background image

PV500-24  03-99 

 

Section 24 

2

QuickDraw

 

WATER WITH SINGLE-WALL / DOUBLE-WALL

 

START-UP OPERATION 
 

1.  The boiler water circulating pump has 

been selected to provide optimum flow 
through the heat exchanger tubes to 
meet demand with the available boiler 
water. The pump is controlled by the 
thermostat and draws from the 
operating boiler water loop. When the 
demand is satisfied, the pump stops, 
causing the boiler water to bypass the 

unit. In addition, the water heater maybe 
equipped with a continuous operation 
tank circulation pump. The boiler water 
circulation pump is sized to satisfy all of 
the head resistance of the heat 
exchanger, therefore no pressure drop 
need be considered for this unit in sizing 
primary loop pumps. 

 

CAUTION: Temperatures higher than 125°F. increase the risk of scald injury. 

 

 

 

 

START-UP PROCEDURE 

 
1.  Fill the tank with water; open the relief 

valve or a nearby hot water outlet to 
purge air from the top of tank. Check for 
plumbing leaks. 

 
2.  Push the control switch to “on” position. 

Check boiler water pump operation. The 
tank circulating pump should also 
operate. Check thermostats for proper 
setting. The thermostats are labeled as 
to their function. The temperature 
limiting device is set at 200

°

F.  

 

Temperature Setting:

 The thermostats 

are set at the factory to 120

°

F on the 

operating   control.    Upon  startup,  the  

factory preset operating temperature is 
visible on the LED indicator of the digital 
controller. Adjust the temperature using 
the appropriate up and down arrow keys 
on the face of the controller. A slight 
variance in temperature control may be 
noticed as the digital control tunes, 
allow time for the temperature to 
stabilize. 

 
3.  Open nearby hot water tap to maintain a  

flow of water through the tank when 
starting up units. Regulate flow of water 
through the tank to allow the boiler 
water pump to cycle off and on, and 
check operation of unit. 

Summary of Contents for QuickDraw PV500-24

Page 1: ...r Water Inlet 10 Tridicator 3 Boiler Water Pump 11 Flow Switch 4 Control Enclosure 12 Relief Valve AGA optional 5 Intratank Circulator 13 Tank Purge Valve 6 Potable Water Inlet 14 Boiler Water Outlet 7 Potable Water Outlet 15 Check Valve 8 Tank Drain Optional CAUTION TEMPERATURES HIGHER THAN 125 F INCREASE THE RISK OF SCALD INJURY IMPORTANT Clearances for servicing and inspection are 18 at top sid...

Page 2: ...with water open the relief valve or a nearby hot water outlet to purge air from the top of tank Check for plumbing leaks 2 Push the control switch to on position Check boiler water pump operation The tank circulating pump should also operate Check thermostats for proper setting The thermostats are labeled as to their function The temperature limiting device is set at 200 F Temperature Setting The ...

Page 3: ... RELIEF VALVE PIPING The water heater is supplied with a pressure and temperature relief valve sized in accordance with ASME requirements Each relief valve should be piped to a suitable floor drain No reducing coupling or other restriction can be installed in the discharge line MAINTENANCE 1 A preventive maintenance program should be established to assure a long trouble free life for the water hea...

Page 4: ... safety device 3 The temperature limiting device and thermostat sensors that extend into the water in the tank may become coated with scale depending on the type of water in your area This coating will affect the accuracy of the sensors and can allow the water temperature to exceed the desired limits They should be removed from the tank and inspected at intervals Remove scale if present CAUTION On...

Reviews: