Pulsar PSBOC1001270 Quick Start Manual Download Page 7

www.pulsar.pl 

 

 

 

 

PSBOC1001270 

 

 

 

 

 
 

- green LED  (Fig.2, element 3) indicates battery voltage level. Under normal status (U

BAT

 > 11,5V) the diode is 

permanently illuminated. In case of decrease of battery voltage (U

BAT

 < 11,5V) the diode is off. 

 

3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

FAC - absence of AC supply output: - OC type output that indicates AC power loss. Under normal status, 
with 230V AC supply, the output is connected to ground (L level – 0V). In case of power loss, the PSU will 
switch the output into high impedance state hi-Z after approx. 10s. 
 

 

FAC - absence of AC supply output: - relay output indicating the absence of AC supply. In case of power 
loss, the PSU module will switch the relay contacts after approx. 10 seconds. 
 

 
CAUTION! In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 
power (AC power failure). 
 
 

 

 

FPS  –  technical  output  indicating  absence  of  DC  voltage  at  the  PSU:  OC  type  output  indicating  the 
PSU failure. In normal state (during correct operation) the output is connected to ground (L level – 0V). In 
case of absence of DC voltage at the output (e.g. short circuit), the output is switched into high impedance 
state – hi-Z. 

 

 

FLB – technical output indicating battery voltage: OC type output. Under normal status (U

BAT

 > 11,5V) 

the output is connected to ground (L level – 0V). In case of decrease of battery voltage (U

BAT

 < 11,5V) the 

output is switched into high impedance state – hi-Z. 
 

 

Fig. 4. Electrical diagram of OC outputs. 

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU module output 
In case of an overload or a short circuit at the PSU output, the output voltage is automatically cut off. The 

voltage is restored automatically after removing the failure (overload). 

 
4.2 Battery-assisted operation.  
In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

 
 

 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the 

battery-assisted  operation,  reducing  voltage  below  9,5V  at  the  battery  terminals  will  cause 
battery disconnection. 

 
 
 
4.3 Maintenance 
Any  and  all  maintenance  operations  may  be  performed  following  the  disconnection  of  the  PSU  from  the 

power  supply  network.  The  PSU  does  not  require  performing  any  specific  maintenance  measures.  However,  in 
case of significant dust ingress, it is recommended to clean the PSU with compressed air. 

 
 
 
 
 
 
 

Summary of Contents for PSBOC1001270

Page 1: ...PSBOC1001270 v 1 0 PSBOC 13 8V 7A OC Caged switched mode buffer power supply unit EN Edition 1st 10th Mar 2012...

Page 2: ...gram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status...

Page 3: ...age 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type 7 FLB output indicating battery low voltage OC type 8...

Page 4: ...e adjustment range 12 14V DC Ripple voltage 120 mV p p max Current consumption by PSU systems 40 mA Battery charging current 1A 2A jumper selectable Short circuit protection SCP electronic Battery cir...

Page 5: ...ulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSU is to be mounted by a...

Page 6: ...outputs to the central or other device 6 Connect the battery in accordance with the signs colours 7 Once the tests and operation control have been completed the enclosure cabinet can be locked Fig 3 M...

Page 7: ...e at the output e g short circuit the output is switched into high impedance state hi Z FLB technical output indicating battery voltage OC type output Under normal status UBAT 11 5V the output is conn...

Page 8: ...ys from the delivery to the service centre of the manufacturer 7 The repair period mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equip...

Reviews: