www.pulsar.pl
AWZ101
GREY POWER
5
W
H
D
the PTC resettable fuse, manual restart (the fault requires
disconnection of the DC output circuit)
Battery circuit protection SCP and reverse
polarity connection
F2A - current limitation, F
BAT
fuse (in case of a failure, fuse-
element replacement required)
Over-discharge protection UVP
U<10
V (± 5%) – disconnection (- BAT) of the battery,
Technical output:
- TAMPER - indicates enclosure opening
- a micro switch, NC contacts (enclosure closed),
0,5A@50V DC (max.)
F
BAT
fuse
F
MAIN
fuse
F2A / 250V
T315mA / 250V
Mechanical specifications (tab. 4).
Enclosure dimensions
200 x 230 x 80+8 (WxHxD) [mm] (+/- 2)
Fixing
175 x 203
x Φ 6 x 4szt (WxH)
Fitting battery
7Ah/12V (SLA) max.
165x100x75mm (WxHxD) max
Net/gross weight
1,8 / 2,1 kg
Enclosure
Steel plate DC01, thickness: 0,8mm, colour: RAL 9003
Closing
Cheese head screw (at the front)
Connectors
Outputs:
Ф0,51÷2,5 (AWG 24-12)
Battery outputs: BAT: 6,3F-0,75, 19cm
Operation safety (tab.5).
Protection class PN-EN 60950-1:2007
I (first)
Degree of Protection PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating specifications (tab.6).
Operating temperature
-
10ºC...+40ºC
Storage temperature
-
20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
PN-83/T-42106
Fig. 4. Current-voltage characteristics of the PSU.