Test Panel (Maintenance)
•
29
Where: xxxx is relative time stamp in ms. [station] is address, [length] is payload
size, aabbccddeeff is payload data.
Example monitor port 1:
PRX
1
<enter
>.
>[0010] aa000300000000a6
<[0010] aa0003000001018945
Example monitor port 1:
PRX
1
ASCII<enter
>.
>[0500] STATUS_ALL
<[0500] STATUS_ALL [01000000]
Example monitor port 1:
PRX
1
RX<enter
>.
>[0090] aa000300000000a6
>[0090] aa000300000000a6
Example monitor port 1:
PRX
1
RX ASCII<enter
>.
>[0090] STATUS_ALL [00][0034] 000000000000000
>[0090] STATUS_UPSETS [00][0008] ffaa000001020304
15.10
Displaying the Software Version (VER)
To display the version of software residing in the 6QBI, type
VER
<enter>.
Example:
VER <enter>
Display:
QEI 6QBI Link:80-XXXXXX-001 Rev. X 1/30/19 Chksum: 6320d4ca
Where XXXXXX = current firmware version/revision.
15.11 PRCAL
This command calibrates the analog section of the 6QBI. The command would be
used when installation is complete and all analog panels are configured and ready to
use. Due to installation variables such as cable lengths and routing the actual
analog voltage at the analog panel terminal is slightly different (usually lower) then
the one read by the 6QBI analog front end. By calibrating the 6QBI analog front-end
by a known input voltage at the physical analog panel terminal (+/- 5 Volts DC) a
calibration value can be determined and save in the 6QBI internal Eprom memory.
Setup: Install a 6QBI with the appropriate link and a single AIP or 6AMP (w/ 6PIB1)
panel, address set to zero (0).
Use a precision voltage source for +/-5volts DC, connect to Panel Point 0.
Connect to 6QBI via the USB maintenance port and TeraTerm on PC.