11.17 

Digicom  Codes  

Enter 

   

HQWHUVHTXHQFH

    Enter  1 digit to select the required reporting format. 

 Examples 

 SIA 

DTMF 

 

 

 

 

SIA pulse format P1 - 1400 Hz handshake 10pps 

 

 

 

 

SIA pulse format P2- 2300 Hz handshake 20pps 

 

 

 

 

SIA pulse format P3 - 1400 Hz handshake 20pps 

 

 

 

 Reserved 

 

 

 

 Reserved 

 

 

 

 Reserved 

 
11.18 

Keyswitch Set Configuration   

Enter 

 Enter digit  0 - 6. 

 Examples 

 

Set A 

 

 

 

 

Set B 

 

 

 

 

Set C 

 

 

 

 

Set D 

 

 

 

 Reserved 

 

 

 

 Reserved 

 

 

 

 Reserved 

 
NOTE:

  If a Keyswitch is required to Unset the system, then all the four Set modes must reflect this in the same zone. 

 
11.19  Group Reporting Telephone Allocation   
This selection requires all four Groups to be programmed. 

Enter

- Group 1 ’Alarm Codes’.  Now select where you require the Alarm Codes to be reported to. 

 

  

 

 

No reporting for group 

 

 

 

 

Report to telephone number 1, backup to number 2 

 

 

 

 

Report to telephone number 2 only 

 

 

 

 

Report to both telephone numbers always 

 
After a number has been selected, the next group will be automatically selected. 
 
 

Group 2 ’User Set/Unset Codes’.  Select from the list above where you require User Set/Unset codes to be  

 reported 

to. 

 

Group 3 ’Maintenance Codes’.  Select from the list above where you require Maintenance codes to be reported to. 

 

Group 4 ’24hr. Test call’.  Select from the list above where you require 24hr.Test Call codes to be reported to. 

 
The dual tone sound indicates programming of Group Reporting is now complete. 
 

Summary of Contents for ATLAS 8

Page 1: ...Rins171 Issue 6 INSTALLATION INSTRUCTIONS Lcd Remote Keypad Pyronix Ltd MARCH 00 This Product is approved for use in the Residential Commercial and Light Industrial Environment...

Page 2: ...gn Pyronix reserve the right to amend specifications without giving prior notice A copy of our warranty can be obtained from the above address 3 URQL LPLWHG 3 URQL RXVH UDLWKZHOO D HOODE 5RWKHUKDP 6 4...

Page 3: ...ons 16 10 8 Powering Up The panel 16 10 9 Atlas Double Pole Wiring Diagram 17 10 10 Atlas End of Line Wiring Diagram 18 11 PROGRAMMING 19 11 1 Factory Defaults 19 11 2 Entering Engineer Mode 20 11 3 S...

Page 4: ...eporting Codes 25 11 17 Digicom Codes 26 11 18 Keyswitch Set Configuration 26 11 19 Group Reporting Telephone Allocation 26 11 20 Engineer NVM Reset 27 11 21 Follow Select 27 11 22 Exiting Engineer Mo...

Page 5: ...g 3 2 Master User Level Enables All Limited User facilities 4 Clearing of event log if allowed by the Engineer 5 Omitting zones 6 Alteration of both Limited and Master User codes 7 LED Strobe Bell Ext...

Page 6: ...try Exit zone then an alarm will be generated immediately Immediate This is a zone which will when triggered wil create an alarm when the panel is set Omit If a zone is programmed as an Omitted zone b...

Page 7: ...Walk test The walk test function allows each of the Set modes to be checked in order to verify that all the intruder detectors on the alarm system are functioning correctly When undergoing a walk test...

Page 8: ...tlas on the same line as an answering machine The default setting is AMC on To remotely access the Atlas in AMC mode dial in and wait for a single ring then hang up and wait for at least 10 seconds bu...

Page 9: ...igit access code required by the alarm company in order to access the Atlas 8 during an uploading or downloading operation Reporting Codes These are unique two digit or single digit numbers used by th...

Page 10: ...will also emit a short duration of sound upon disarming Default value OFF Bell Time Minutes Seconds This option allows for very short bell durations Default value Minutes AC Fail Delay This option del...

Page 11: ...carefully Plan out the various areas and degrees of protection required from each zone It is important to decide which type each zone should be if selective sets are to be used Work out the cable rou...

Page 12: ...kaging containing the control panel and PCB Push in the PCB support posts from the rear of the panel as shown If required assemble the tamper switch from the optional kit of parts as indicated If nece...

Page 13: ...l mounting hole using one of the screws and plugs from the screw pack If possible use a spirit level or some other means to position the control panel squarely then drill two more holes into the wall...

Page 14: ...ed BAT on the PCB Battery Positive Battery Negative 10 3 Bell Strobe and Extension Speaker Connections Bell Positive Bell Trigger Strobe Positive Strobe Negative Speaker Positive Speaker Negative NOTE...

Page 15: ...r external sounder 0 050 Single remote keypad 0 015 Required capacity for alarm condition 0 815 x 0 333 0 271 Ahrs Capacity required for standby 7hrs 40 mins 7 67 hrs Non alarm current for control pan...

Page 16: ...to protect all the zone tamper wiring Up to ten sensors or door contacts may be wired on each zone 10 7 Telephone Connections T 1 R 1 TIP RING 10 8 Powering Up Your Panel RKP a Connect the battery lea...

Page 17: ...7 7 1 7 7 1 H J 0 0 7 2 1 9 1 5 2 2 0 7 7 5 5 5 3 521 3 5 7 0 3 5 5 0 6 8 3 3 3 521 3 5 7 7 67 5 0 6 3 5 1 6 3 H J 6 6 2 1 7 0 3 5 5 0 6 8 3 3 7 1 6 2 1 6 3 5 2 3 7 2 1 7 7 5 7 7 5 5 6 7 2 7 3 2 1 6 6...

Page 18: ...5 6 7 2 7 3 2 1 6 6 7 0 3 7 0 3 5 2 1 1 7 2 1 6 6 2 8 5 7 2 2 1 3 5 2 5 0 0 2 5 7 0 3 5 7 3 2 1 1 7 2 5 5 3 6 3 H J 6 6 2 1 H J 0 0 7 2 1 9 1 5 2 2 0 7 1 6 2 1 6 3 5 2 3 7 2 1 2 3 7 2 1 6 5 1 9 0 1 7...

Page 19: ...d Of Line Resistor Programmable Outputs Off System Option 1 End Of Line Zone User Log Reset Disabled Tone Dial Internal Sounder Only On Tamper Activation System Option 2 24 Hour Test Dial Dial In Spar...

Page 20: ...mode Use the link supplied to connect the NVM reset pins together and enter on the key pad remove the link The system is now back to factory default settings 11 5 Setting the Panel when Mains Fails Un...

Page 21: ...e new Engineer Code gives an audible acceptance tone then the new Engineer Code again gives an audible acceptance tone If an incorrect key is entered an error tone will be given and the function ended...

Page 22: ...ard handshake filters Audible PA zones Press to accept 11 11 5 System Option 3 Enter followed by The RKP display will toggle and X as the numbered keys are pressed indicating the selection made Key Pr...

Page 23: ...ically when the last digit is entered 11 14 Customer Account Code Issued by Central Monitoring Station Enter HQWHU VHTXHQFH followed by the 4 digit code e g 4 digit 11 15 Downloading Access Code Enter...

Page 24: ...set reporting codes To disable an event insert blanks by pressing the key in place of the two digits Examples Set A Set B Set C Set D Duress Set Duress Unset Confirmed alarm code To use HEX codes use...

Page 25: ...n event insert blanks by pressing the key in place of the two digits Examples P A alarm entered at RKP Fire alarm entered at RKP Engineer mode entered Bell fuse failure Auxiliary fuse failure Battery...

Page 26: ...tion requires all four Groups to be programmed Enter Group 1 Alarm Codes Now select where you require the Alarm Codes to be reported to No reporting for group Report to telephone number 1 backup to nu...

Page 27: ...ill work 11 21 Follow Select Enter This function is used in conjunction with Programmable Output 1 and 2 option 5 Follow Zone Enter the zone to be followed Enter for zones 1 to 8 or if no zone is to b...

Page 28: ...be emitted every 5 seconds when the panel is in day mode Press a function key to stop the error tone The fault will remain on until the fault has been corrected To determine the fault go into the log...

Page 29: ...00mA Strobe 500mA PR1 PR2 250mA Alarm bell time 2 to 20 minutes software programmable Zone type Normally closed loops which activate when opened or short circuit Zone loop current 0 76 to 1 03mA Zone...

Page 30: ...1 System option 2 System option 3 Spare Re Sets First telephone number Second telephone number Customer account code Downloading access code Zone alarming reporting codes Zone tamper reporting codes S...

Page 31: ...activation System Option 2 1 Default 24 hour test dial 2 Default no dial in 3 Default Standard filters 4 Default Audible P A System Option 3 1 Default User NVM reset 2 Default Open zones not displaye...

Page 32: ...Alarm Zone 5 Alarm Zone 6 Alarm Zone 7 Alarm Zone 8 Alarm Tamper Alarm Reporting Codes Zone 1 Tamper Zone 1 Tamper Zone 1 Tamper Zone 1 Tamper Zone 1 Tamper Zone 1 Tamper Zone 1 Tamper Zone 1 Tamper...

Page 33: ...User 5 Set User 6 Set User 7 Keyswitch User Unset Reporting Codes Unset User 1 Unset User 2 Unset User 3 Unset User 4 Unset User 5 Unset User 6 Unset User 7 Keyswitch Maintenance and Priority Codes P...

Page 34: ...storal Reporting Codes User code Restoral Bell Timeout Restoral Battery Restoral A C Restoral Test Transmission Digicom Codes Keyswitch Set Configuration Group Allocation Group 1 Group 2 Group 3 24hr...

Page 35: ...Rins171 Issue 6 Page 35...

Page 36: ...Page 36...

Reviews: