Pulsar PSBOC1001270 Quick Start Manual Download Page 4

www.pulsar.pl 

 

 

 

 

PSBOC1001270 

 

 

 

 

 
 

 

 

Fig. 2. The view of the PSU. 

1.4 Specifications: 
- electrical specifications (tab.2) 
- mechanical specifications (tab.3) 
- operation safety (tab.4) 
- operating specifications (tab.5) 

 

     Electrical specifications (tab. 2). 
 

Mains supply 

176 ÷ 264V AC 

Current consumption 

0,95A@230VAC max.  

PSU power  

100W max.  

Efficiency 

80% 

Output voltage 

11V÷ 13,8V DC – buffer operation 
9,5V÷13,8V DC – battery-assisted operation 

Output current 

6A + 1A battery charge 
5A + 2A battery charge 

Output current t

AMB

<30°C 

6A + 1A battery charge – see chart 1 
5A + 2A battery charge – see chart 1
 

Output current t

AMB

=40°C 

4,9A + 0,1A battery charge - see chart 1 

3,9A + 2A battery charge - see chart 1 

Voltage adjustment range 

12÷14V DC 

Ripple voltage 

120 mV p-p max. 

Current consumption by PSU systems 

40 mA  

Battery charging current 

1A/2A jumper selectable 

Short-circuit protection SCP  

electronic

 

Battery circuit protection SCP and reverse 
polarity connection

 

polymer fuse 

Deep discharge protection UVP 

U<9,5V (± 5%) – disconnection of the battery terminal 

Technical outputs: 

- FAC; output indicating AC power 
failure 

  
 
 
 
 
- FPS; output indicating DC absence/PSU 
failure 
-FLB output indicating battery low voltage 

 
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s. 
CAUTION!  In  Fig.2.  the  contact  set  in  the  potential-free  status 
corresponds to a state with no AC power (AC power failure). 
- OC type, 50mA max., normal status: L (0V) level, failure: hi-Z 
level, time lag: 10s. 
 
 
- OC type, 50mA max., normal status: L (0V) level, failure: hi-Z  
 
- OC type, 50mA max., normal status: (U

BAT

 >11,5V): L (0V), 

 failure: (U

BAT

 <11,5V): hi-Z level 

 

Summary of Contents for PSBOC1001270

Page 1: ...PSBOC1001270 v 1 0 PSBOC 13 8V 7A OC Caged switched mode buffer power supply unit EN Edition 1st 10th Mar 2012...

Page 2: ...gram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status...

Page 3: ...age 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type 7 FLB output indicating battery low voltage OC type 8...

Page 4: ...e adjustment range 12 14V DC Ripple voltage 120 mV p p max Current consumption by PSU systems 40 mA Battery charging current 1A 2A jumper selectable Short circuit protection SCP electronic Battery cir...

Page 5: ...ulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSU is to be mounted by a...

Page 6: ...outputs to the central or other device 6 Connect the battery in accordance with the signs colours 7 Once the tests and operation control have been completed the enclosure cabinet can be locked Fig 3 M...

Page 7: ...e at the output e g short circuit the output is switched into high impedance state hi Z FLB technical output indicating battery voltage OC type output Under normal status UBAT 11 5V the output is conn...

Page 8: ...ys from the delivery to the service centre of the manufacturer 7 The repair period mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equip...

Reviews: