background image

www.pulsar.pl   

 

 

 

AWZ101 

 

 

 

          

GREY POWER

 

 
 

Features: 

 

  13,8VDC/1A uninterruptible supply  

  fitting battery: 7Ah/12V 

  mains supply 230VAC 

  linear voltage regulator 

  battery over-discharge protection (UVP) 

  battery charge and maintenance control 

  battery output full protection against short-circuit 

    and reverse polarity connection 

  battery charging current 0,1A 

 

  LED indication 

  protections: 

 

SCP short-circuit  

 

OLP overload  

 

OHP overheat  

 

over voltage  

 

against sabotage 

  warranty 

– 5 year from the production date 

 
 

 
CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors. 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication 
3.2 Technical outputs

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU output  
4.2 Battery-assisted operation 
4.3 Maintenance 
 

 

 
1. Technical description. 
 

1.1 General description. 

A buffer PSU is intended for an uninterrupted supply to alarm system devices requiring stabilized voltage of 

12V DC (+/-15%)

. A linear stabilizing system, which has been used in the unit, provides voltage with a lower level 

of noise and a quicker response to interference when compared to a switched-mode regulator. The PSU provides 
voltage of 

Uout = 12,8V ÷ 13,8V DC 

during buffer operation, with current capacity:  

 
 

 

1. Output current 1A (without a battery) 

 

2. Output current 0,9A + 0,1A battery charge 

 

Total current of the rec battery: 1A max.

 

In case of power decay, a battery back-up is activated immediately. 

The battery is protected against 

over-discharge (UVP). 

The PSU is housed in a metal enclosure which can accommodate a 7Ah/12V battery. It 

features a micro switch (TAMPER) that indicates door opening (front cover). 

 

 
 
CAUTION! 

In case of using the PSU for CCTV, KD, SSWiN devices (or other, of similar application), it 

is recommended to use an over voltage protection module MZN1 in the output circuit of DC power. 
 

 

 

 

 

Summary of Contents for AWZ 101

Page 1: ...AWZ 101 v1 2 AWZ 13 8V 1A 7Ah L Linear Buffer Power Supply Unit EN Edition 5 from 15 05 2014 Supercedes the edition 4 from 13 02 2014 GREY POWER...

Page 2: ...4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to alarm system devices requiring stabilized voltage of 12V DC 15 A linear stabili...

Page 3: ...age in the range of 12V 14 5V 4 5 LED indication AC LED for AC voltage AUX LED for DC output voltage 6 Connectors BAT DC supply output of the battery BAT red BAT black AUX DC supply output AUX U AUX G...

Page 4: ...ating specifications tab 6 Electrical specifications tab 3 PSU type A EPS External Power Source Mains supply 230V AC 10 10 Current consumption 0 16 A max Power frequency 50Hz PSU power 18 W Output vol...

Page 5: ...ess 0 8mm colour RAL 9003 Closing Cheese head screw at the front Connectors Outputs 0 51 2 5 AWG 24 12 Battery outputs BAT 6 3F 0 75 19cm Operation safety tab 5 Protection class PN EN 60950 1 2007 I f...

Page 6: ...230Vac to L N clips of the PSU Connect the ground wire to the clip marked by the earth symbol Use a three core cable with a yellow and green PE protection wire to make the connection Lead the cables...

Page 7: ...nute In the case of a short circuit to the AUX BAT output load 200 250 of the PSU power or a reverse polarity connection the FBAT fuse in the battery circuit becomes permanently damaged and the restor...

Page 8: ...ilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried...