Setpoint
By
default
the Voltage Output will represent
empty
(
0
volts)
and
100%
of
the operational
span
(
5 volts
), but you may wish to have the output
represent a section of the operational span. For example, the application has
an operational span of 6 metres but the
output
is to
represent
empty
(
0
volts)
to a
level
of
5 metres
(
5 volts)
. If so P834 (Low Level) should be set
to 0.00 metres and P835 (High Level) should be set to 5 metres.
P834 Output Low Level
This parameter sets the level, distance or space, depending on the selected
Output Mode
(
P831
) at which the low voltage output will occur, (
0 VDC
if
Output Range
(
P830
)
= 2),
when using the voltage output.
Default = 0.000m
P835 Output High Level
This parameter sets the level, distance or space, depending on the selected
Output Mode
(
P831
) at which the high voltage output will occur
(
5 VDC
).
Default = 5.700m
Limits
P836 Output Low Limit
This parameter sets the lowest level that the voltage output will drop to, the
default is 0 VDC
, but you can override this if required.
P837 Output High Limit
This parameter sets the highest level that the voltage output will rise to, the
default is 5 VDC
, but you can override this if required.
Trim
P838 Output Low Trim
If the device you are connected to is not calibrated, and not showing the low
value, then you can trim it using this parameter. You can either type in the
offset directly, or use the arrow keys to move the output up and down until
you get the expected result on the device that is connected.
P839 Output High Trim
If the device you are connected to is not calibrated, and not showing the
high value, then you can trim it using this parameter. You can either type in
the offset directly, or use the arrow keys to move the output up and down
until you get the expected result on the device that is connected.