Pulsar PSBOC1001270 Quick Start Manual Download Page 6

www.pulsar.pl 

 

 

 

 

PSBOC1001270 

 

 

 

 

 
 

 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the ‘PE’ terminal. Using the PSU 
without a properly made and fully operational shock protection circuit is UNACCEPTABLE! 
It can cause a device failure or an electric shock. 
 

 

 

4. Connect load/loads to proper output connectors of the power supply (positive pole is marked as +V, 
negative pole as -V) 
5. Connect the technical outputs to the central or other device. 
6. Connect the battery in accordance with the signs (colours). 
7. Once the tests and operation control have been completed, the enclosure/cabinet can be locked. 

 

 

Fig 3. Mechanical view of the PSU. 

 
3. Operating status indication. 
 

3.1 LED indication 

 

The PSU is equipped with 3 LEDs on the PCB board: 

 - red LED (Fig.2, element 1) normal status (AC power): permanently illuminated. AC power absence is 
indicated by the AC diode going out.  
Caution! LED indicates power absence if the outage lasts >10s. 

 

-  green  LED  (Fig.2,  element  2)  indicates  DC  power  at  the  PSU  output.  Under  normal  status  the  diode  is 
permanently illuminated. In case of a short circuit or an overload, the diode is off. 
 

Summary of Contents for PSBOC1001270

Page 1: ...PSBOC1001270 v 1 0 PSBOC 13 8V 7A OC Caged switched mode buffer power supply unit EN Edition 1st 10th Mar 2012...

Page 2: ...gram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status...

Page 3: ...age 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type 7 FLB output indicating battery low voltage OC type 8...

Page 4: ...e adjustment range 12 14V DC Ripple voltage 120 mV p p max Current consumption by PSU systems 40 mA Battery charging current 1A 2A jumper selectable Short circuit protection SCP electronic Battery cir...

Page 5: ...ulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSU is to be mounted by a...

Page 6: ...outputs to the central or other device 6 Connect the battery in accordance with the signs colours 7 Once the tests and operation control have been completed the enclosure cabinet can be locked Fig 3 M...

Page 7: ...e at the output e g short circuit the output is switched into high impedance state hi Z FLB technical output indicating battery voltage OC type output Under normal status UBAT 11 5V the output is conn...

Page 8: ...ys from the delivery to the service centre of the manufacturer 7 The repair period mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equip...

Reviews: