I N S T R U C T I O N   M A N U A L

KEPCO

An ISO 9001 Company.

HSF-1UR

50W SERIES

KEPCO SINGLE OUTPUT, 1U, 50 WATT 

HOT SWAP PLUG-IN POWER SUPPLIES

I — INTRODUCTION

The Kepco HSF-1UR, 50 Watt Series hot swappable, high
frequency switching, plug-in power supplies with built-in
power factor correction (PFC) employ forward conversion
and are designed to operate in a fault tolerant power sys-
tem with either a-c or d-c input. A thermistor soft-start cir-
cuit limits start-up surge. Built-in OR-ing diodes (all models)
and a forced current share circuit (all models except 3.3V)
allow configuration of all models for hot-swap and parallel-
redundant N+1 operation. Outputs of 3.3, 5, 12, 15, 24, 28
or 48V are available (see Table 1). 

These power supplies are designed to be used with
Kepco’s Series RA 19-1U rack adapters. The RA 19-1U
rack adapter accepts up to four 50 Watt, 100 Watt or 150
Watt units (see Figure 2). All input/output connections are
through a 24-pin connector that plugs in to the rack
adapter. All external connections are made through the
rack adapter. I/O signals and implementation of HSF
options are described in detail in the RA 19-1U Rack
Adapter Manual. Surface mount technology permits effi-
cient component layout for minimum mounting space. 

EMI filtering is designed to meet FCC Class B rating and
VDE 0871 Class B rating. Table 1 contains specifications
that vary for each model of the HSF-1UR 50 Watt Series.
Common specification are listed on page 5. 

OPTIONS.  

There are four options available: T, C, X and

Y. Features for all models are the same, except as follows:

The heart of the standard 50W HSF-1UR (no options) mod-
els is a Kepco RKW power supply (28V model not avail-
able). 

T option (-1URT) models use a Kepco RTW power supply
instead of the RKW. T option models weigh less, and have
improved efficiency (input current) specifications. All volt-
ages are available.

C option (-1URC) models include a current sensing resis-
tor, allowing external current monitoring within ±10% (con-
tact Kepco if greater accuracy required). In addition, a 28V
model is available with Option C. All voltages are available.

X option (-1URX) remote control models are identical to T
option, but also include the ability to turn the unit on and off
from a remote location. All voltages are available.

Y option models (-1URY) are identical to T option, but also
include both current monitoring and remote on-off capabili-
ties. All voltages are available.

When the input is cut off, the output is maintained for 15
milliseconds minimum (25 for T, C, X and Y models). If the
power supply shuts down due to an output overvoltage
condition, it is then necessary to wait 60 seconds minimum
(30 for T, C, X and Y models) before turning the unit on
again. 

II — FEATURES

FRONT PANEL ACCESS. 

 

The front panel provides a

power ON/OFF switch controlling input power and a “VDC
ON” light which indicates when the unit is operating. 

NOTE:

The ON/OFF switch must be set to OFF before remov-
ing unit from rack adapter.

 The front panel “MASTER

ON” LED lights when 1) the unit operates independently, or
2) the unit is used in parallel redundant configurations while
a) the output is less than 10% of nominal or b) the output is
within 10% to 100% of nominal and the unit is functioning

as a master. In parallel redundant configurations, the mod-
ule with the highest voltage functions as the master. The
other units are slaves, and track the output voltage of the
master. Refer to 

Current Share Bus (CSB)

 on page 4 for

details. The front panel Vadj trimmer provides adjustment of
the output voltage within the limits specified in Table 1; test
points connected to the +S and –S lines are available at the
front panel for measuring the output. 

Summary of Contents for HSF-1UR 50W Series

Page 1: ...od els is a Kepco RKW power supply 28V model not avail able T option 1URT models use a Kepco RTW power supply instead of the RKW T option models weigh less and have improved efficiency input current specifications All volt ages are available C option 1URC models include a current sensing resis tor allowing external current monitoring within 10 con tact Kepco if greater accuracy required In additio...

Page 2: ...T CURRENT NOMINAL 3 10A 10A 4 3A 3 5A 2 2A 3 2A Peak 8 1 8A 1 1A CURRENT LIMIT 4 10 5A min 10 5A min 4 5A min 3 68A min 3 3A 2 3A 9 min 1 9A min 1 15A min OUTPUT POWER MAX 5 33W 50W 51 6W 52 5W 52 8W 50 4W 52 8W SHORT CIRCUIT CURRENT 4 15A 15 5 9 12 6A 5 6A 5 4A 4 5 9 3A 9 2 5A 2 4A 1 7A 9 RIPPLE AND NOISE mV p p 0 40 C 10 100 LOAD switching typ 80 80 100 100 100 150 200 spike noise d c 50MHz 120 ...

Page 3: ... drop across REQ is measured across IMON pins requires millivoltmeter range 0 to 250mV Accuracy is 10 contact Kepco if greater accuracy is required There is no isolation between IMON alarm circuit and d c out put Refer to the applicable RA 19 1U Manual for details ALARM CIRCUIT The HSF 1UR includes an isolated internal relay offering normally closed and normally open contacts referenced to an isol...

Page 4: ...indicates that forced current share is no longer work ing units are simply in current share mode If forced cur rent sharing at less than 10 nominal current per supply is needed contact Kepco application engineering Remote sensing is recommended For master slave oper ation to work properly each unit should be adjusted to 40 mV optimum less than the next paralleled unit unit 1 is adjusted to VOUT un...

Page 5: ...ces less than 4 output excursion Recovery occurs to within 1 of the original setting in 2 ms load change tr or tf equal to or greater than 50µsec START UP TIME 500 ms maximum HOLDUP TIME 1UR 20 ms typ 120V a c 15 ms min 100V a c Options T C X and Y all except 3 3V and 28V mod els 30ms typ 20ms min Options T C X and Y 3 3V model 55ms typ 40ms min Options T C X and Y 28V model 35ms typ 25ms min DIEL...

Page 6: ... Adapter CAUTION The ON OFF switch must be set to OFF before removing the unit from the rack adapter V OPERATION Turn the unit on using the front panel POWER switch see Figure 6 CAUTION DO NOT repeatedly toggle the POWER on off switch as this may cause unit to fault When output voltage is available the VDC ON LED is on green All 50W models use convection cooling and do not include a fan While moni...

Page 7: ...MENSIONS ARE IN INCHES DIMENSIONS IN BRACKETS ARE IN MILLIMETERS FRONT PANEL KEPCO DUAL TONE GRAY C FRONT PANEL 0 090 THK ALUM 6061 T6 A BACKPLATE 0 064 THK ALUM 5052 H32 3 MODULE IS KEYED AS SHOWN IN DETAIL 0 591 15 0 1 MATERIAL B PCB 0 063 THK FR 4 2 FINISH KEY PIN LOCATION 48 VOLTS 28 VOLTS 24 VOLTS 15 VOLTS 5 VOLTS 3 3 VOLTS 12 VOLTS 0 129 3 3 3 755 95 4 0 303 7 7 0 690 17 5 4 275 108 6 0 260 ...

Reviews: