August 3, 2015
7038-206E
21
5700 STEP TOP
30-1/8 in.
(765mm)
59 - 1/2 in.
(1511mm)
53 - 7/8 in.
(1368mm)
16
(FRONT
DOOR OPENING)
33-5/8 in.
(854mm)
16 in. from glass
8 in.
Fuel loading door
33-5/8 in.
minimum
44-7/8 in.
minimum
8 in.
Figure 21.3
Figure 21.1
Figure 21.2
Figure 21.4
fuel loading door. Open the door and measure 8 inches
(203mm) from the side edge of the opening in the face of the
appliance. *
See exception.
In Canada,
it is necessary to install a fl oor protector of a
minimum of 1 inch (k=0.49, R value= 2.04) of non-combus-
tible material a minimum of 18 inches (457 mm) in front and
8 inches (203 mm) from the sides and rear of the appliance.
*
See exception.
*EXCEPTION:
Non-combustible floor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
Figure 21.4.
Fire Risk
.
Hearth pads must be installed exactly as specifi ed.
High temperatures or hot embers may ignite
concealed combustibles.
WARNING
USA
203mm (8 in.)
203mm
(8 in.)
203mm
(8 in.)
457mm (18 in.)
1429mm
(56-1/4 in.)
minimum
1092mm (43 in.)
minimum
Must extend 2 in.
(51mm) beyond
each side of pipe
(shaded area)
CANADA
USA
NOTE:
•
Illustrations and photos refl ect typical installations and are
FOR DESIGN PURPOSES ONLY.
•
I
llustrations/diagrams are not drawn to scale.
•
Actual installation may vary due to individual design
preference
•
Hearth & Home Technologies reserves the right to alter its
products.
Corner hearth pad dimensions with single
and double wall pipe