21
/
32
19PIMV0802
5.
Maintenance
5.1 Trouble Shooting:
Danger:
The PowerCube-M1 is a high voltage DC system, operated by qualified and authorized
person only.
Danger:
Before check the failure, must check all the cables connection and setting of ADD
Switches are right or not (refer to chapter 3), and the BESS system can turn on normally or
not.
No
Problem
Possible Reason
Solution
1
Turn on the BMS. The Status
LED is lighting red. But all
battery modules’ status LED
is lighting green.
This battery string is under
protection. It is possible
Over Current or Failure
Protection.
Communication cables
failure;
Battery String is reversed
connection.
Through the monitor or
maintenance
software
check the battery cell,
battery module has alarm
or not.
Check
the
Communication Cables;
Reversed connection is
serious danger!
2
Turn on the BMS. The BMS’s
Status LED is lighting red and
some the battery module’s
status LED is lighting green
but some is lighting red.
This battery string is under
protection. It is possible Over
Current, Over Voltage, Low
Voltage, Over Temperature,
Low Temperature or Failure
Protection.
Use
the
monitor
or
maintenance software to
check the battery cell,
battery module has alarm or
not.
3
After turn on the BMS power
Switch, the BMS still can’t
turn on.
External Power Supply or
internal DC/DC module is
abnormal;
Power cable is broken;
Check the external Power
Supply is normal nor not.
Has it enough power for
the
system
devices
because of setting of UPS.
Check all the power
cables and connections
are fine or not.
4
Turn on the BMS power
Switch. The Status LED shows
OK. But can’t output power.
Turn on and turn off the
“POWER OUTPUT” Switch, it
has
clear
mechanic
switching sound inside of
BMS.
DC Output breaker is fault.
Check the DC output
breaker is fault or not. If it is
fault, change the control
module (BMS module).
5
Turn on the BMS power
Electrical operation for
Check the Electrical