Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 

 

2. Installation. 

 

2.1 Requirements. 

 

The buffer PSU shall be mounted by a qualified installer with appropriate  permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  positi on  that 
guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 
Before installation, prepare a PSU load balance. During normal operation, the total current drawn 

by the device may not exceed I = 1,5 A;  Maximum battery charge current: 0.3 A. Total device c 
battery: 1,8 A max. 

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 
 

2.2 Installation procedure. 
 

1. Before installation, cut off the voltage in the 230V power-supply circuit. 
2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 
earth symbol PE (PSU module connector). Use a three-core cable (with a yellow and green PE protection wire) to 
make the connection. Lead the cables to the appropriate clips through the insulating bushing of the connection 
board. 
 
 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the terminal - marked with  

 symbol on the PSU enclosure. Operation of the PSU without the properly made and 

fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  a  device 
failure or an electric shock. 

 
4. Connect the receivers’ cables to the terminals 

V+ (+), V-(-) 

of the PSU module.  

5. Connect the power (~230V) 
6. Connect the battery (mind the colours):   
- battery output (+V):  BAT+ cable / red, 
- battery output (0V):  BAT – cable / GND / black. 

Summary of Contents for HPSBOC 1824B

Page 1: ...HPSBOC 1824B v 1 0 HPSBOC 27 6V 1 5A 2x7Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 2 from 07 03 2013 Supersedes edition 1 from 13 02 2013...

Page 2: ...r PSU is intended for uninterrupted supply to devices that require stabilised voltage of 24 V DC 15 The PSU provides voltage of U 27 6 V DC with output current of I 1 5A 0 3A for battery charge In cas...

Page 3: ...e 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type 7 FLB output indicating battery low voltage OC type 8 VA...

Page 4: ...y 77 Output voltage 22V 27 6V DC buffer operation 19V 27 0V DC battery assisted operation Output current 1 5A 0 3A battery charge Output current tAMB 30 C 1 5 A 0 3A battery charge refer to chart 1 Ou...

Page 5: ...ers tab 4 Enclosure dimensions 285 x 297 x 80 8 280 x 292 x 80 WxHxD Fixation See figure 3 Fitting battery 2x 7Ah 12V SLA max Net gross weight 2 20kg 2 40kg Enclosure Steel plate DC01 0 7mm colour RAL...

Page 6: ...over the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Inst...

Page 7: ...s permanently illuminated In case of decrease of battery voltage UBAT 23V the diode is off 3 2 Technical outputs The PSU has indication outputs FAC absence of AC supply output OC type output that indi...

Page 8: ...switched into a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminal...

Page 9: ...t within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs o...

Reviews: