DeltaTherm IR Cure Module
Revision B
/
February 2020
Page 19 of 41
•
When in Auto Cycle, the DeltaTherm IR Cure Module operates the exhaust fan
and the intake fan.
•
The IR panels will start and increase to the set system parameters. It may take a
few minutes to increase to the set values.
•
When the machine is in the range of the system parameters, auto cycle will start.
Differences in the parameters may occur to maintain optimum conditions.
Note: With two-sided IR ovens, the upper panels may indicate temperatures higher
than the setpoint due to absorption of energy from the lower panels. This is normal.
•
If the DeltaTherm IR Cure Module is the last machine in a line, the alarm will
signal when a board exits. This only occurs if a downstream SMEMA signal is not
present.
•
When the conveyors stop for a board to be removed, the cure module will
maintain the parameters. The module will not time-out if a board is not removed.
•
In Auto Cycle, the PLC will send a signal through the RS485 cable to the next
machine every 5 seconds to tell the next machine the width of the conveyor.
•
Push the
Home Button
on screen or F3 Key to leave Auto Cycle at any time.
Boards in the system are not removed when you exit.
Note: Make sure all boards have exited the system before you exit Auto Cycle.