background image

August 3, 2015   

 

 

 

           7038-206E 

 

 

 

         

                  11

5700 STEP TOP

Chimney Systems

NOTE: I

n Canada when using a factory-built chimney it must be 

safety listed,

 Type UL103 HT (2100

o

F) CLASS “A” 

or conform-

ing to 

CAN/ULC-S629M, STANDARD FOR 650

o

C FACTO-

RY-BUILT CHIMNEYS.

A.  Venting Systems 

The venting system consists of:

•  A chimney connector (also known as fl ue or stove pipe) 
• A 

chimney

• Thimble

These get extremely hot during use.  Temperatures inside 
the chimney may exceed 2000

F (1100

C) in the event of a 

creosote fi re.

To protect against the possibility of a house fi re:

•  Chimney connector and chimney 

must be properly 

installed and maintained.

• 

An approved thimble must be used when a connection is 
made through a combustible wall to a chimney.

•  A chimney support package must be used when a 

connection is made through the ceiling to a factory built 
chimney.

•  An approved thimble and chimney support package are 

absolutely necessary

 to provide safe clearances to 

combustible wall and

 

ceiling material.

Thimble 

A thimble is a manufactured or site-constructed device 
installed in combustible walls through which the chimney 
connector passes to the chimney.

•  It is intended to keep the walls from igniting.
•  Site constructed thimbles must meet NFPA 211 Standards.
•   Factory-built must be suitable for use with selected 

chimney and meet UL103 Type HT Standards.

•  Follow instructions provided by the manufacturer for 

manufactured thimbles for masonry chimney and factory- 
built chimneys.

Air Clearances

 • Masonry chimney clearance must meet NFPA 211 mini-

mum requirement of 2 inches (51mm) to sheet metal sup-
ports and combustibles.

 • Minimum of 1 inch (25mm) clearance around the chim-

ney connector.

 • Top of wall opening is a minimum of 13-1/2 inches 

(343mm) from ceiling or 4-1/2 inches (114mm) below 
minimum clearance specifi ed by chimney connector 
manufacturer.  NFPA 211 minimum vertical clearance of 
18 inches (457mm) from chimney connector and ceiling 
or minimum recommended by chimney connector manu-
facturer.  

Figure 11.1.

Instructions:

1.  Open inside wall at proper height for the chimney con-

nector to entry the masonry chimney. 

 Figure 11.1

2.  Entry hole to masonry chimney must be lined with an 8 

inch (203mm) minimum diameter clay liner, or equiva-
lent, secured with refractory mortar.

3.  Construct a 17 inch x 17 inch (432mm x 432mm) outside 

dimension frame from 2 x 2 framing lumber to fi t into wall 
opening.  Inside opening of frame should be no less than 
14 inch x 14 inch (356mm x 356mm).  

Figure 11.1.

4.  Attach the wall spacer to the chimney side of the frame.

5.  Nail the frame into the wall opening.  The spacer should 

be on the chimney side.

6.  Insert the section of the solid insulated chimney into the 

outer wall of the masonry chimney.

7.  Tightly secure the length of the solid insulated chimney 

with the wall band to the masonry chimney.

8.  Insert a section of chimney connector into the chimney.  

Make sure it does not protrude past the edge of the clay 
chimney liner inside the chimney.

9.  Seal the end of the chimney connector to the clay liner 

with refractory mortar.

10.  Install trim collar around the sold pack chimney section.

Figure 11.1

1.5”

1.0” 

2.0”

2.0”

1.5”

14.0” ID

17.0” OD

ceiling

Minimum18.0” 

NFPA 211

13.5” below ceiling to top 
of opening

1.0”

8.0”

1.5   2x2 framing stud

2.0   min air clearance

1.0   min air clearance
4.5

or top of opening is a min.of 
4.5” below min.clearance 
specified by connector mfg.

Center of Hole

Thimble

C

L

C

L

Wall

Include depth 
of hearth pad

Summary of Contents for 57ST-ACC

Page 1: ... or chimney con nector glows you are overfiring Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies recommends NFI certified professionals or technicians supervised by an NFI certified professional WARNI...

Page 2: ...e Safety 4 C Negative Pressure 5 D Tools And Supplies Needed 5 E Inspect Appliance and Components 5 F Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearances to Combustibles 8 C Locating Your Stove Chimney 9 D Chimney Termination Requirements 9 E 2 10 3 Rule 10 4 Chimney Systems 11 A Venting Systems 11 B Chimney Systems 12 C Chimney Height Rise and Run 12 D Installi...

Page 3: ...nded to the frame of the mobile home and use only listed double wall connector pipe Outside Air Kit part OAK ACC must be installed in a mobile home installation D Glass Specifications This stove is equipped with 5mm ceramic glass Replace glass only with 5mm ceramic glass Please contact your dealer for replacement glass Improper installation adjustment alteration service or maintenance can cause in...

Page 4: ...tructions and be sure to maintain regularly 2 A conveniently located Class A fire extinguisher to contend with small fires resulting from burning embers 3 A CO detector should be installed in the room with the appliance 4 A practiced evacuation plan consisting of at least two escape routes 5 A plan to deal with a chimney fire as follows In the event of a chimney fire a Evacuate the house immediate...

Page 5: ...ts Report damaged parts to dealer To minimize the effects of negative air pressure Install the outside air kit with the intake facing prevailing winds during the heating season Ensure adequate outdoor air for all combustion appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the appliance Avoid installing the appliance near...

Page 6: ...m height requirements Roof flashing installed and sealed Terminations installed and sealed Clearances Section 3 Pg 7 Combustible materials not installed in non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installation manual requirements Protective hearth strips and hearth extension installed per manual requirements Applia...

Page 7: ... 32 3 8 in 822mm 30 1 4 in 768mm 18 in 458mm 13 1 2 in 343mm 33 7 8 in 861mm 14 15 16 in 380mm 9 3 16 in 233mm 26 1 16 in 662mm 21 1 16 in 535mm 17 1 8 in 435mm 29 7 8 in 760mm 27 9 16 in 700mm 6 11 16 in 170mm Back of Stove to Glass Figure 7 3 Front View Figure 7 4 Side View 5700 Pedestal Model 5700 Leg Model 3 Dimensions and Clearances A Appliance Dimensions NOTE Flue Collar size is 6 inch 152mm...

Page 8: ...81 2 51 15 381 45 1143 N A DOUBLE WALL PIPE A B C and D dimensions are based off of certification clearances Stove pipe manufacture clearances MUSt be adhered to if they exceed certified unit clearances DOUBLE WALL PIPE 12 1 2 318 7 1 2 191 28 1 2 724 15 381 2 51 15 381 45 1143 N A INSTALLATION Horizontal with Minimum 2 Foot Vertical Off Stove Top SINGLE WALL PIPE 12 1 2 318 7 1 2 191 28 1 2 724 1...

Page 9: ...all through the warm space enclosed by the build ing envelope This helps to produce more draft espe cially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the affects of wind turbulence and down drafts Consider the appliance location in order to avoid floor and ceiling attic joists and rafters Locate termination cap away from trees adjacent structures...

Page 10: ...3 ft 91cm Minimum Wall or Parapet Flat Roof E 2 10 3 Rule These are safety requirements and are not meant to assure proper flue draft This appliance is made with a 6 inch 152mm diameter chimney connector as the flue collar on the unit Changing the diameter of the chimney can affect draft and cause poor performance It is not recommended to use offsets and elbows at altitudes above 4000 feet above s...

Page 11: ...mm clearance around the chim ney connector Top of wall opening is a minimum of 13 1 2 inches 343mm from ceiling or 4 1 2 inches 114mm below minimum clearance specified by chimney connector manufacturer NFPA 211 minimum vertical clearance of 18 inches 457mm from chimney connector and ceiling or minimum recommended by chimney connector manu facturer Figure 11 1 Instructions 1 Open inside wall at pro...

Page 12: ...ustibles Chimney Connector Fire Clay Flue Liner with Airspace Masonry Chimney Wall Band to Secure Chimney Section Wood Studs Used for Framing Spaced 2 inch 51mm clearance from Masonry Chimney Wall Spacer Solid Pack Chimney with Metal Supports as a Thimble Figure 12 1 The Listed connectors must conform to each other to ensure a proper fit and seal C Chimney Height Rise and Run This product was desi...

Page 13: ...ust meet the following minimum requirements Must be a 6 inch 152mm diameter ID high temperature chimney listed to UL 103 HT 2100o F or ULC S629M Must use components required by the manufacturer for installation Must maintain clearances required by the manufacturer for installation Refer to manufacturers instructions for installation Floor Protector Chimney Connector Ceiling Support Listed Chimney ...

Page 14: ...g Joist Combustible Wall Airtight Cleanout Door Fireclay Flue Liner With Air Space Sheathing Eave 1 in 25mm Clearance With Firestop Rafter Flashing Concrete Cap Outside Air Termination Cap Outside Air Rear Vent Spark Arrestor Cap F Masonry Chimney WARNING ONLY use connector Within the room between appliance and ceiling or wall Connector shall NOT pass through Attic or roof space Closet or similar ...

Page 15: ...to darken and produce excessive creosote 2 It is recommended that a chimney with a larger diameter than 6 inches 152mm be relined The oversized flue can cause poor performance and contribute to the accumulation of creosote 3 Have the chimney cleaned before the stove is installed and operated The following bullets list the more critical requirements for a properly constructed chimney The masonry wa...

Page 16: ...instructions when installing venting system WARNING Fire Risk Do NOT pack insulation or other combustibles between spacers ALWAYS maintain specified clearances around venting and spacers Install spacers as specified Failure to keep insulation or other material away from vent pipe may cause fire WARNING Manufacturer designed adjustable support kit can be ordered from your dealer Final approval of t...

Page 17: ...al model is also included if not needed discard Tools Required Phillips head screwdriver 7 16 socket wrench 3 32 and 5 36 Allen wrench Begin installing the ARS System 1 Remove 3 bricks as shown in Figure 17 1 and remove the ARS access cover with tool supplied in the compo nent pack 2 Lay body of stove on its back on a protective pad or pallet 3 Remove the 2 nuts and 2 bolts holding the ash grate c...

Page 18: ...e lifting up stove 5 Carefully stand stove up and place in desired location Finishing the ARS Installation 1 Re install the ash grate channel and secure with 2 bolts previously removed Set the ARS access cover and the 3 front cut bricks in place Figure 18 2 2 Install the ash drawer 3 Check to make sure baffle boards and ceramic blanket are in their proper locations See page 20 in Owner s Manual NO...

Page 19: ...rews and use to secure the mounting brackets to the stove at the very top and bottom of the brackets Figure 19 1 3 There are 6 screws included with the leg kit Attach 4 of the screws to the bracket at the bottom leaving the 2 screws loose as identified in Figure 19 1 3 Slide the ash pan assembly bottom slots over the screw heads This allows the weight of the ash pan to rest on the screws while you...

Page 20: ...ach degree F of temperature difference from one side of the material to the other The LOWER the k factor means less heat is being conducted through the non combustible material to the combustible material beneath it The k value of a material must be equal or smaller then the required k value to be accept able BTU inch foot2 hour o F Thermal Resistance R value The R value is a measure of a material...

Page 21: ...ce See exception EXCEPTION Non combustible floor protections must extend beneath the flue pipe when installed with horizontal venting and extend 2 inches 51mm beyond each side Figure 21 4 Fire Risk Hearth pads must be installed exactly as specified High temperatures or hot embers may ignite concealed combustibles WARNING USA 203mm 8 in 203mm 8 in 203mm 8 in 457mm 18 in 1429mm 56 1 4 in minimum 109...

Page 22: ...ccommodate outside air piping Use 4 inch 102mm aluminum metal flex or rigid piping to directly connect outside air to appliance intake Use the supplied termination cap with a rodent screen Seal between the wall or floor and the pipe with silicone to prevent moisture penetration WARNING Fire Risk Asphyxiation Risk Do not draw outside combustion air from Wall floor or ceiling cavity Enclosed space s...

Page 23: ... magnet under the bottom left rear corner as shown in Figure 23 1 See pages 15 and 21 for detailed operating instructions for the blower and snap disc Shock Risk Do NOT remove grounding prong from plug Plug directly into properly grounded 3 prong receptacle Route cord away from appliance Do NOT route cord under or in front of appliance CAUTION Figure 23 1 Snap Disc Bracket with Magnet Secure wires...

Page 24: ...nector manufacturer s instructions when installing the flue system for use in a mobile home 7 Maintain clearance to combustibles 8 Floor protection requirements must be followed precisely 9 Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure NOTE Offsets from the vertical not exceeding 45 are allowed per...

Page 25: ...t Repair Kit 1 4 20 3 8 16 Rivnut Tools RIVNUT REPAIR Y Nut Ser Flange Small 1 4 20 Pkg of 24 226 0130 24 Y Screw Pan Head Philips 8 32 X 3 8 Pkg of 40 225 0500 40 Y Screw Sheet Metal 8 X 1 2 S Grip Pkg of 40 12460 40 Y Washer 1 4 Sae Pkg of 24 28758 24 Y Service Parts R 57ST ACC Beginning Manufacturing Date April 2009 Ending Manufacturing Date Active IMPORTANT THIS IS DATED INFORMATION Parts must...

Page 26: ...26 7038 206E August 3 2015 5700 STEP TOP ...

Page 27: ...August 3 2015 7038 206E 27 5700 STEP TOP ...

Page 28: ...eration DO NOT DISCARD Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer log onto www quadrafire com CONTACT INFORMATION This product may be covered by one or more of the following patents United States 5341794 5263471 6688302 7216645 7047962 or other U S and foreign patents pending We recommend that you record the following per...

Reviews: