1.2 Block diagram (Fig. 1). 

 

 

Fig. 1. Block diagram of the PSU. 

 

1.3 Description of PSU components and connectors.  

 

Table 1.  Elements of the PSU pcb (see Fig. 2). 

Element no. 

Description 

[1] 

Connector: AC power supply input 

– factory setting 

[2] 

F

BAT

 

fuse in the battery circuit 

– F2A 

[3] 

P1 potentiometer, adjustable DC voltage in the range of 

12V÷ 14,5V 

[4], [5] 

LED indication: 
AC 

- LED for AC voltage

  

AUX 

- LED for DC output voltage 

[6] 

Connectors: 
+BAT- 

DC supply output of the battery (+BAT= red, -BAT=black) 

+AUX- 

DC supply output (+AUX= +U, -AUX=GND) 

 TAMPER -

 contacts of the sabotage protection switch

 

(NC)

 

[7] 

P

BAT

; pins 

- configuration of UVP battery protection function 

 

P

BAT

 

= protection (disconnection) of the battery off 

 

P

BAT

 

= protection (disconnection) of the battery on - page.7 section.4.2

 

[8] 

START

 

– button (launching the PSU from a battery)- page.7 section.4.2 

 

Fig. 2. The view of the PSU pcb. 

Summary of Contents for AWZ 101

Page 1: ...AWZ 101 v1 2 AWZ 13 8V 1A 7Ah L Linear Buffer Power Supply Unit EN Edition 5 from 15 05 2014 Supercedes the edition 4 from 13 02 2014 GREY POWER...

Page 2: ...4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to alarm system devices requiring stabilized voltage of 12V DC 15 A linear stabili...

Page 3: ...age in the range of 12V 14 5V 4 5 LED indication AC LED for AC voltage AUX LED for DC output voltage 6 Connectors BAT DC supply output of the battery BAT red BAT black AUX DC supply output AUX U AUX G...

Page 4: ...ating specifications tab 6 Electrical specifications tab 3 PSU type A EPS External Power Source Mains supply 230V AC 10 10 Current consumption 0 16 A max Power frequency 50Hz PSU power 18 W Output vol...

Page 5: ...ess 0 8mm colour RAL 9003 Closing Cheese head screw at the front Connectors Outputs 0 51 2 5 AWG 24 12 Battery outputs BAT 6 3F 0 75 19cm Operation safety tab 5 Protection class PN EN 60950 1 2007 I f...

Page 6: ...230Vac to L N clips of the PSU Connect the ground wire to the clip marked by the earth symbol Use a three core cable with a yellow and green PE protection wire to make the connection Lead the cables...

Page 7: ...nute In the case of a short circuit to the AUX BAT output load 200 250 of the PSU power or a reverse polarity connection the FBAT fuse in the battery circuit becomes permanently damaged and the restor...

Page 8: ...ilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried...

Reviews: