F. Equivalent Feet of Pipe 

The table below can help you calculate the equivalent feet 

of pipe which is a method used to determine pellet vent 

size (

Figure 16.1).

Example of 3 Elbow-Rear Vent Termination Calculation

Table 16.2

3 in. or 4 in. (76mm or 

102mm)  Diameter   Pipe 

3 in. or 4 in. (76mm or 

102mm)  Diameter   Pipe 

Equivalent Pipe 

Length In Feet

Equivalent Pipe 

Length In Feet

ALTITUDE IN THOUSANDS OF FEET

ALTITUDE IN THOUSANDS OF FEET

0

20

30

   

1        2       3       4       5       6        7       8        9     10

4 in. (102mm) Diameter Pipe Only

4 in. (102mm) Diameter Pipe Only

10

Example 1

Example 1

Example 2

Example 2

Example 1

: If the equivalent length of pipe is 23 feet (7m) 

with altitude of 8,000 feet (2438m) you must use 4 inch 

(102mm) diameter type “L” or “PL” vent.

Example 2

: If the equivalent length of pipe is 12 feet (3.7m) 

with altitude of 6,000 feet (1829m) you may use 3 or 4 inch 

(76 to 102mm) diameter type “L” or “PL” vent.

Figure 16.1

Table 16.1

2 ft. 

2 ft. 

3 ft. 

2 ft. 

Pellet 

Venting 

Component

# of 

Elbows

Feet 

of 

Pipe

Multiplied 

By

Equivalent 

Feet

Components

Equivalent 

Feet

90° Elbow or 

Tee

3

X

5

15

45° Elbow

X

3

Horizontal 

Pipe

7

X

1

7

Vertical Pipe

2

X

0.5

1

Total Equivalent Feet

23

NOTE:

 This is a generic example and is not intended to represent any specific 

fuel type.

G. Pipe Selection Chart

The chart will help you in determining proper venting 

size according to the equivalent feet of pipe calculated 

previously and the altitude above sea level of this 

installation 

(Figure 16.2)

.

1. 

Locate the calculated equivalent feet of pipe on the 

vertical left side of the chart.

2.  Move to the right horizontally on the chart until you 

reach your altitude above sea level.

3. 

If you fall below the diagonal line, 3 or 4 inch (76 to 

102mm) pipe may be used.

4.  If it is anywhere above the diagonal line, a 4 inch 

(102mm) diameter pipe is required.

NOTICE:

• 

A 90° elbow is 5 times as restrictive to the flow of 

exhaust gases under positive pressure as 1 foot 

(305mm) of horizontal pipe.

•  A foot of horizontal pipe is twice as restrictive as a 

foot of vertical pipe.

Risk of Injury or Property Damage.

•  Improper installation, adjustment, 

alteration, service or maintenance can 

cause injury or property damage.

•  Refer to the owner’s information manual 

provided with this appliance.

• 

For assistance or additional information 

consult a qualified installer, service 

agency or your dealer.

WARNING

Vent surfaces get HOT, can cause burns 

if touched. Non-combustible shielding or 

guards may be required.

WARNING

Risk of Fire!

• 

Only LISTED venting components may 

be used.

• 

NO OTHER vent components may 

be used.

•  Substitute or damaged vent components 

may impair safe operation.

WARNING

Summary of Contents for SANTA FE SANTAFE-C

Page 1: ...e could result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Do not over fire If ap...

Page 2: ...6 5 Venting Systems A Through The Wall 17 B Vertical into Existing Class A Chimney 18 C Through The Wall Vertical Exterior 18 D Vertical Interior Typical Installation 18 E Masonry 19 F Alternate Mason...

Page 3: ...er operation It is against federal regulations to operate this pellet appliance in a manner inconsistent with operating instructions in this manual Emissions Report Number 0061PM077E EPA Certification...

Page 4: ...f such fuels can expose you to chemicals including carbon black which is known to the State of California to cause cancer and carbon monoxide which is known to the State of California to cause birth d...

Page 5: ...to installation Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdicti...

Page 6: ...on to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements C Tools And Supplies Needed Tools and building supplies normally required...

Page 7: ...n and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appli...

Page 8: ...1mm 28 3 4 in 730mm 9 7 8 in 251mm 12 3 4 in 324mm 3 3 4 in 95mm 6 7 8 in 175mm 2 1 2 in 64mm Figure 8 3 Top View with Top Vent Adapter TPVNT 2 and Offset Adapter 812 3570 Figure 8 2 Top View with Top...

Page 9: ...set Adapter 812 3570 18 1 4 in 464mm 21 in 533mm 16 3 4 in 427mm 28 3 4 in 730mm 26 7 8 in 653mm Figure 9 2 Side View with Top Vent Adapter TPVNT 2 and Offset Adapter 811 0720 Figure 9 4 Side View wit...

Page 10: ...rner Installation Inches Millimeters G Side Wall to Appliance Corner 2 51 H Side Wall to Flue Pipe 3 76 Installations with TPVNT 2 Top Vent Adapter w Heat Shield Clean out TPVNT 6 Top Vent Adapter wit...

Page 11: ...area to the wall thimble 152MM FUEL DOOR OPENING USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under the...

Page 12: ...um Inches Millimeters Inches Millimeters A Height 43 1092 n a n a B Width 38 965 n a n a C Depth n a n a 36 914 D To Side Wall 6 152 n a n a Figure 12 2 NOTE Illustrations reflect typical installation...

Page 13: ...ences and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted i...

Page 14: ...ance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pel...

Page 15: ...vertically or horizontally NOTE Follow venting manufacturers recommendations for sealing pipe joints NOTICE Hearth Home Technologies assumes no responsibility for the improper performance of the chimn...

Page 16: ...t intended to represent any specific fuel type G Pipe Selection Chart The chart will help you in determining proper venting size according to the equivalent feet of pipe calculated previously and the...

Page 17: ...or mobile home installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage throu...

Page 18: ...76mm Minimum Cleanout Cover 12 in 305mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit All three installations are a...

Page 19: ...oncrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Non combustible Hearth Pad Airtight Clean out Door Sheathing 2 in 51mm Minimum Flashing 1 in 25mm Clearance 1 in 25mm Clearance with Fi...

Page 20: ...ps head screwdriver wire cutters hole saw or jig saw 1 Measure distance from floor to air vent opening in appliance and mark location on wall Use a saw to cut opening in wall Cut a 2 1 2 to 3 inch 64...

Page 21: ...e silicone on the 3 inch 76mm exhaust outlet Do not put silicone inside of pipe Figure 21 1 2 Slide the adapter onto the rear exhaust outlet and adjust the assembly to the appropriate position 3 Insta...

Page 22: ...see Figure 22 4 TERMINAL BLOCK CENTER 2 SCREWS FOR THERMOSTAT WIRES POWER OUTLET Figure 22 1 Figure 22 2 Figure 22 3 1 Separate the body of the thermostat from the mounting plate by gently pulling the...

Page 23: ...PART NUMBER 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 23 1 WARNING Products of combustion generate carbon monoxide and different fue...

Page 24: ...24 09 20 7050 801E SANTA FE FREESTANDING 8 Reference Materials A Service and Maintenance Log Date of Service Performed By Description of Service...

Page 25: ...25 09 20 7050 801E SANTA FE FREESTANDING Date of Service Performed By Description of Service...

Page 26: ...apter 90 Cleanout TPVNT 6 Vent Adapter Rear 811 0620 Damper 3 inch PEL DAMP3 Y Damper 4 inch PEL DAMP4 Additional service part numbers appear on following page IMPORTANT THIS IS DATED INFORMATION Part...

Page 27: ...of 24 226 0130 24 Y Pin 3 16 x 1 2 7000 229 Rivet Iron 1 4 X 1 1 4 Pkg of 25 229 0090 25 Screw 8 32 X 1 4 Qty 40 225 0240 40 Screw Hwh 1 4 20 X 3 4 Ns Pkg of 25 220 0080 25 Y Screw Flat Head Screw 1 4...

Page 28: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Reviews: