background image

www.pulsar.pl                                                       

PSBS3024C                                                                  

BLUE POWER

     

 

PSU features: 

 

 

uninterruptible power supply DC 27,6V/3A  

 

battery housing: 2x17Ah/12V 

 

supply voltage AC 230V  

 

high efficiency 84% 

 

low voltage ripple 

 

battery charging and maintenance control 

 

deep discharge battery protection (UVP)  

 

battery charging current 0,5A/1A, jumper selectable  

 

START button to start the battery  

 

battery output protection against short-circuit and 
reverse connection  

 

LED indication  

 

EPS technical output of 230V power failure  
– OC type 

 

PSU technical output indicating PSU failure 

– OC type 

 

LoB technical output indicating low battery voltage 

 

– OC type  

 

Optional installation of the MPSBS relay module  
changing technical outputs of the OC type to relay 
type  

 

adjustable times of 230V AC failure indication 

 

Protection type: 

 

SCP short-circuit protection 

 

Overheat protection OHP 

 

surge protection  

 

overload protection OLP 

 

Tamper protection: enclosure opening and 

detachment from the wall 

 

warranty - 5 years from the production date 

 
TABLE OF CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of components and connectors 
1.4 Technical parameters 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Power supply operation indication. 

3.1 Optical indication of operation 
3.2 Technical outputs 
3.3 Relay technical outputs 

4. Service and operation 

4.1 Overload or short-circuit the power supply output (SCP activation) 
4.2  Running the PSU from the battery. 
4.3  Deep discharge battery protection UVP. 
4.4  Maintenance 
 

 

 
1. Technical description. 
 

1.1 General description. 

A  buffer  PSU  is  designed  for  uninterrupted  supply  of  devices  requiring  stabilized  voltage  of 

24V  DC  (+/-

15%).

 The PSU supplies voltage of 

U=27,6V DC 

and total current capacity of:

 

 

1. Output current 3A + 0,5A battery charging 

 

 

 

2. Output current 2,5A + 1A battery charging 

 

 

 

 
Total c battery is max. 3,5A 

 

In  case  of  mains  power  loss,  the  unit  will  instantly  switch  to  battery  operation.  The  PSU  is  enclosed  in  a 

metal casing (color RAL 9003) with battery housing for two 17Ah/12V batteries. The enclosure is fitted with a micro 
switch indicating door opening (front cover) and the detachment from the wall. 

 
 
 
 
 
 
 
 
 

Summary of Contents for PSBS 3024C

Page 1: ...PSBS 3024C v 1 0 PSBS 27 6V 3A 2x17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 4 from 03 11 2016 Supercedes edition 3 from 01 06 2016...

Page 2: ...te TABLE OF CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Install...

Page 3: ...4 3x1A AWZ575 AWZ576 2x17Ah 3 Buffer power supply PSBS 27 6V 6x0 5A 2x17Ah PSBS 3024C LB8 6x0 5A AWZ578 AWZ580 2x17Ah 4 Buffer power supply PSBS 27 6V 24V 2x17Ah PSBS 3024C RN25024 27 6V 24V 2x17Ah 5...

Page 4: ...nt FBAT fuse in the battery circuit F5A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of P...

Page 5: ...Isolation transformer Printed Circuit Board see Table 1 Fig 2 TAMPER micro switch of tamper protection NC FMAINS fuse in the power supply circuit 230V T3 15A 250V L N power supply connector 230V AC PE...

Page 6: ...rrent limitation the FBAT melting fuse failure requires fuse replacement Surge protection varistors Deep discharge battery protection UVP U 20V 0 5V disconnection of battery terminal Tamper protection...

Page 7: ...between input circuit and output or protection circuit 100 M 500V DC Table 6 Operation parameters Environmental class II Operating temperature 10 C 40 C Storing temperature 20 C 60 C Relative humidit...

Page 8: ...roperly made and fully operational shock protection circuit is UNACCEPTABLE It can cause damage to the equipment or an electric shock 4 Connect the receiver cables to the AUX terminals at the power su...

Page 9: ...icates 230V AC power failure Under normal status with the 230V AC supply on the output is shorted to ground GND In case of power failure the PSU will switch the output into hi Z high impedance state a...

Page 10: ...ntly damaged The voltage restoration at the BAT output requires fuse replacement 4 2 Running the PSU from the battery The power supply is equipped with the button on the PCB allowing to run the PSU fr...

Page 11: ...quipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they m...