background image

15

09/20

7050-801E

SANTA FE FREESTANDING

C. Negative Pressure

Negative pressure results from the imbalance of air available 

for the appliance to operate properly. It can be strongest in 

lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)

•  Range hoods
•  Combustion air requirements for furnaces, water 

appliances and other combustion appliances

•  Clothes dryers

•  Location of return-air vents to furnace or air conditioning

•  Imbalances of the HVAC air handling system
•  Upper level air leaks such as: 

-  Recessed lighting

-  Attic hatch

-  Duct leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion appliances 

and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed
•  Attic mounted duct work and air handler joints and seams 

taped or sealed

D. Draft

Draft is the pressure difference needed to vent an appliance 

successfully. When an appliance is drafting successfully, all 

combustion byproducts are exiting the home through the 

chimney.
Install through the warm airspace enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

Considerations for successful draft include:

•  Preventing negative pressure
•  Location of appliance and chimney

E. Chimney and Exhaust Connection

1. 

Chimney & Connector: 

Use  3  or  4  inch  (76-102mm) 

diameter type “L” or “PL” venting system. It can be vented 

vertically or horizontally.

NOTE:

 

Follow venting manufacturers recommendations 

for sealing pipe joints.

NOTICE:

 Hearth & Home Technologies assumes no 

responsibility for the improper performance of the 

chimney system caused by:

•  Inadequate draft due to environmental conditions

•  Down drafts

•  Tight sealing construction of the structure

•  Mechanical exhausting devices

NOTE:

 The appliance exhaust outlet is designed to 

accommodate 3 inch venting. Use of 4 inch venting 

requires the use of a 3-to-4 inch exhaust vent increaser 

in addition to any other venting components needed, sold 

separately.

Risk of Asphyxiation!

Negative pressure can cause spillage of combustion 

fumes and soot

WARNING

2. 

Mobile Home: 

Approved  for  all  Listed  pellet  vent.  If 

using  the  3  inch  (76mm)  vertical Top  Vent Adapter  Kit 

or the 3 to 6 inch (76-152mm) Top Vent Offset Adapter, 

use  Listed  double  wall  flue  connector.  A  Quadra-Fire 

Outside Air Kit must be used with manufactured home 

installations.

3. 

Residential: 

The  3  inch  (76mm)  vertical  Top  Vent 

Adapter Kit and the 3 to 6 inch (76 to 152mm) Top Vent 

Offset Adapter are tested to use 24 gauge single wall flue 

connector or Listed double wall flue connector to Class 

A Listed metal chimneys, or masonry chimneys meeting 

International Residential Code standards for solid fuel 

appliances.

4. 

INSTALL VENT AT CLEARANCES SPECIFIED BY 

THE VENT MANUFACTURER.

5.  Seal exhaust venting system to the unit with High Temp 

500ºF RTV silicone sealant. Secure the venting system 

to the unit with at least (3) screws. All pellet vent pipe 

must be secured together either by means provided by 

the pipe manufacturer or by (3) screws at each joint.

6.  DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST 

VENTING SYSTEM OF THIS Appliance.

7.  DO  NOT  CONNECT  THIS Appliance  TO A  CHIMNEY 

FLUE SERVING ANOTHER APPLIANCE.

USE 

ONLY 

RECOMMENDED 

VENTING 

COMPONENTS;  OTHERWISE  MAKESHIFT  PARTS 

MAY  RESULT  IN  PROPERTY  DAMAGE,  PERSONAL 

INJURY, OR DEATH.

WARNING

Summary of Contents for SANTA FE SANTAFE-C

Page 1: ...e could result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Do not over fire If ap...

Page 2: ...6 5 Venting Systems A Through The Wall 17 B Vertical into Existing Class A Chimney 18 C Through The Wall Vertical Exterior 18 D Vertical Interior Typical Installation 18 E Masonry 19 F Alternate Mason...

Page 3: ...er operation It is against federal regulations to operate this pellet appliance in a manner inconsistent with operating instructions in this manual Emissions Report Number 0061PM077E EPA Certification...

Page 4: ...f such fuels can expose you to chemicals including carbon black which is known to the State of California to cause cancer and carbon monoxide which is known to the State of California to cause birth d...

Page 5: ...to installation Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdicti...

Page 6: ...on to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements C Tools And Supplies Needed Tools and building supplies normally required...

Page 7: ...n and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the appli...

Page 8: ...1mm 28 3 4 in 730mm 9 7 8 in 251mm 12 3 4 in 324mm 3 3 4 in 95mm 6 7 8 in 175mm 2 1 2 in 64mm Figure 8 3 Top View with Top Vent Adapter TPVNT 2 and Offset Adapter 812 3570 Figure 8 2 Top View with Top...

Page 9: ...set Adapter 812 3570 18 1 4 in 464mm 21 in 533mm 16 3 4 in 427mm 28 3 4 in 730mm 26 7 8 in 653mm Figure 9 2 Side View with Top Vent Adapter TPVNT 2 and Offset Adapter 811 0720 Figure 9 4 Side View wit...

Page 10: ...rner Installation Inches Millimeters G Side Wall to Appliance Corner 2 51 H Side Wall to Flue Pipe 3 76 Installations with TPVNT 2 Top Vent Adapter w Heat Shield Clean out TPVNT 6 Top Vent Adapter wit...

Page 11: ...area to the wall thimble 152MM FUEL DOOR OPENING USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under the...

Page 12: ...um Inches Millimeters Inches Millimeters A Height 43 1092 n a n a B Width 38 965 n a n a C Depth n a n a 36 914 D To Side Wall 6 152 n a n a Figure 12 2 NOTE Illustrations reflect typical installation...

Page 13: ...ences and protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted i...

Page 14: ...ance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional ventilation to the space in which the pel...

Page 15: ...vertically or horizontally NOTE Follow venting manufacturers recommendations for sealing pipe joints NOTICE Hearth Home Technologies assumes no responsibility for the improper performance of the chimn...

Page 16: ...t intended to represent any specific fuel type G Pipe Selection Chart The chart will help you in determining proper venting size according to the equivalent feet of pipe calculated previously and the...

Page 17: ...or mobile home installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage throu...

Page 18: ...76mm Minimum Cleanout Cover 12 in 305mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit All three installations are a...

Page 19: ...oncrete Cap 1 in 25mm Clearance with Firestop 6 in 152mm Minimum Non combustible Hearth Pad Airtight Clean out Door Sheathing 2 in 51mm Minimum Flashing 1 in 25mm Clearance 1 in 25mm Clearance with Fi...

Page 20: ...ps head screwdriver wire cutters hole saw or jig saw 1 Measure distance from floor to air vent opening in appliance and mark location on wall Use a saw to cut opening in wall Cut a 2 1 2 to 3 inch 64...

Page 21: ...e silicone on the 3 inch 76mm exhaust outlet Do not put silicone inside of pipe Figure 21 1 2 Slide the adapter onto the rear exhaust outlet and adjust the assembly to the appropriate position 3 Insta...

Page 22: ...see Figure 22 4 TERMINAL BLOCK CENTER 2 SCREWS FOR THERMOSTAT WIRES POWER OUTLET Figure 22 1 Figure 22 2 Figure 22 3 1 Separate the body of the thermostat from the mounting plate by gently pulling the...

Page 23: ...PART NUMBER 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 23 1 WARNING Products of combustion generate carbon monoxide and different fue...

Page 24: ...24 09 20 7050 801E SANTA FE FREESTANDING 8 Reference Materials A Service and Maintenance Log Date of Service Performed By Description of Service...

Page 25: ...25 09 20 7050 801E SANTA FE FREESTANDING Date of Service Performed By Description of Service...

Page 26: ...apter 90 Cleanout TPVNT 6 Vent Adapter Rear 811 0620 Damper 3 inch PEL DAMP3 Y Damper 4 inch PEL DAMP4 Additional service part numbers appear on following page IMPORTANT THIS IS DATED INFORMATION Part...

Page 27: ...of 24 226 0130 24 Y Pin 3 16 x 1 2 7000 229 Rivet Iron 1 4 X 1 1 4 Pkg of 25 229 0090 25 Screw 8 32 X 1 4 Qty 40 225 0240 40 Screw Hwh 1 4 20 X 3 4 Ns Pkg of 25 220 0080 25 Y Screw Flat Head Screw 1 4...

Page 28: ...maintenance instructions included Read understand and follow these instructions for safe installation and operation Leave this manual with party responsible for use and operation of this appliance We...

Reviews: