www.pulsar.pl
PSBEN3012C/LCD
BLACK POWER
26
-
press the „SET” button, the prompt will appear at the end of the line
-
use the „<” or „>” buttons to select
YES
– if the battery is connected to the power supply
NO
– if the battery is not connected to the power supply
-
confirm by pressing the „SET” button
6.2.2
Battery test ON/OFF.
This function allows to enable or disable the battery test (see section 7.3) during which the power supply
measures the electrical parameters in accordance with the implemented measurement procedure.
-
use the „<” or „>” buttons to display the
Battery test
menu
-
press the „SET” button, the prompt will appear at the end of the line
-
use the „<” or „>” buttons to select
ON
– battery test ON
OFF
– battery test OFF
-
confirm by pressing the „SET” button
Enabling/disabling the battery test using the STOP button on the printed circuit board of the power supply.
Press and hold the STOP button on the printed circuit board for 3 seconds during mains operation of the
PSU. The device will confirm the activation or deactivation of the test:
Single beep
Double beep
Enabling/disabling the battery test
is stored is stored even after the device is disconnected from the
power supply. Disabling the test also disables the battery failure indication at the APS FLT output
but does not disable the deep discharge battery protection.