background image

10/08

Page  5

Quadra-Fire  •  Hudson Bay  •  7003-121 Rev. i

NOTE:

 The following requirements reference various 

Massachusetts and national codes not contained in this 
document.

For all side wall horizontally vented gas fueled equipment 
installed in every dwelling, building or structure used in whole 
or in part for residential purposes, including those owned or 
operated by the Commonwealth and where the side wall 
exhaust vent termination is less than seven (7) feet above 
fi nished grade in the area of the venting, including but not 
limited to decks and porches, the following requirements 
shall be satisfi ed:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 
gas fueled equipment, the installing plumber or gas fi tter shall 
observe that a hard wired carbon monoxide detector with an 
alarm and battery back-up is installed on the fl oor level where 
the gas equipment is to be installed. In addition, the installing 
plumber or gas fi tter shall observe that a battery operated or 
hard wired carbon monoxide detector with an alarm is installed 
on each additional level of the dwelling, building or structure 
served by the side wall horizontal vented gas fueled equip-
ment. It shall be the responsibility of the property owner to 
secure the services of qualifi ed licensed professionals for the 
installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled 
equipment is installed in a crawl space or an attic, the hard 
wired carbon monoxide detector with alarm and battery back-
up may be installed on the next adjacent fl oor level.

In the event that the requirements of this subdivision can not 
be met at the time of completion of installation, the owner shall 
have a period of thirty (30) days to comply with the above 
requirements; provided, however, that during said thirty (30) 
day period, a battery operated carbon monoxide detector with 
an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance 
with the above provisions shall comply with NFPA 720 and 
be ANSI/UL 2034 listed and IAS certifi ed.

Signage

A metal or plastic identifi cation plate shall be permanently 
mounted to the exterior of the building at a minimum height 
of eight (8) feet above grade directly in line with the exhaust 
vent terminal for the horizontally vented gas fueled heating 
appliance or equipment. The sign shall read, in print size no 
less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

H.  Requirements for the Commonwealth of     
      Massachusetts

Inspection

The state or local gas inspector of the side wall horizontally 
vented gas fueled equipment shall not approve the installa-
tion unless, upon inspection, the inspector observes carbon 
monoxide detectors and signage installed in accordance with 
the provisions of 248 CMR 5.08(2)(a) 1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a) 
1 through 4:

The equipment listed in Chapter 10 entitled “Equipment 
Not Required To Be Vented” in the most current edition of 
NFPA 54 as adopted by the Board; and 

Product Approved side wall horizontally vented gas fueled 
equipment installed in a room or structure separated from 
the dwelling, building or structure used in whole or in part 
for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall 
horizontally vented gas fueled equipment provides a vent-
ing system design or venting system components with the 
equipment, the instructions provided by the manufacturer for 
installation of the equipment and the venting system shall 
include:

Detailed instructions for the installation of the venting sys-
tem design or the venting system components; and 

A complete parts list for the venting system design or 
venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall hor-
izontally vented gas fueled equipment does not provide the 
parts for venting the fl ue gases, but identifi es “special vent-
ing systems”, the following requirements shall be satisfi ed by 
the manufacturer:

The referenced “special venting system” instructions shall 
be included with the appliance or equipment installation 
instructions; and 

The “special venting system” shall be Product Approved 
by the Board, and the instructions for that system shall 
include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved 
side wall horizontally vented gas fueled equipment, all vent-
ing instructions, all parts lists for venting instructions, and/or 
all venting design instructions shall remain with the appli-
ance or equipment at the completion of the installation.

See Gas Connection section for additional Common-
wealth of Massachusetts requirements.

Summary of Contents for Hudson Bay Direct Vent Gas Appliance...

Page 1: ...n manufactured home USAonly or mobile home and must be installed in accordance with the manufacturer s instructions and the manufactured home con struction and safety standard Title 24 CFR Part 3280 o...

Page 2: ...TEMENTS LES MEUBLES LA GAZOLINE ET LES AUTRES LIQUIDES DE VAPEUR INFLAMMABLE LOIGN S CAUTION DO NOT OPERATE THIS APPLIANCE WITH GLASS REMOVED CRACKED OR BROKEN REPLACEMENT OF THE PANEL S SHOULD BE DON...

Page 3: ...on 12 G Vertical Termination 15 Section 6 Gas Information A Fuel Conversions 22 B Gas Pressures 24 C Gas Connection 25 Section 7 Electrical Information A Recommendation for Wire 26 B Connecting to the...

Page 4: ...Home installation may occur only after the home is site located and must conform with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or when such a standard is not appli...

Page 5: ...st vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF AL...

Page 6: ...o tective surface Remove log set and component pack from firebox Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before startin...

Page 7: ...ions in manual WARNING B Clearances Figure 3 1 NOTE Flooring beneath appliance may reach 90 degrees plus room ambient temperature Check with flooring manufacturer for maximum temperature allowed on fl...

Page 8: ...Measure horizontal clearances from this surface See Figure 4 4 for specific clearances Opening HORIZONTAL OVERHANG VERTICAL WALL GAS DIRECT VENT TERMINATION CAP 12 X ROOF PITCH IS X 12 LOWEST DISCHARG...

Page 9: ...__________________________________________ _ _ QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMA X...

Page 10: ...flue WARNING Diagonal runs have both vertical and horizontal vent aspects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect See Figure 5 1 Two 45...

Page 11: ...914mm VERTICAL DISTANCE FROM APPLIANCE TO TO THE 90 ELBOW TOTAL HORIZONTAL RUN TO OUTSIDE OF EXTERIOR WALL INCLUDING ELBOWS EX 2 EX 1 11 2 4 6 8 10 12 14 15 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 0...

Page 12: ...r installation instructions Connect vent sections per installation instructions Maintain all clearances to combustibles Do NOT allow vent to sag below connection point to appliance Maintain specified...

Page 13: ...tic around its outside edges so as to make a seal between it and the wall attach termination cap to the exterior wall with the four wood screws provided The arrow on the vent cap should be pointing up...

Page 14: ...hment from the vent pipe to the vent termination cap must be sealed with silicone Termination caps shall not be recessed into a wall or siding FOLD STRAP HERE WALL THIMBLE COVER CEILING FIRESTOP AS RE...

Page 15: ...for required 1 in 25mm clearances air space to combustibles when passing through ceilings walls roofs enclosures attic rafters or other nearby combustible surfaces See page 17 Figure 5 16 Check the in...

Page 16: ...outlined in the current CAN CGA B149 Installation Codes in Canada the National Fuel Gas Code NFPA 54 ANSI Z223 1 in USA or local codes Note that for steep roof pitches the vent height must be increase...

Page 17: ...sheetrocked with standard construction materials however refer to these installation instructions for the minimum allowable clearance between the outside of the vent pipe and the combustible surfaces...

Page 18: ...p edges of the support box to make a seal between it and the roof Clean out any combustible material from inside the support box Step 7 Complete the cathedral ceiling installation by following the sam...

Page 19: ...nto the ceiling support box center the retro connector and attach it to the support box with sheet metal screws Step 7 The connection between the appliance and the retro connector may be completed wit...

Page 20: ...framed a wall thimble is required This allows the retro connector to mount directly on the masonry and provide the correct clearances to combustibles Figure 5 25 Step 4 To determine the length of flex...

Page 21: ...Figure 5 25 page 20 If needed add a section of direct vent pipe to the retro connector in order to extend through the opening in the wall thimble cover Step 8 Secure the top adapter to the flashing U...

Page 22: ...t and socket Figure 6 2 Lift burner up and out of the firebox opening Figure 6 3 Remove the three screws on the front of the burner support Set screws aside Figure 6 4 Slide the burner support to the...

Page 23: ...rn off gas supply to unit before proceeding if converting fuel on an appliance already fully installed WARNING Figure 6 5 With a 5 8 in wrench remove the orifice retaining nut Replace with appropriate...

Page 24: ...LP Minimum Inlet Pressure 4 5 inches w c 11 0 inches w c Maximum Inlet Pressure 7 0 inches w c 14 0 inches w c Manifold Pressure on HI 3 5 inches w c 10 0 inches w c WARNING Verify inlet pressures Hi...

Page 25: ...d and Commonwealth of Massachusetts approved 1 2 inch 13mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 inch 13mm control valve inlet If substituting for these co...

Page 26: ...ostat 5 Use the following chart for wire sizing 6 Keep wire lengths as short as possible by removing any excess wire length 7 Low voltage and 110 VAC voltage cannot be shared within the same wall box...

Page 27: ...improper and dangerous operation Verify proper operation after servicing Shock hazard Replace damaged wire with type 105O C rated wire Wire must have high temperature insulation CAUTION RED 28 IN 711...

Page 28: ...all fingerprint oils from the gold or nickel surface of crown PRIOR to lighting the appliance Figure 8 1 Open lower access panel Pull out and unhook the two spring latches on the bottom of the applian...

Page 29: ...f firebox Holding against heat exchangers slide baffle towards front of appliance D Grille Installation Figure 8 5 Following instructions stated above remove the door of appliance Remove the four scre...

Page 30: ...still breakable the logs do not become fragile until after the appliance is burned and they have cured After curing any handling must be done with care as breakage can easily occur PLEASE NOTE Logs h...

Page 31: ...he right rear log and the left front log G Mineral Wool Follow ember placement instructions in manual Do NOT place embers directly over burner ports Replace ember material annually Explosion Risk WARN...

Page 32: ...om the bracket The blower motor comes standard with two male spade wire connectors If your appliance has a different con nection use the two female spade wire connectors pro vided to modify the applia...

Page 33: ...a horizontal termination After adjustment tighten nut to lock in place K Glass Replacement 1 Turn off gas to appliance 2 Remove door from the appliance and set on a protec tive surface 3 Remove door c...

Page 34: ...that there are no gas leaks Ensure that the glass is sealed and in the proper posi tion Ensure that the flow of combustion and ventilation air is not obstructed front grilles and vent caps B Controls...

Page 35: ...the power from the appliance 4 Open the door of the appliance May need to remove face front first 5 Push in gas control knob slightly and turn clockwise to the OFF position Do not force 6 Wait five 5...

Page 36: ...detectors Smoke and odors may be irritating to sensitive individuals CAUTION Prevent accidental appliance operation when not attended Unplug or remove batteries from remote control if absent or if app...

Page 37: ...e thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocoupl...

Page 38: ...ng exhaust gases back into the system Check for proper vent connection at flue collar and all vent joints c Horizontal vent improperly pitched The horizontal vent cap should slope down only enough to...

Page 39: ...ching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL...

Page 40: ...as neces sary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for...

Page 41: ...ence Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For clearances refer to Section 3 Figure 12 1 Appliance Dimensions Location Inches Millim...

Page 42: ...n 184 mm 7 1 4 in 184 mm 5 1 4 in 133 mm 25 1 4 in 641 mm 37 1 4 in 946 mm 49 1 4 in 1251 mm 13 1 4 in 337 mm 13 1 4 in 337 mm 6 5 8 in 168 mm 6 5 8 in 168 mm 6 5 8 in 168 mm 6 5 8 in 168 mm SLP45 SLP...

Page 43: ...ling Firestop SLP WS Wall Firestop SLP HVS Pipe Support Hanger 950 Vinyl Protector Kit SL Pipe DRC RADIUS Decorative Radius Cover HTI DV WT Wall Thimble RF4 8 Roof Flashing TERMINATION KITS SLP TRAP2...

Page 44: ...03 121 Rev i D Service Parts List R HUDBAY FS Service Parts Diagram Part number list on following page Log Set Assembly Hudson Bay Free Standing 1 2 3 4 5 6 10 9 8 7 Beginning Manufacturing Date April...

Page 45: ...0110 10 Valve Cover 7003 119 Adaptor Inner 4 200 2470 Adaptor 6 5 8 7000 162 Brick Retainer 479 0190 Electrode EZ Flush 42 842 4580 Y Fan Deflector 468 0190 Flex Line 3 8 comp x 30 200 2940 Y Flex Lin...

Page 46: ...0730 Y 3 Piezo Ignitor 291 513 Y 4 Knob On Off 571 534 Y 5 Knob Hi Lo 571 533 Y 6 Valve NG 842 0240 Y Valve LP 842 0230 Y Valve Bracket 7003 118 7 Latch Assembly Qty 2 reg 7003 005 Y 8 Blower 812 490...

Page 47: ...ble under this warranty is limited to the purchase price of the product In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product Adjustments regular...

Page 48: ...ed and approved by HHT in writing This warranty does not apply to non HHT venting components hearth components or other accessories used in conjunction with the installation of this product This warra...

Page 49: ...___________ Hudson Bay Direct Vent Gas Appliance Do NOT discard this manual CAUTION Important operating and maintenance instructions included Read understand and follow these instruc tions for safe in...

Reviews: