Troubleshooting Guide
Troubleshooting Guide
‘Dry’ Reset Procedure
From time to time, the valve may
display an error code for various
reasons. The first troubleshooting step
is to perform a ‘dry’ reset.
Remove the faceplate, opening the tabs on either side of the valve. This will expose the
Power Circuit board with a number of wires connected.
On the bottom right hand corner is a 4 pin adaptor labelled ‘12VAC PWR’, disconnect the
adaptor and reconnect after 5 seconds. The valve will then whir twice, and should return
to the normal screen.
If the error message is still present, refer to the troubleshooting guide.
PROBLEM
POSSIBLE CAUSE
SOLUTION
No display/blank screen on valve.
A. Transformer not connected.
A. Connect transformer.
B. No power at outlet/source.
B. Use working outlet/repair outlet.
C. Switched outlet/improper voltage.
C. Use uninterrupted outlet/ensure source is
delivering proper voltage.
D. Dead battery.
D. Replace battery (CR2032).
E. Defective transformer.
E. Replace transformer.
F. Defective PC Board.
F. Replace PC Board.
Valve does not display correct time of day.
A. Power outage(s).
A. Reset time of day, replace battery
(CR2032).
B. Time of day set incorrectly.
B. Reset to correct time of day.
C. Switched outlet.
C. Use uninterrupted outlet.
D. Tripped breaker switch.
D. Reset breaker switch.
E. Defective PC Board.
E. Replace PC Board.
Valve regenerates at wrong time of day.
A. Power outage(s).
A. Reset time of day, replace battery
(CR2032).
B. Time of day set incorrectly.
B. Reset to correct time of day.
C. Time of regeneration set incorrectly.
C. Reset regeneration time.
D. Control valve set for immediate
regeneration.
D. Contact Puretec for assistance.
E. Control valve set for delayed and/or
immediate regeneration.
E. Contact Puretec for assistance.
Time of day flashes on and off.
A. Power outage(s).
A. Reset time of day, replace battery (CR2032)
and then perform a ‘dry’ reset.