background image

www.pulsar.pl                                                      HPSBOC7012C                                                             

GREEN POWER plus

 

 

 

6

 

Mechanical parameters (tab. 4) 

Dimensions 

W=280, H=292, D+D

1

=82+8 [+/- 2mm] 

W

1

=285, H

1

=296 [+/- 2mm] 

The dimensions of the 
battery compartment 

190x170x75mm (WxHxD) max 

Fixation 

See figure 2 

Net/gross weight 

2,3kg / 2,5kg 

Enclosure  

Steel plate, DC01 0,7mm colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front), (lock assembly possible) 

Connectors 

Power supply: 

Φ0,63-2,50 (AWG 22-10) 

Outputs: Φ0,63-2,50 (AWG 22-10), battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The enclosure does not adjoin the assembly surface so that cables can be led. 

     

   

      Operation safety (tab.5) 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

      
     Operating parameters (tab.6) 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 

2. Installation. 

 

2.1 Requirements. 

             

The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall be 
mounted in confined spaces, according to the environment class II, with normal air humidity (RH=90% max. without 
condensation) and the temperature from -

10°C to +40°C. The PSU shall work in a vertical position that guarantees 

sufficient convectional air-flow through ventilating holes of the enclosure. 

 

             Before installation, prepare a PSU load balance. 

1.  Output current 6A + 1A battery charge

*

 

2.  Output current 5A + 2A battery charge

*

 

                                                       Total device c battery: 7A max

*

                                                 

*

 

See chart 1

 

Summary of Contents for GREEN POWER PLUS HPSBOC 7012C

Page 1: ...HPSBOC 7012C v 1 1 HPSBOC 13 8V 6A 17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 9 from 01 03 2018 Supercedes edition 8 from 01 06 2016 GREEN POWER plus...

Page 2: ...load or short circuit of the PSU output SCP on 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to de...

Page 3: ...he PSU 1 3 Description of the module s components and connectors Table 1 Elements of the module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC...

Page 4: ...ER plus 4 Fig 2 The view of the PSU Description of PSU components and connectors tab 2 fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 Output terminals of...

Page 5: ...ction polymer fuse Surge protection varistors Overvoltage protection OVP 16V automatic recovery Excessive discharge protection UVP U 9 5V 5 disconnect of connection battery Tampering protection system...

Page 6: ...protection circuit 100 M 500V DC Operating parameters tab 6 Operating temperature 10 C 40 C see chart 1 Storage temperature 20 C 60 C Relative humidity 20 90 without condensation Vibrations during ope...

Page 7: ...nd green wire coat of the power cable shall stick to one side of the terminal marked with symbol on the PSU enclosure Operation of the PSU without the properly made and fully operational shock protect...

Page 8: ...V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contacts of the relay change over CAUTION...

Page 9: ...o a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5V at the battery terminals will caus...

Page 10: ...l waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the appl...