UG-1062 DIO-
9100 USER’S GUIDE
UG-1091
6QBI QUICS Board
Interface
User’s Guide
April 2021
Page 1: ...UG 1062 DIO 9100 USER S GUIDE UG 1091 6QBI QUICS Board Interface User s Guide April 2021 ...
Page 2: ...ucts herein described to improve reliability function or design QEI LLC does not assume liability arising out of the application or use of any product or circuit described herein neither does it convey any license under its patent rights nor the rights of others This manual and all data contained constitutes proprietary information of QEI and shall not be reproduced copied or disclosed to others o...
Page 3: ...Release Dec 6th 2018 B Changes due to firmware revisions Dec 19th 2018 C Changes due to firmware revisions Jan 18th 2019 D Changes due to firmware revisions Jun 19th 2019 E Changes due to firmware revisions Aug 29th 2019 F Changed Calibration Mode Oct 2nd 2019 G Added 6PIB1 functionality April 26th 2021 ...
Page 4: ...Pinout 10 7 Communications Ports 11 7 1 General 11 7 2 RS 422 Ports J14 Port 1 J13 Port 2 11 7 3 Serial Fiber Port Optional 12 7 4 USB Maintenance Port J5 14 8 Dip Switches 15 8 1 Option DIP Switches SW1 15 8 2 Watchdog Disable Switch SW1 Position 6 16 9 LED Indications 17 10 Earth Grounding 18 10 1 Earth Grounding Method 18 11 Mechanical 18 12 Installation 19 12 1 General 19 12 2 Typical Installa...
Page 5: ... for Test Panel Commands 24 15 5 Reading Analog Values RA 26 15 6 Reading Status Values RS 26 15 7 Reading Accumulator Values RC 26 15 8 Relay Control 27 15 8 1 On Relay Operation CN point dwell 27 15 8 2 Off Relay Operation CF point dwell 27 15 9 Communication Checks 28 15 9 1 PRX Command 28 15 10 Displaying the Software Version VER 29 15 11 PRCAL 29 ...
Page 6: ...er of each I O panel per RTU along with all the same functionality for the panels With the QUICS 3000 series panels the number of status points is limited to 320 For analogs and control points the 6QBI supports up to the maximum allowable via a 6PIB1 When paired with the MicroPAQ 940P the 6QBI can be retrofit to replace a 6CPPX within the existing space in the RTU cabinet The 6QBI includes two RS ...
Page 7: ...S 422 Main Port 2 Protocol Asynchronous Byte Oriented Bit Rate 115 2Kbps Connector RJ45 J14 Port 3 Interface Serial Fiber Multimode Protocol Asynchronous Byte Oriented Bit Rate 115 2Kbps Connector ST Connectors TX RX Port 4 Interface USB 2 0 Maintenance Port Connector USB Type B J20 Control Point Interface J5 Panel Type 6COP1 or 6PIB1 Addressability Sixteen 6COP1 or 6ROP panels x 8 control points ...
Page 8: ...verter Number of Bits 12bits 11 bits sign bit Accuracy 1 Bit Conversion rate 50 conversions per second minimum CMRR 70 dB min for power line fundamental ref Earth gnd Normal Rejection 70 db for power line fundamental Isolation 1 kVdc analog common to logic common Connector 16 Pin IDC Header Power Input Voltage 12Vdc nominal Current 3VA nominal 200mA 12Vdc Connector 3 pin socket J8 Pin 1 12Vdc Pin ...
Page 9: ...dc input nominal maximum 16Vdc Input power connections are made at 3 pin connector J8 J8 PIN Name Description 1 DC Input Connect a 12Vdc Power Supply here 2 Common Power supply common connection here 3 DC Output 12Vdc 200mA output connection here RS 422 OPTION SW MAINT 6AIP1 6SIP1 6COP1 1 12VDC IN 2 COMMON 3 12VDC OUT ...
Page 10: ...1 each containing 16 inputs for a total of 256 individual digital input points When paired with a 6PIB1 the Status Panel Interface can monitor 20 Status Multiplexer Panels 6SMP containing 16 inputs each for a total of 320 digital input points Some communication protocols may limit the number of input points defined as status points to a lesser number of points The Status Panel Interface under prog...
Page 11: ...J6 PIN Name Description 1 12V 12V Power out to 6SIP1 Panels 2 SIP ACK 6SIP1 Panel Acknowledge Input 3 COM Power output common 4 COM Power output common 5 PSEL BIT3 Panel Select Bit 3 6 PSEL BIT1 Panel Select Bit 1 7 PSEL BIT4 Panel Select Bit 4 8 LATCH EN Latch Delay Pulse 9 PSEL BIT0 Panel Select Bit 0 10 PSEL BIT2 Panel Select Bit 2 11 thru 26 Status Word Sixteen Bit Status Word from 6SIP1 ...
Page 12: ... however some may have only four control output points or less The Control Panel Interface executes a command by selecting a single external relay then energizing its coil for a pre defined period of time To do this the Control Panel Interface provides 16 current source lines and 16 current sink lines The current source lines 8 trip and 8 close act as a relay select while the current sink lines ac...
Page 13: ...ol Connector J5 Pinout RS 422 SERIAL FIBER OPTION SW MAINT 6AIP1 6SIP1 6COP1 PIN 1 PIN 2 PIN 33 PIN 34 J5 PIN Name Description 1 NC No Connect 2 NC No Connect 3 thru 10 TRIP 0 7 Trip Row Lines 0 thru 7 11 thru 18 CLOSE 0 7 Close Row Lines 0 thru 7 19 thru 34 COLUMN 0 15 Column Lines 0 thru 15 ...
Page 14: ...s digitized by the A D converter into a 12 bit signed value 11 bit plus sign This value is stored in RAM for further processing and subsequent transmission to the client Unlike the other panel interfaces where the isolation is done at the panels themselves the Analog Panel Interface has its own isolation on board A DC DC converter provides the necessary power supply and isolation for the analog in...
Page 15: ...L FIBER OPTION SW MAINT 6AIP1 6SIP1 6COP1 PIN 1 PIN 2 PIN 15 PIN 16 J7 PIN Name Description 1 ANA IN Analog Input 2 A15 6AIP1 Power 15Vdc 3 5 7 PNL SEL X Power Common 4 A15 6AIP1 Power 15Vdc 6 8 ACOM Power Common 7 9 11 13 PT SEL X Panel Point Select Ack 14 ACOM 6AIP1 Signal Common 15 ANA IN Analog Input 16 ANA IN Analog Input ...
Page 16: ...ated shared isolation and transient protected The 6QBI also includes an available optional serial fiber port for use with the ePAQ 9410 or ePAQ 942x Also included is a USB Maintenance Port for field testing and troubleshooting 7 2 RS 422 Ports J14 Port 1 J13 Port 2 Two isolated RS 422 communication ports Connections are via 8 pin RJ45 connectors Baud rate is fixed at 115 2 kbps for compatibility w...
Page 17: ...Port TX RX allows for 6QBI communications with the ePAQ 9410 or ePAQ 942x via serial fiber Connections are made via ST fiber connectors using multimode POF fiber It may be necessary to remove the 6QBI front cover to reach the fiber connections Designation on 6QBI TX and RX Connector Type Separate Fiber optic Receiver and Transmitter with ST bayonet type connectors quarter turn locking Receiver Ava...
Page 18: ...UG 1091 6QBI User s Guide Copyright 2021 QEI Communications Ports 13 RS 422 OPTION SW MAINT 6AIP1 6SIP1 6COP1 SERIAL FIBER ...
Page 19: ...s and analogs etc See the appendix for available test panel functions The port uses a USB type B connection Typical connection to a PC is through any USB B to USB A cable not supplied This port is compatible with terminal programs such as TeraTerm PuTTY and HyperTerm and may require installation of the 6QBI USB driver depending on Windows version Any baud rate will work with the 6QBI RS 422 OPTION...
Page 20: ... During normal RS 422 communications all four DIP switch positions are OFF UP The function of each switch is as follows DIP Switch Function 1 On J13 and J14 RS485 Operational 2 On Fiber port and J13 Operational 3 On J13 to Fiber repeater 4 Not Used 5 Not Used 6 On Watch Dog OFF LED D1 is illuminated RS 422 OPTION SW MAINT 6AIP1 6SIP1 6COP1 ...
Page 21: ... switch disables the watchdog circuit This switch is a factory setting When the SW1 switch is OFF UP the watchdog circuit is enabled factory setting and LED D1 is off DO NOT set the switch to ON DOWN as doing so doing so will disable the watchdog circuit and may result in incorrect operation When the watchdog is disabled LED D1 turns on as a warning ...
Page 22: ... Cover Indicates 5Vdc power is active D16 COP Bottom Edge Control Panel Error Operating Red D17 COP Bottom Edge Control Panel OK Green D18 SIP Bottom Edge Status Panel Error Red D19 SIP Bottom Edge Status Panel OK Green D20 AIP Bottom Edge Analog Panel Error Red D21 AIP Bottom Edge Analog Panel OK Green D23 RS 422 Top Edge Main RS 422 Port 1 TX Red D24 RS 422 Top Edge Main RS 422 Port 1 RX Green D...
Page 23: ...re to do so will render the transient protection circuits on the 6QBI RS 422 ports inoperative and may result in damage to the board The J20 grounding tab is also located near the top left swage on mounting hole 11 Mechanical Dimensions are 11 675 L x 4 25 W x 1 5 D Mounting holes are for 6 32 screws at the four corners of the board Top left mounting hole is also chassis earth ground or use Tab J2...
Page 24: ...ding on the desired installation it is possible to mount a 6QBI in the same location using the same cabinet or panel as was used for the previous 6CPP6 it replaces Likewise the connectors for input power J8 30V relay power J9 and ribbon cable interfaces to the Analogs J7 Statuses J6 and Controls J5 are in practically identical locations on both the 6QBI and 6CPP6 boards This can eliminate the need...
Page 25: ... HBT OPTIONS TX RX PWR S1 TX RX J13A J13B J13C J13D TX RX J14A J14B J14C J14D J15A J15B J15C J15D J16A J16B J16C J16D PORT 20 TX RX TX RX TX L A L A TX J9 J7B J7D H L L H PORT 21 PORT 22 PORT 23 FIBER 20 FIBER 22 FIBER 24 FIBER 26 FIBER 28 FIBER 30 FIBER 32 FIBER 34 PORT 7 J1A J1B J2A J2B J2C J2D J3 J4 J12A J12B J12C J12D J10 J11 J9 J7A J7B J7C J7D J8A J8B J6 J5 RS 422 IRIG PORT 9 PORT 11 PORT 8 P...
Page 26: ...nterface between the ePAQ 9410 942x or MicroPAQ 940P and the QUICS III 6PIB1 Required or QUICS IV I O Cards The 6QBI mounts in less than half the space of an existing 6CPP6 panel in any existing RTU cabinet The 6QBI includes two isolated RS 422 ports for communication with a MicroPAQ 940P or ePAQ 9410 942x The two ports allow for redundant communications with multiple RTUs A Serial Fiber port is a...
Page 27: ...I O Panels 0 QUICS IV 1 QUICS III B 0 Future Use C Serial Fiber Option 0 None 1 Installed 14 Software 14 1 General The 6QBI communicates with either a MicroPAQ 940P or ePAQ 9410 942x The 6QBI does not require software configuration and no special 6QBI Client is required for either the MicroPAQ 940P or ePAQ 9410 ePAQ 942x the 6QBI will appear to the gateway as its own local I O See the Addendum for...
Page 28: ...r 6QBI serial port it will appear under connected device window Configure the port as 8 bit 1 stop no parity no flow 6QBI will connect at any speed Once connected press enter key a few times to get main prompt tp n where n is the command index number The 6QBI TP interface can save eight 8 previously entered commands Once a command is entered it is stored in a rotating buffer of eight Use the key t...
Page 29: ...log measurement points of its own it does have a readable 2 5Vdc reference voltage other analog point values within the overall subsystem can be displayed 15 3 2 Status Monitoring In this mode of operation the test panel will display the status on or off of points within the 6QBI Subsystem Status points will be displayed in groups of 16 corresponding to hardware status point connections at the pan...
Page 30: ...ip PRX port option option Print Port Traffic VER Print Code Version DIP Read Dip Switches TIME hh mm hh mm ss Set Time of Day DATE mm dd yyyy Set Date of Day CONFIG Display current Configuration STATUS Display 6QBI status voltages temperature PRCAL mode Analog Calibration Mode HELP Display all menu options Same as HELP Note fields are required are optional ...
Page 31: ...tage RA P3 0 4 V Display 48 4 25v 49 1 24v 50 4 50v 51 5 00v 15 6 Reading Status Values RS Status points can be selected and displayed in real time They are display as two 2 8 bit registers To enter the desired analog points proceed as follows Example read single point RS 4 enter Display 4 00000000 00000000 Example read multiple points RS 0 2 Display 0 00000000 00000000 1 10101010 01010101 2 11111...
Page 32: ...illiseconds Default of 250ms will be used if not specified Note that Dwell time may not be noticed if latching relay 15 8 1 On Relay Operation CN point dwell To operate the function 2 ON Close relay on a control point type CN space and the point number of the relay Example CN 1 enter Result Turn ON Close point 1 for standard Dwell time of 250ms Example CN 127 500 enter Result Turn ON Close point 1...
Page 33: ...sages is 9999ms 9 999 seconds and will roll over to zero 0 To help debug communications several PRX options are available Order of options is not critical use minimal entry to unique format i e A for ASCII T for TX etc PRX port option option option Options only first letter required N ONE turns off all monitoring options A SCII modifier decodes data in ASCII TEXT format H EX modifier decode data i...
Page 34: ... 80 XXXXXX 001 Rev X 1 30 19 Chksum 6320d4ca Where XXXXXX current firmware version revision 15 11 PRCAL This command calibrates the analog section of the 6QBI The command would be used when installation is complete and all analog panels are configured and ready to use Due to installation variables such as cable lengths and routing the actual analog voltage at the analog panel terminal is slightly ...
Page 35: ...indicates voltage to apply to Point zero 0 Raw value is the un calibrated value read Cal value should be 4095 the indicates the calibration value used Press p to select 5Vdc input mode make sure this voltage is applied to Point 0 Press n to select 5Vdc input mode make sure this voltage is applied to Point 0 Press s to save the calibration values to Eprom The 6QBI internal calibration memory can be...