Features: 

 

 

13,8VDC/7A uninterrupted supply 

 

wide range of supply voltage 176÷264VAC  

 

high efficiency 80% 

     battery charge and maintenance control 

     deep discharge battery protection (UVP) 

 

battery charging current 1A/2A 

     battery output protection against short circuit 

and reverse polarity connection 

     LED indication 

 

 

FAC technical output indicating AC power loss 

 

FPS technical output indicating PSU failure 

 

FLB technical output indicating battery low 
voltage 

 

protections: 

 

SCP short-circuit protection 

 

OVP over voltage protection 

 

surge protection (AC output) 

 

OLP overload protection 

 

 

 
CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication of operating status 
3.2 Technical outputs

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU output  
4.2. Battery-assisted operation 

 

4.3. Maintenance 

 
1. Technical description. 
 

1.1 General description 
A buffer PSU is intended for an uninterrupted supply to devices requiring stabilized voltage of 12 V DC 

 (+/-15%). The PSU provides voltage of U=13,8 V DC current efficiency: 

 

                                               1. Output current 6A + 1A battery charging 
                                               2. Output current 5A + 2A battery charging 

                                       Total device c battery: 7A max. 

 
 

         In the case of power failure from prime supply, the unit is instantly switched to battery 
assisted operation.

 

The power supply unit features: short circuit, overload, surge and over voltage 

protections. 

 

 

 

 

 

 

 

 

Summary of Contents for PSBOC1001270

Page 1: ...PSBOC1001270 v 1 0 PSBOC 13 8V 7A OC Caged switched mode buffer power supply unit EN Edition 1st 10th Mar 2012...

Page 2: ...gram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status...

Page 3: ...age 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type 7 FLB output indicating battery low voltage OC type 8...

Page 4: ...e adjustment range 12 14V DC Ripple voltage 120 mV p p max Current consumption by PSU systems 40 mA Battery charging current 1A 2A jumper selectable Short circuit protection SCP electronic Battery cir...

Page 5: ...ulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSU is to be mounted by a...

Page 6: ...outputs to the central or other device 6 Connect the battery in accordance with the signs colours 7 Once the tests and operation control have been completed the enclosure cabinet can be locked Fig 3 M...

Page 7: ...e at the output e g short circuit the output is switched into high impedance state hi Z FLB technical output indicating battery voltage OC type output Under normal status UBAT 11 5V the output is conn...

Page 8: ...ys from the delivery to the service centre of the manufacturer 7 The repair period mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equip...