background image

PV500-24  03-99 

 

Section 24 

3

QuickDraw

 

 WATER WITH SINGLE-WALL / DOUBLE-WALL  (con't)

 

 

ELECTRICAL 

 

The heater is wired for 120 volts and must be electrically grounded in accordance with local 
codes, or in the absence of local codes, with the latest edition of the National Electrical Code 
ANSI/NFPA. When unit is installed in Canada, it must conform to the CSA C22.1, Canadian 
Electrical Code, Part 1 and/or local electrical codes. 
 
1.  Water must be pumped continuously 

through the boiler when it is being fired. 

 
2.  Do not energize water heater or pumps 

until tank is full of water. Serious 
damage may result.  

3.  All wiring must be in accordance with all 

local, state, or federal codes. 

 
4.  Provide proper overload protection for 

the system's circulating pumps. 

 

 
 

NOTE:  Use only copper wire of proper sizing for incoming service. Damage 

resulting from use of aluminum wiring will be excluded from coverage under 
the warranty of this unit. 

 
 
 

RELIEF VALVE PIPING 

 

The water heater is supplied with a 
pressure and temperature relief valve, sized 
in accordance with ASME requirements. 
Each relief valve should be piped to a 

suitable floor drain. No reducing coupling or 
other restriction can be installed in the 
discharge line.  

 
 

 
 

MAINTENANCE 

 

1.  A preventive maintenance program 

should be established to assure a long, 
trouble-free life for the water heater. 

 
2.  Scale will normally form in the tank 

during operation and will accumulate on 
the bottom of the tank. The scale is 
formed from the natural chemicals in the 
water that precipitate  out during the 
heating cycles. Some water supplies 
contain more of these chemicals than

 

others,  and  the scale buildup will occur 

 
 

 
 

more rapidly. Other factors affecting the 
scale buildup are the amount of hot 
water used and the temperature of the 
water. The more hot water used, the 
more fresh water containing the scale-
forming chemicals is brought into the 
tank. As the temperature of the water 
increases, the rate of scale deposited 
will be increased. The unit should be 
inspected and cleaned as required  by 
local water conditions. 

 
 
 

Summary of Contents for QuickDraw PV500-24

Page 1: ...r Water Inlet 10 Tridicator 3 Boiler Water Pump 11 Flow Switch 4 Control Enclosure 12 Relief Valve AGA optional 5 Intratank Circulator 13 Tank Purge Valve 6 Potable Water Inlet 14 Boiler Water Outlet 7 Potable Water Outlet 15 Check Valve 8 Tank Drain Optional CAUTION TEMPERATURES HIGHER THAN 125 F INCREASE THE RISK OF SCALD INJURY IMPORTANT Clearances for servicing and inspection are 18 at top sid...

Page 2: ...with water open the relief valve or a nearby hot water outlet to purge air from the top of tank Check for plumbing leaks 2 Push the control switch to on position Check boiler water pump operation The tank circulating pump should also operate Check thermostats for proper setting The thermostats are labeled as to their function The temperature limiting device is set at 200 F Temperature Setting The ...

Page 3: ... RELIEF VALVE PIPING The water heater is supplied with a pressure and temperature relief valve sized in accordance with ASME requirements Each relief valve should be piped to a suitable floor drain No reducing coupling or other restriction can be installed in the discharge line MAINTENANCE 1 A preventive maintenance program should be established to assure a long trouble free life for the water hea...

Page 4: ... safety device 3 The temperature limiting device and thermostat sensors that extend into the water in the tank may become coated with scale depending on the type of water in your area This coating will affect the accuracy of the sensors and can allow the water temperature to exceed the desired limits They should be removed from the tank and inspected at intervals Remove scale if present CAUTION On...

Reviews: