PUREGAS, LLC
P4200PM / P5000PM Remote Air Dryer User’s Guide
Page 72 of 79
P012649 – Rev B
13.13 Can’t Create a Compressor Excessive Run Time Alarm
Possible Cause
Check
Corrective Action
Compressor Excessive
Run Time Alarm set
point higher that the
default of 3:00 minutes
Verify Excessive
Compressor Run Time
Alarm set point (section
8.11)
Allow the compressor
to run longer than the
verified set point
(section 9.12)
Defective Control Board Verify that the
compressor has run
longer than the verified
Excessive Compressor
Run Time Alarm set
point (above)
Replace Control Board
(section 11.2) if the
compressor runs longer
than the verified
Excessive Compressor
Run Time Alarm set
point by 1 minute or
more and fails to create
an alarm.
13.14 Compressor Rapid ON/OFF Cycling
Possible Cause
Check
Corrective Action
Defective Solid State
Relay
Measure voltages at
Solid State Relay
(section 9.5)
If measurements are
bad, replace Solid State
Relay (section 11.2)
Defective Control Board Measure voltages at
Solid State Relay
(section 9.5)
If measurements are
good, replace Control
Board (section 11.2)