INSTALLATION AND OPERATION MANUAL SOLAR MODULES DUO-G5.X – HANWHA Q CELLS – NA

INSTALLATION AND OPERATION MANUAL SOLAR MODULES DUO-G5.X – HANWHA Q CELLS – NA

2 PLANNING

2.3  Mounting options

Module Selection

For detailed key electrical data, please refer to the product data 
sheet for the respective product. 

 

Ä

For  maximum  energy  yields,  mismatches  of  specified  electric 

current (I

MPP

) of more than 5 % should be avoided for all modules 

connected in series.

Safety Factor

During normal operation, a module may generate a greater current 
and / or higher voltage than that determined under standardized test 
conditions. Accordingly, the values of I

SC

 and V

OC

 marked on the 

module should be multiplied by a facot of 1.25 when determining:

• 

the component voltage ratings,

• 

conductor ampacities,

• 

fuse sizes,

• 

size of controls connected to the PV output. 

Refer to Section 690-8 of the National Electrical Code for an 
additional multiplying factor of 125 percent (80 percent derating) 
which might be applicable.

 

Ä

Please follow the valid national guidelines for the installation 
of electrical systems (refer to section 690-8 of the NEC for an 
additional multiplying factor of 125 percent [80 percent derating] 
which may be applicable).

Series Connection

Connection of modules in series is only permitted up to the 
maximum system voltage as listed in the applicable data sheet.  

 

Ä

Take into account all possible operating situations and all relevant 
technical norms and regulations when designing the system. 
This will ensure that the maximum system voltage, including all 
necessary safety margins, is not exceeded. 

 

Ä

Take the voltage limit of the inverter into account when determining 
the maximum number of modules in the string.

Parallel Connection

Modules may be damaged by the occurrence of reverse currents 
(caused by module defects, ground leaks, or defective insulation).

 

Ä

Ensure that the maximum reverse current load capacity indicated 
in the data sheet is met. 

In order to limit reverse currents that may occur, we recommend 
using the following safety options:

1)  Layout with a limited number of parallel connected strings :

Without undertaking further current blocking measures, a maximum 
of two module strings may be operated in parallel on a single 
inverter or MPP tracker.

2)  Layout with string fuses :

Place fuses for each string of modules at the plus and minus ends. 
Observe the maximum permitted number of strings as indicated 

in the specifications provided by the respective string fuse manu

-

facturer and the technical guidelines.

NOTE! 

When installing different product versions, the lowest minimum 
permitted reverse current load capacity applies.  

Inverters

Inverters with or without transformers may be used.

2.4  Electrical layout

2 PLANNING

Specifications

MODULE TYPE

MOUNTING 
OPTION

POSITION OF CLAMPS* [IN (MM)]

TEST LOAD  
PUSH/PULL** 
[PA] 

DESIGN LOAD 
PUSH/PULL** 
[PA] 

SAFETY  
FACTOR

Q.PEAK DUO-G5.X

Q.PEAK DUO BLK-G5.X

CL1 / CL3

9.84 - 17.72 (250 - 450)

5400/4000

3600/2670

1.5

FB1 / FB2

13.58 (345)

IP1

-

CL1

0 - 9.84 (0 - 250) 
17.72 - 21.65 (450 - 550)

2400/2400

1600/1600

CL2

0 - 9.84 (0 - 250)

CL4

0- 11.81 (0 - 300)

CL5

short side: 0 - 9.84 (0 - 250)
long side: 11.81 - 15.75 (300 - 400)

4000/4000

2670/2670

MODULE TYPE

MOUNTING 
OPTION

POSITION OF CLAMPS* [IN (MM)]

TEST LOAD  
PUSH/PULL*** 
[PA] 

DESIGN LOAD 
PUSH/PULL*** 
[PA] 

SAFETY  
FACTOR

Q.PEAK DUO-G5.X

Q.PEAK DUO BLK-G5.X

IP2

-

2400/2200

1600/1470

1.5


** 
*** 

Distance between outer edge of module and middle of the clamp. 
Loads according to IEC 61215-2:2016 and UL 1703. 
Test sequence according to IEC 61215-2:2016.

ATTENTION

 

Ä

The loads in the table are related to the mechanical stability of the solar modules. The mechanical stability of the mounting system 
including clamps has to be evaluated by the system supplier. The system installer is responsible for the determination of location-

specific load requirements.

 

Ä

Ensure, that the subconstruction does not touch the junction box (even under load).

 

Ä

Ensure, that the connection cables of the junction box do not run between laminate and mounting rails.

 

Ä

Ensure, minimum support depth of 15 mm on the back side of the module for IP2, CL2 and CL4. Ensure minimum support depth 
of 10 mm on the front side of the module for IP2.

 

Ä

Module bend under loads. Therefore, sharp objects (e.g. screws) must not be mounted near the module backside.

 

Ä

Use M8 corrosion-proof screws and washers (diameter 

 15.8 mm  or 

 0.62 in) for FB1 and FB2 mounting.

Summary of Contents for Q.PEAK DUO BLK-G5 series

Page 1: ...Valid for North America Q PEAK DUO G5 X SOLAR MODULE SERIES INSTALLATION AND OPERATION MANUAL ...

Page 2: ...ou check the results of said procedure Prohibited Beware of possible danger or damage Categories Danger Risk of fatal injury Attention Risk of serious injury or damage to property Note Risk of damage to product Units Where both Imperial and U S units for example inches are shown metric units are definitive References to Data Sheet or Module Data Sheet refer to the Module Data Sheet applicable to t...

Page 3: ... of accepted guarantees Q CELLS accepts no other responsibility for the functionality and safety of the modules Ä Ä Please observe the instructions for any other system components that may be part of the complete solar power system It may be necessary to carry out a structural analysis for the entire project Ä Ä If your questions are not satisfactorily answered in the manual please contact your sy...

Page 4: ...ar ventilation of the module Guarantees long term stability Avoid of different metals to prevent contact corrosion Allows for stress free expansion and contraction due to temperature fluctuations Ä Ä Ensure that no mechanical stresses e g caused by vibrations twisting or expansion applied to on the module Ä Ä Ensure that the clamps and the mounting frame are compatible Clamp System Requirements Us...

Page 5: ...r of parallel connected strings Without undertaking further current blocking measures a maximum of two module strings may be operated in parallel on a single inverter or MPP tracker 2 Layout with string fuses Place fuses for each string of modules at the plus and minus ends Observe the maximum permitted number of strings as indicated in the specifications provided by the respective string fuse man...

Page 6: ...ely in cool and dry rooms The packaging is not weatherproof DANGER Risk of fatal injury due to electric shock Ä Ä Do not install damaged modules Ä Ä Inform your vendor of any damages immediately 3 1 Safety and transport 3 INSTALLATION NOTE Module damage may occur Ä Ä Do not drop modules NOTE Module damage may occur Ä Ä Only make modifications to the module which have been confirmed in writing by Q...

Page 7: ...insulated tools Ä Ä Do not carry out the installation alone Only install undamaged modules and components Ä Ä Do not modify the module e g do not drill any additional holes 3 2 Preparation of installation 3 INSTALLATION Ä Ä Maintain an interval of at least 0 39 in 10 mm between two modules along the short side and 0 20 in 5 mm along the long side 0 39 in 10mm 0 2 0 i n 5 m m Option 2 Ä Ä Install t...

Page 8: ...rvals specified by the inverter manufacturer after switching off the inverter DANGER Risk of fatal injury due to electric shock Ä Ä Never open the junction box Ä Ä Do not remove bypass diodes DANGER Risk of fatal injury due to electric shock Ä Ä Never touch live contacts with bare hands Ä Ä Cover connectors by suitable protective caps until installation DANGER Risk of fatal injury due to electric ...

Page 9: ...nd safe condition 4 3 Connection of modules 4 ELECTRICAL CONNECTION Ä Ä To avoid complex cabling arrangements it is often advantageous to rotate some modules 180 Ä Ä Module orientation can clearly be identified from the front side by the serial number and barcode labelled behind the module glass on the side with negative connection cable Inverter 180 180 Ä Ä Ensure that all necessary safety and fu...

Page 10: ...ductor Aluminum Frame Screw Stainless Steel are marked with a ground symbol as shown below on the frame section drawing To install the grounding lug follow the specified instructions of the manufacturer The grounding lug should be made of stainless steel or tin plated metals such as aluminum to avoid corrosion The grounding lug should be attached to the frame grounding hole using a stainless steel...

Page 11: ...ve cooled down Ä Ä Do not carry or wear any electrically conductive parts WARNING Risk of falling due to unsecured access Ä Ä Never access the installation area alone or without taking adequate security precautions Ä Ä Please commission a trade specialist NOTE Module surface damage may occur Ä Ä Remove snow and ice without force e g with a very soft broom Ä Ä Do not scratch off dirt Ä Ä Rinse dirt...

Page 12: ...C 300 Spectrum Center Drive Suite 1250 Irvine CA 92618 USA TEL 1 949 748 59 96 EMAIL inquiry us q cells com WEB www q cells us Subject to change without notice Hanwha Q CELLS Installation manual solar modules DUO G5 X_2017 10_Rev01_NA ...

Reviews: