Code-Compliant Planning and Installation Guide V 1.0 (New Zealand) - Complying with AS/NZS 1170.2-2021 -
- Installation Instructions -
Tile Interface Installation
Determine the positions of the Roof Hooks according to your plans.
Remove the roof tiles at the marked positions or, if possible, simply
push them up slightly.shown in Figures 5.3C and 5.3D.
Fix the Roof Hooks to the rafter using Clenergy provided Buildex
14 gauge Hex Head Zips screw with minimum 25 mm embedment
as shown in the figure on the right following the Buildex screws
installation guide below:
- Use a 3/8" Hex Socket.
- Use a mains powered or cordless screw driver with a drive speed
of 3,000 RPM maximum.
- Fit the driver bit into the screw and place at the fastening position.
- Apply consistently firm pressure (end load) to the screw driver
until the screw is fastened.
Incorrect
Correct
The roof hook must not press against the roof tile.
If necessary, pack the roof hook with max pack
height of 17 mm for Clenergy provided Buildex 50
mm long screw, with max pack height of 35 mm
for Clenergy provided Buildex 65 mm long screw.
If necessary, use an angle grinder to cut a recess in the tile covering the Roof Hook at the point where the Roof Hook
extends so that the tile lies flat on the surface. If grooved tiles are used, it will also be necessary to cut a recess in the
lower tile.