Quadra-Fire 41I-ACC User Manual Download Page 12

 12 

 

 

 

 

                        7045-910 

 

 

 

           October 14, 2013

41I-ACC

Chimney Systems

D.  Masonry Chimney

  • Must meet minimum standards of NFPA 211.
  • Must have at least 5/8 inch (16mm) fireclay lining joined 

with  refractory  cement.      (Installations  into  a  clay  flue 

without a stainless steel liner may reduce draw which 

affects performance, will cause the glass to darken and 

produce excessive creosote).

  • 

The  masonry  wall  of  the  chimney,  if  brick  or  modular 

block, must be a minimum of 4 inches (102mm) nominal 

thickness.

  • 

A chimney of rubble stone must be at least 12 inches 

(305mm) thick.

  • Cross-sectional  area  shall  conform  to  NFPA  211-2006 

Section 12.4.5.1.

  • Should be lined with a 6 inch (152mm) stainless steel 

flue liner to improve performance and reduce creosote 

build-up.

  • 

An equivalent liner must be a listed chimney liner system 

or other approved material.

  • No dilution air is allowed to enter the chimney.

   1. 

Secure the fireplace damper in the open position.  If 

this cannot be accomplished, it will be necessary to 

remove the damper

  

    2. Seal damper area of chimney around chimney 

connector with a high temperature sealant or seal 

insert against the face of the fireplace.

    3. Both methods must be removable and replaceable 

for cleaning and re-installation.

  • When possible, install an airtight clean-out door to the 

rear of the smoke shelf.

A.  Venting Systems

Chimney Connector:

It is also known as flue pipe or stove pipe.  It must be 6 inches 

(152mm) minimum diameter stainless steel connector pipe.

Chimney

:

The chimney can be new or existing, masonry or prefabricated 

and must meet the following minimum requirements as 

specified below.

WARNING! Risk of Fire!

Follow  venting  manufacturer’s  clearances  and 

instructions when installing venting system.

B.  Inspections

Existing chimneys should be inspected and cleaned by a 

qualified professional prior to installation.  The chimney must 

not have cracks, loose mortar or other signs of deterioration 

and blockage.  Hearth & Home recommends a NFI or CSIA 

certified professional or a technician, under the direction of 

a  certified  professional,  conduct  a  Level  II  inspection  per 

NFPA 211.

Fire Risk

Inspection of Chimney:
•  Chimney must be in good condition.
•  Meets minimum standard of NFPA 211
•  Factory-built chimney must be 6 inch 

(152mm) UL103 HT.

WARNING

NOTICE:

 Check with your local building authorities 

and/or consult the National Fire Protection Association 

(NFPA 211).  

C.  Larger Chimneys

It is recommended that chimneys with larger diameters 

than 6 inches (152mm) be relined.  An oversized flue can 

affect draft and impair performance and will allow increased 

build-up of creosote.

Summary of Contents for 41I-ACC

Page 1: ...liance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may...

Page 2: ...es Needed 5 E Inspect Appliance and Components 5 F Install Checklist 6 3 Dimensions and Clearances A Appliance Dimensions 7 B Clearances to Combustibles 8 C Alternate Floor Protection Calculation 9 D...

Page 3: ...ed trademark of Hearth Home Technologies Installation and use of any damaged appliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation and...

Page 4: ...national codes and regulations Consult insurance carrier local building fire officials or authorities having jurisdiction about restrictions installation inspection and permits CAUTION WARNING DO NOT...

Page 5: ...ir handler joints and seams taped or sealed Basement installations should be avoided D Tools And Supplies Needed Before beginning the installation be sure the following tools and building supplies are...

Page 6: ...ght requirements Roof flashing installed and sealed Terminations installed and sealed Clearances Section 3 Pg 8 Combustible materials not installed in non combustible areas Verified all clearances mee...

Page 7: ...ound w Cast STD 45 in 1143mm 31 in 787mm Metal Surround w Cast Trim REG 48 in 1219mm 34 in 864mm Metal Surround w Standard Trim STD 43 in 1092mm 31 in 787mm Metal Surround w Standard Trim LRG 51 in 12...

Page 8: ...6 inch 152mm S635 flue liner required as per ULC S628 In USA a minimum 5 ft length 1 82m 6 inch 152mm diameter flue liner is required as per UL 1482 SIDE TRIM SIDE WALL TOP TRIM 22 5 8 575mm 32 1 8 81...

Page 9: ...r k value The HIGHER the R factor means less heat is being conducted through the non combustible material to the combustible material beneath it The R value of a material must be equal or larger then...

Page 10: ...rough the warm space enclosed by the build ing envelope This helps to produce more draft espe cially during lighting and die down of the fire Penetrate the highest part of the roof This minimizes the...

Page 11: ...Minimum 3 ft 91cm Minimum Wall or Parapet Flat Roof F 2 10 3 Rule These are safety requirements and are not meant to assure proper flue draft This appliance is made with a 6 inch 152mm diameter chimne...

Page 12: ...cleaning and re installation When possible install an airtight clean out door to the rear of the smoke shelf A Venting Systems Chimney Connector It is also known as flue pipe or stove pipe It must be...

Page 13: ...ordance with Insert Listing Follow Manufacturer s Instructions for Maximum Liner Extension Above Chimney Maximum 30 Degrees Offset in Chimney Combustible Floor Masonry Chimney Cont d This insert confo...

Page 14: ...ue collar and the chimney top The air flow of the factory built zero clearance fireplace system must not be altered The flue liner top support attachment must not reduce the air flow for the existing...

Page 15: ...lace opening the portion of the insert extending onto the hearth must be supported Manufacturer designed adjustable support kit can be ordered from your dealer Final approval of this installation type...

Page 16: ...ly Chimney heights exceeding 25 feet 7 62m from base of appliance may create an over draft situation Overdraft condition may create over firing Over firing may ignite creosote and or damage appliance...

Page 17: ...tion WARNING Option One Installation Instructions The outside air cover comes packaged with the component pack It is necessary to remove the blower housing and block off the room air with the outside...

Page 18: ...gure 18 1 2 Attach gasket to bottom side of flue collar with a thin coat of silicone C Leveling Legs 1 Remove the 2 screws already installed on each leg 2 Move legs to the desired height 3 Re install...

Page 19: ...w driver attach the side sur rounds to the top surround using 2 8 sheet metal screws provided with the kit Figure 19 1 3 Lay the trim face down and place the corner brackets into position 4 Using a st...

Page 20: ...0 1 3 Using phillips head screw driver remove snap disc bracket and cord restraint bracket from right side Figure 20 2 4 Re install snap disc bracket and cord restraint bracket to left side of blower...

Page 21: ...eet metal shears cut trim along the marked edge The cut edge fits under lip of top trim so it allows for some variance in your straight edge 5 The double sided tape that holds front and side trims to...

Page 22: ...from each side of insert and use plumbers tape to secure to structure a washer may be required Re install bolts 3 Unit must be grounded with 8 solid copper grounding wire or equivalent and terminated...

Page 23: ...ludes Door Trim Spring Handle Hinge Pins And Logo Gold 41IDRTRIM GD Nickel 41IDRTRIM NL D T S C C A I 1 4 P S y l e t a r e p e S t i K m i r T r e d r O 1 3 X 3 4 d n u o r r u S Surround Trim Kit 43...

Page 24: ...mportant operating and maintenance instruc tions included Leave this manual with party responsible for use and operation Read understand and follow these instruc tions for safe installa tion and opera...

Reviews: