGENCY LIGHTING UNIT RECALL INSPECTION & CIRCUIT BOARD REPLACEMENT INSTRUCTIONS | 8
Destroy recalled circuit boards by breaking
the three-pronged edge connectors that extend
from the middle of one of the long edges of the
board, making the circuit board inoperable.
Then discard any remaining wire(s) attached.
NOTE: ELM2 circuit boards will be discarded
with yellow, blue and red wires attached as
shown in the photo to the right.
ELM circuit boards will be discarded with only the
red wire attached.
Destroy and discard recalled circuit board:
F
7TH STEP:
INSTALLING THE NEW CIRCUIT BOARD:
Use needle-nosed pliers to connect the blue wire
terminal by plugging it securely onto the circuit
board (BAT BLUE) terminal. Replacement boards
will be blue.
Connect the blue battery wire connector:
A
ELM2 units only: Connect the two blue and
yellow wire lamp connectors. The connectors
should lock together by engagement of the top
latch.
ELM units only: Disconnect the blue and yellow
lamp leads on each side of the new, blue circuit
board and discard them.
Connect the lamp connectors
(Blue and Yellow wire harnesses):
B