1.3 Description of components and power supply terminals (Table 1, Fig.2).
Table 1. Components of the Power supply PCB (Printed Circuit Board) (see Fig. 2).
Component
no.
Description
P
BAT
Jumper
– configuration of discharged battery disconnection system (UVP)
P
BAT
=
discharged battery disconnection system OFF
P
BAT
=
discharged battery disconnection system ON
T
AC
Jumper
- setting the delay time for AC power failure indication
T
AC
=
delay time T= 60s
T
AC
=
delay time T= 10s
Description:
jumper on,
jumper off
START
button (running the PSU from the battery)
V
ADJ
potentiometer,
DC
24 ÷ 29V voltage adjustment
F
BAT
fuse in the battery circuit, F5A / 250V
Terminals:
~AC~
– AC power input
EPS
– technical output of AC power failure indication
hi-Z state
= AC power failure
0V state
= AC power - O.K.
PSU
– technical output of PSU failure indication
hi-Z state
= failure
0V state
= PSU status O.K.
LoB
– technical output of low battery voltage indication
hi-Z state
= battery voltage U
BAT
<23V
0V state
= battery O.K.
+BAT-
–
terminals for battery connection
+AUX-
– DC power output, (+AUX= +U, -AUX=GND)
Description: hi-Z
– high impedance, 0V – connection to the ground GND
LEDs
– optical indication:
AC
– AC power
AUX
– output voltage DC
Optional, external optical indication output terminal
I
BAT
Jumper;
- battery charging current configuration
I
BAT
=
, Ibat =0,5 A
I
BAT
=
, Ibat =1 A
Description:
jumper on,
jumper off
LB
– LED battery charging indication
Fig. 2. The view of the Power supply PCB.