The  power  supply  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch. 

Therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the user should 
be informed how to disconnect the power supply unit from the mains supply (usually by assigning an appropriate fuse in 
the fuse box). The electrical system shall be made in accordance with applicable standards and regulations. 

 
2.2 Installation procedure. 

 

1.  Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 

2.  Mount the PSU in a selected location. The tamper bracket, located in the central part of the housing (see 

Fig. 3 [3]), signaling the attempts to detach the PSU from the mounting surface, should be screwed to the 
mounting surface.  

  

 

Fig. 4. Mounting the tamper bracket. 

 

3.  Connect  the  power  cables  (230V  AC)  to  the  L-N  terminals  of  the  PSU.  Connect  the  ground  wire  to  the 

terminal  marked  with  the  PE  symbol  (power  supply  module  connector).  Use  a  three-core  cable  (with  a 
yellow  and  green  PE  protection  wire)  to make  the  connection.  The  power  cables  should  be  connected  to 
the appropriate terminals on the connection board through the bushing. 

 

The shock protection circuit shall be done with a particular care: the yellow and green 

wire coat of  the  power  cable  should be connected to  the  terminal  marked  with  
the PE  symbol. Operation of the PSU without the properly made and fully operational 

shock protection circuit is UNACCEPTABLE! It can cause damage  to  the equipment  or 
an electric shock

  

 

4.  Connect the receiver cables to the AUX terminals at the power supply board. 
5.  If needed, connect the device cables to the technical outputs: 

- EPS; technical output indicating AC power failure 
- PSU; technical output indicating PSU failure. 

- LoB; technical output indicating low battery voltage 
- Optional installation of the MPSBS relay module changing technical outputs of the OC type to relay type 

(page 9, section. 3.3) 
6.  Use  the  I

BAT

  jumper  to  set  the  maximum  battery  charging  current,  taking  into  account  the  battery 

parameters. 

7.  Use  the  P

BAT

  jumper  to  set  to  turn  on/off  deep  discharge  battery  protection  U<20V  (+/-5%). 

Deep 

discharge battery protection is ON when the P

BAT 

jumper is OFF.

 

8.  Mount the battery in the battery compartment of the enclosure (Fig. 3). Connect the batteries with the PSU 

paying special attention to the correct polarity.  

9.  Switch on the 230V AC supply. The corresponding LEDs on the power supply PCB should be ON: red AC 

and green AUX. The yellow LB LED should light up while charging. 

10.  Check  the  output  voltage  (the  power  supply  voltage  without  load  should  be  27,2

V ÷ 27,8V, 22V ÷ 27,6V 

while battery charging). If the voltage requires adjustment, use the V

ADJ

, potentiometer while monitoring the 

voltage at the AUX output of the power supply. 

11.  Check the current consumption of the receivers, taking into account the battery charging current, so as not 

to exceed the total current efficiency of the PSU (section 1.1). 

12.  Close the cover after installing and checking the operation of the power supply. 

 
 
 

Summary of Contents for PSBS 3024C

Page 1: ...PSBS 3024C v 1 0 PSBS 27 6V 3A 2x17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 4 from 03 11 2016 Supercedes edition 3 from 01 06 2016...

Page 2: ...te TABLE OF CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Install...

Page 3: ...4 3x1A AWZ575 AWZ576 2x17Ah 3 Buffer power supply PSBS 27 6V 6x0 5A 2x17Ah PSBS 3024C LB8 6x0 5A AWZ578 AWZ580 2x17Ah 4 Buffer power supply PSBS 27 6V 24V 2x17Ah PSBS 3024C RN25024 27 6V 24V 2x17Ah 5...

Page 4: ...nt FBAT fuse in the battery circuit F5A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of P...

Page 5: ...Isolation transformer Printed Circuit Board see Table 1 Fig 2 TAMPER micro switch of tamper protection NC FMAINS fuse in the power supply circuit 230V T3 15A 250V L N power supply connector 230V AC PE...

Page 6: ...rrent limitation the FBAT melting fuse failure requires fuse replacement Surge protection varistors Deep discharge battery protection UVP U 20V 0 5V disconnection of battery terminal Tamper protection...

Page 7: ...between input circuit and output or protection circuit 100 M 500V DC Table 6 Operation parameters Environmental class II Operating temperature 10 C 40 C Storing temperature 20 C 60 C Relative humidit...

Page 8: ...roperly made and fully operational shock protection circuit is UNACCEPTABLE It can cause damage to the equipment or an electric shock 4 Connect the receiver cables to the AUX terminals at the power su...

Page 9: ...icates 230V AC power failure Under normal status with the 230V AC supply on the output is shorted to ground GND In case of power failure the PSU will switch the output into hi Z high impedance state a...

Page 10: ...ntly damaged The voltage restoration at the BAT output requires fuse replacement 4 2 Running the PSU from the battery The power supply is equipped with the button on the PCB allowing to run the PSU fr...

Page 11: ...quipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they m...