7. Message Description
51
Type
Code
Description
Measures
system event is settled.
E706
RCMU (Residual Current
Monitoring Unit) FAULT
Turn off system power when the
leakage current level is above
standard level.
Check the leakage current level,
then restart or turn off to get
back to the below standard
level.
E708
PV INSULATION FAULT
OFF Turn off system power if PV
INSULATION RESISTANCE is at
the standard level.
Restart after 3 minutes.
E709
ANTI ISLANDING FAULT
If the electric power system
blacks out, it automatically
detects the state and turns off
the All in One.
Restart after 3 minutes.
E710
FUNCTIONAL SAFETY
FAULT
When the two MCU measuring
values are mismatched.
Restart after 3 minutes if no
problem is found.
[Table 7-9 : Single fault events list]
7.3
Significant Events
If a significant event is notified, the system is set to stop operation. If that is the case,
contact your installer to restore the system to normal operation.
Checking event codes is available on the website (
https://myess.hansoltechnics.com
).
If the Internet is not available, the event codes cannot be checked.
Type
Code
Description
Measures
Significant
E901
SPI COMMUNICATION
EVENT
Occurs on internal non-
communication between the
INVERTER.
Contact the installer
immediately.
E902
CAN (Controller Area
Network)
COMMUNICATION
EVENT
Occurs on non-communication
with the EMS.
When in operation, the All in
One System is converted to the
Stand Alone mode.
Contact the installer