3.2 Technical outputs

 

The PSU has indication outputs: 
 

 

EPS - absence of AC supply output

:  

-  OC  type  output  that  indicates  AC  power  loss.  Under  normal  status,  with  230V  AC  supply,  the  output  is 

connected  to  ground  (L  level 

–  0V).  In  case  of  power  loss,  the  PSU  will  switch  the  output  into  high 

impedance state hi-Z after approx. 10s. 

relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the relay 

contacts after approx. 10 seconds. 

 
 

CAUTION!

 In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 

power (AC power failure). 
 

 

 

PSU 

– technical output indicating absence of DC voltage at the PSU

-  OC type output indicating the PSU failure. In normal state (during correct operation) the output is connected 

to ground  (L  level 

– 0V). In case of absence of DC voltage at the output (e.g. short circuit), the output is 

switched into high impedance state 

– hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION!

  In  the  Fig.2.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 

corresponds to a state with no DC power (PSU failure). 

 

 

LoB 

– technical output indicating battery voltage

:  

- OC type output. Under normal status (U

BAT

 > 11,5V) the output is connected to ground (L level 

– 0V). In case 

of decrease of battery voltage (U

BAT

 < 11,5V) the output is switched into high impedance state 

– hi-Z. 

      -  relay output. In case of a battery voltage drop U

BAT

 < 11,5V, the contacts of the relay change over. 

       The  power  supply  unit  does  not  feature  a  battery  detection  function.  In  the  case  of  no  battery  or  non  battery 

connected, the output is in the normal mode. 

 
 

CAUTION!

 In the Fig.2. the set of contacts shows a potential-free status of the relay which 

corresponds to a state with low battery level (U

BAT

 <11,5V). 

 

 

Fig. 4. Electrical diagram of OC outputs. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Summary of Contents for GREEN POWER PLUS HPSBOC 7012C

Page 1: ...HPSBOC 7012C v 1 1 HPSBOC 13 8V 6A 17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 9 from 01 03 2018 Supercedes edition 8 from 01 06 2016 GREEN POWER plus...

Page 2: ...load or short circuit of the PSU output SCP on 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to de...

Page 3: ...he PSU 1 3 Description of the module s components and connectors Table 1 Elements of the module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC...

Page 4: ...ER plus 4 Fig 2 The view of the PSU Description of PSU components and connectors tab 2 fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 Output terminals of...

Page 5: ...ction polymer fuse Surge protection varistors Overvoltage protection OVP 16V automatic recovery Excessive discharge protection UVP U 9 5V 5 disconnect of connection battery Tampering protection system...

Page 6: ...protection circuit 100 M 500V DC Operating parameters tab 6 Operating temperature 10 C 40 C see chart 1 Storage temperature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during ope...

Page 7: ...nd green wire coat of the power cable shall stick to one side of the terminal marked with symbol on the PSU enclosure Operation of the PSU without the properly made and fully operational shock protect...

Page 8: ...V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contacts of the relay change over CAUTION...

Page 9: ...o a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5V at the battery terminals will caus...

Page 10: ...l waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the appl...

Reviews: