1.4 Specifications:  

- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operation safety (tab.5) 
- operating parameters (tab.6) 

 
     Electrical parameters (tab. 3) 

Mains supply 

176÷264V AC  

Current up to 

0.95A@230VAC  

Supply power 

100W max.  

Efficiency 

80% 

Output voltage 

11V 

÷ 13,8V DC – buffer operation 

9,5V 

÷ 13,8V DC – battery-assisted operation 

Output current t

AMB

<30°C 

6A + 1A battery charge - see chart 1 
5A + 2A battery charge - see chart 1 

Output current t

AMB

=40°C 

4,9A + 1A battery charge - see chart 1 
3,9A + 2A battery charge - see chart 1

 

Voltage adjustment range 

12

÷14VDC 

Ripple 

120mV p-p max. 

Current consumption by PSU systems  

60 mA 

Battery charge current 

1A or 2A max. @ 17Ah (

± 5%) – jumper selectable 

Short-circuit protection SCP 

electronic, automatic recovery 

Overload protection OLP 

105-150% of power supply, automatic recovery 

Battery circuit protection SCP and reverse 
polarity connection 

polymer fuse 

Surge protection 

varistors 

Overvoltage protection OVP 

>16V (automatic recovery) 

Excessive discharge protection UVP 

U<9,5V (

± 5%) – disconnect of connection battery 

Tampering protection system: 
- TAMPER 

– indicating unwanted opening of the 

PSU’s enclosure 

- a microswitch, NC contacts (enclosure closed) 
0,5A@50V DC (max.) 

LED indication:  
- AC diode indicating AC power status 
- AUX diode indicating DC power status at 
the PSU output 
- BAT diode indicating battery voltage level 

- red, normal status 

– on, failure: off 

- green, normal status 

– on, failure: off 

 
- green, normal status 

– on, failure: off 

Technical outputs: 
- EPS; output indicating AC power failure 
 
 
 
- PSU; output indicating DC absence/PSU failure 
 
 
 
- LoB output indicating battery low voltage 
 
 

 
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s. 
- OC type, 50mA max., normal status: L (0V) level, 
failure: hi-Z level, time lag: 10s. 
 
- relay type: 1A@ 30VDC/50VAC 
- OC type, 50mA max., normal status: L (0V) level, 
failure: hi-Z level  
 
- relay type: 1A@ 30VDC/50VAC 
- OC type, 50mA max., normal status: (U

BAT

 >11,5V): L 

(0V) level,  failure: (U

BAT

 <11,5V): hi-Z level 

The power supply unit does not feature a battery 
detection function. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for GREEN POWER PLUS HPSBOC 7012C

Page 1: ...HPSBOC 7012C v 1 1 HPSBOC 13 8V 6A 17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 9 from 01 03 2018 Supercedes edition 8 from 01 06 2016 GREEN POWER plus...

Page 2: ...load or short circuit of the PSU output SCP on 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to de...

Page 3: ...he PSU 1 3 Description of the module s components and connectors Table 1 Elements of the module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC...

Page 4: ...ER plus 4 Fig 2 The view of the PSU Description of PSU components and connectors tab 2 fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 Output terminals of...

Page 5: ...ction polymer fuse Surge protection varistors Overvoltage protection OVP 16V automatic recovery Excessive discharge protection UVP U 9 5V 5 disconnect of connection battery Tampering protection system...

Page 6: ...protection circuit 100 M 500V DC Operating parameters tab 6 Operating temperature 10 C 40 C see chart 1 Storage temperature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during ope...

Page 7: ...nd green wire coat of the power cable shall stick to one side of the terminal marked with symbol on the PSU enclosure Operation of the PSU without the properly made and fully operational shock protect...

Page 8: ...V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contacts of the relay change over CAUTION...

Page 9: ...o a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5V at the battery terminals will caus...

Page 10: ...l waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the appl...

Reviews: