RED LED: 

 

on – the PSU is supplied with 230V AC  

 

off – no 230V AC supply  

 

GREEN LED: 

 

on – DC voltage in the AUX output of the PSU 

 

off – no DC voltage in the AUX output of the PSU 

 

7. Check the PSU operation indicator: green LED. 
8. Check the PSU output voltage: 
- the PSU voltage without load should amount to U=27,6V DC.   
9. After installing and checking proper working, the enclosure can be closed. 
 
3. Operating status indication. 

 
3.1 LED indication of operating status. 
The PSU is equipped with two diodes on the front panel: 
 
 
 

 

 
 
 
 
Moreover, the PSU is equipped with 3LEDs on the PCB board: 

 - red LED (Fig.2, element 1) normal status (AC power): permanently illuminated. AC power absence is 
indicated by the AC diode going out.  
Caution! LED indicates power absence if the outage lasts >10s. 

 

-  green  LED  (Fig.2,  element  2)  indicates  DC  power  at  the  PSU  output.  Under  normal  status  the  diode  is 
permanently illuminated. In case of a short circuit or an overload, the diode is off. 
 
- green LED  (Fig.2, element 3) indicates battery voltage level. Under normal status (U

BAT

 > 23V) the diode is 

permanently illuminated. In case of decrease of battery voltage (U

BAT

 < 23V) the diode is off. 

 

 

3.2 Technical outputs

 

The PSU has indication outputs: 
 
FAC  -  absence  of  AC  supply  output:  -  OC  type  output  that  indicates  AC  power  loss.  Under  normal  status, 

with 230V AC supply, the output is connected to ground (L level – 0V). In case of power loss, the PSU will 
switch the output into high impedance state hi-Z after approx. 10s. 
 

FAC  -  absence  of  AC  supply  output:  -  relay  output  indicating  the  absence  of  AC  supply.  In  case  of  power 

loss, the PSU module will switch the relay contacts after approx. 10 seconds. 
 

 
CAUTION! In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 
power (AC power failure). 
 
 

 
FPS – technical output indicating absence of DC voltage at the PSU: OC type output  indicating the PSU 

failure. In normal state (during correct operation) the output is connected to ground (L level – 0V). In case 
of absence of DC voltage at the output (e.g. short circuit), the output is switched into high impedance state 
– hi-Z. 

 

FLB  –  technical  output  indicating  battery  voltage:  OC  type  output.  Under  normal  status  (U

BAT

  >  23V)  the 

output is connected to ground (L level – 0V). In case of decrease of battery voltage (U

BAT

 < 23V) the output 

is switched into high impedance state – hi-Z. 
 

Summary of Contents for HPSBOC 1824B

Page 1: ...HPSBOC 1824B v 1 0 HPSBOC 27 6V 1 5A 2x7Ah OC Buffer switch mode power supply unit with automatic operation control EN Edition 2 from 07 03 2013 Supersedes edition 1 from 13 02 2013...

Page 2: ...r PSU is intended for uninterrupted supply to devices that require stabilised voltage of 24 V DC 15 The PSU provides voltage of U 27 6 V DC with output current of I 1 5A 0 3A for battery charge In cas...

Page 3: ...e 4 FAC AC absence technical output relay type 5 FAC AC absence technical output OC type 6 FPS output indicating DC absence PSU failure OC type 7 FLB output indicating battery low voltage OC type 8 VA...

Page 4: ...y 77 Output voltage 22V 27 6V DC buffer operation 19V 27 0V DC battery assisted operation Output current 1 5A 0 3A battery charge Output current tAMB 30 C 1 5 A 0 3A battery charge refer to chart 1 Ou...

Page 5: ...ers tab 4 Enclosure dimensions 285 x 297 x 80 8 280 x 292 x 80 WxHxD Fixation See figure 3 Fitting battery 2x 7Ah 12V SLA max Net gross weight 2 20kg 2 40kg Enclosure Steel plate DC01 0 7mm colour RAL...

Page 6: ...over the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Inst...

Page 7: ...s permanently illuminated In case of decrease of battery voltage UBAT 23V the diode is off 3 2 Technical outputs The PSU has indication outputs FAC absence of AC supply output OC type output that indi...

Page 8: ...switched into a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminal...

Page 9: ...t within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs o...

Reviews: