background image

www.pulsar.pl

                                                      

HPSBOC1824B  

         

 

2

 

Features: 

 

 

DC 27,6V/1,5A uninterruptible power supply  

 

fitting battery: 2x 7Ah/12V  

 

wide range of mains supply: 176÷264V  

 

high efficiency 77% 

 

battery charging and maintenance control 

 

excessive discharging (UVP) protection 

 

battery charge current 0,3A 

 

battery output full protection against short-
circuit and reverse polarity connection 

 

LED indication  

 

 

FAC technical output indicating AC power loss 

 

FPS technical output indicating PSU failure 

 

FLB technical output indicating battery low 
voltage 

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage protection  

 

against sabotage 

 

overload protection (OLP) 

 

warranty – 2 year from the production date

 

 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors. 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication of operating status 
3.2 Technical outputs

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU output (SCP on) 
4.2 Battery-assisted operation  
4.3 Maintenance 

 

 
1. Technical description. 
 

1.1 General description. 
A buffer PSU is intended for uninterrupted supply to devices that require stabilised voltage of 24 V DC (+/-

15%). The PSU provides voltage of U=27,6 V DC with output current of I=1,5A + 0,3A for battery charge.  In case 
of power decay, a battery back-up is activated immediately.  The PSU is constructed based on the switch mode 
PSU, with high energy efficiency. The PSU is housed in a metal enclosure (colour RAL 9003) which can 
accommodate two 7Ah/12V batteries. A micro switch indicates door opening (front cover). 

 

During normal operation, the total current drawn by the equipment may not exceed I = 1,5 A;  

Maximum battery charge current: 0.3 A. Total device c battery: 1,8 A max. 

 

OPTIONAL POWER SUPPLY CONFIGURATIONS:  

(visualisation available at: www.pulsar.pl) 

 

1. Buffer power supply unit  HPSBOC 27,6V/2x0,75A/2x7Ah. 

- HPSBO  LB2 2x0,75A (AWZ586) + 2x7Ah 

2. Buffer power supply unit  HPSBOC 27,6V/3x0,5A/2x7Ah. 

- HPSBO  LB4 3x0,5A (AWZ574 or AWZ576) + 2x7Ah 

3. Buffer power supply unit  HPSBOC 27,6V/24V/1,5A/2x7Ah. 

- HPSBO RN25024 (27,6V/24V) + 2x7Ah 

4. Buffer power supply unit  HPSBOC 27,6V/24V/2x0,75A/2x7Ah. 

- HPSBO RN25024 (27,6V/24V) + LB2 2x0,75A (AWZ586) + 2x7Ah 

5. Buffer power supply unit  HPSBOC 27,6V/24V/3x0,5A/2x7Ah. 

       - HPSBO RN25024 (27,6V/24V) + LB4 3x0,5A (AWZ574 or AWZ576) + 2x7Ah 

6. Buffer power supply unit  HPSBOC 27,6V/5V÷18V/5V÷18V/2A÷1,3A/2x7Ah. 

       - HPSBO DCDC20 (5V÷18V/2A÷1,3A) + 2x7Ah 

 

Summary of Contents for HPSBOC 1824B

Page 1: ...HPSBOC 1824B v 1 0 HPSBOC 27 6V 1 5A 2x7Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 2 from 07 03 2013 Supersedes edition 1 from 13 02 2013...

Page 2: ...r PSU is intended for uninterrupted supply to devices that require stabilised voltage of 24 V DC 15 The PSU provides voltage of U 27 6 V DC with output current of I 1 5A 0 3A for battery charge In cas...

Page 3: ...e 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type 7 FLB output indicating battery low voltage OC type 8 VA...

Page 4: ...y 77 Output voltage 22V 27 6V DC buffer operation 19V 27 0V DC battery assisted operation Output current 1 5A 0 3A battery charge Output current tAMB 30 C 1 5 A 0 3A battery charge refer to chart 1 Ou...

Page 5: ...ers tab 4 Enclosure dimensions 285 x 297 x 80 8 280 x 292 x 80 WxHxD Fixation See figure 3 Fitting battery 2x 7Ah 12V SLA max Net gross weight 2 20kg 2 40kg Enclosure Steel plate DC01 0 7mm colour RAL...

Page 6: ...over the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Inst...

Page 7: ...s permanently illuminated In case of decrease of battery voltage UBAT 23V the diode is off 3 2 Technical outputs The PSU has indication outputs FAC absence of AC supply output OC type output that indi...

Page 8: ...switched into a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminal...

Page 9: ...t within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs o...

Reviews: